CONDUIT SCHEDULE CONDUIT SCHEDULE
<br /> TAG( A ) FROM TO SIZE CONDUCTORS NOTES TAG( A ) FROM TO SIZE CONDUCTORS NOTES
<br /> GNO MAIN CB AND RODS 3/4" 116 AWG Cl CONTROL PANEL PUMP ROOM 1" SPARE
<br /> P1 SNOPUD HIGHWAY PL MAIN SWITCHGEAR (3)4" (6)500 KCMIL SKV,(2)500 KCMIL N I SPARE CONDUIT,VIA VAULT C2 CONTROL PANEL PUMP ROOM 1" SPARE
<br /> P2 MAIN SWITCHGEAR A ATE A (2)4" (3)500 KCMIL SKV,(1)NZ AWG G I SPARE CONDUIT C3 CONTROL PANEL SURGE ANTICIPATORS 1" (24)1114
<br /> P3 MAIN SWITCHGEAR A ATS B 1 2 4" 3 500 KCMI SKV N2 A E UT C4 CONTROL PANEL PRESSURE XDCR L" (2)TWP NEE
<br /> P4 ATS A SWITCHGEAR A (2)4" 13)500 KCMIL SKV,(1)N2 AWG G 1 SPARE CONDUIT CS CONTROL PANEL DOOR INTRUSION SWITCHES 1" (4)I114
<br /> P5 ATS B SWITCHGEAR B (2)4" (3)500 KCMIL SKV,(1)42 AWG G 1 SPARE CONDUIT C6 CONTROL PANEL SMOKE DETECTORS 3/4" (4)P14
<br /> P6 FUTURE GENERATOR MTS (6 A C D S AT R C] CONTROL PANEL FLOW METER 1" TWP 1118
<br /> P7 MTS XFMR GEN 16)4" (18)350 KCMIL,16)350 KCMIL N,(6)250 KCMIL G C8 CONTROL PANEL FLOW METER I" (6)P14 FLOW TOTAL,VAULT FLOOD
<br /> PB XFMR GEN SWITCHGEAR GEN (2)4" (3)350 KCMIL SKV,(1)112 AWG G 1 SPARE CONDUIT C9 CONTROL PANEL FUTURE GENERATOR 11/2"
<br /> P9 SWITCHGEAR GEN SWITCHGEAR A 4" (3)350 KCMIL SKV,(1)N2 AWG G CIO CONTROL PANEL FUTURE GENERATOR 1"
<br /> PLO SWITCHGEAR GEN SWITCHGEAR B 4" (3)350 KCMIL SKV,(1)N2 AWG G C11 ASD PI PUMP NI MOTOR BEARINGS 3/4" (4)N14
<br /> PEE SWITCHGEAR B ASD HE 3' (3)N2/0 AWG 5KV,p4AWG G C12 ASO Nl PUMP 111 MOTOR THERMAL 3/4" (2)N14
<br /> P12 SWITCHGEAR A ASD N2 3" (3)42/0 AWG SKY,FAAWG G C13 ASO N1 CONTROL PANEL 1" (8)N14
<br /> P13 SWITCHGEAR B ASO N3 3" (3)N2/0 AWG 5KV,p4AWG G C14 ASO N1 CONTROL PANEL 1" (3)TSP FEB
<br /> P1d SWITCHGEAR A ASO N4 3" (3)R2/OAWG 5KV,N4AWG G C15 ASO 41 CONTROL PANEL I" CAT SE
<br /> P15 SWITCHGEAR A ASO NS 3" (3)N2/0 AWG 5KV,p4AWG G C16 CONTROL PANEL PUMP 42 VALVES 1" (12)1114 SOLENOIDS.PRESSURE SW,LIMIT SW
<br /> PIE SWITCHGEAR A XFMR A 3" (3)N8 AWG 5KV,(1)N10 A C21 ASD N2 PUMP 112 MOTOR BEARINGS 3/4" (4)1114
<br /> P17 SWITCHGEAR B XFMR A 3" (3)118 AWG SKV,(1)1110 G C22 ASO P2 PUMP N2 MOTOR THERMAL 3/4" (2)1114
<br /> P18 XFMR A PANEL A 4" (3)SOO KCMIL,(1)500 KCMIL N,N2 AWG G C23 ASO N2 CONTROL PANEL 1" (8)N14
<br /> P19 PANEL A PANEL R 3" (3)44/0 AWG,(1)4/0 AWG N,12 AWG G C24 ASD N2 CONTROL PANEL 1" (3)TSP N18
<br /> P20 SWITCHGEAR B WALL 3' SPARE C25 AS0112 CONTROL PANEL 1" CAT SE
<br /> P21 ASD NI PUMP NI MOTOR 3" 13)112 AWG 5KV,1/6 AWG G C2G CONTROL PANEL PUMP N3 VALVES 1" (12)N14 SOLENOIDS,PRESSURE SW.LIMIT SW
<br /> P22 ASO N2 PUMP N2 MOTOR 3" (3)N2 AWG 5KV,ER AWG G C31 ASO N3 PUMP 43 MOTOR BEARINGS 3/4" (4)P14
<br /> P23 ASO N3 PUMP N3 MOTOR 3" (3)N2 AWG SKV,46 AWG G C32 ASD n3 PUMP N3 MOTOR THERMAL 3/4" (2)P14
<br /> PIN ASO N4 PUMP N4 MOTOR 3" (31 N2 AWG 5KV,46 AWG G C33 ASO N3 CONTROL PANEL 1" (B)PIN
<br /> P25 ASD PS PUMP A5 MOTOR 3" 13)N2 AWG 5KV,1/6 AWG G C34 ASO n3 CONTROL PANEL 1" (3)TSP 1/18
<br /> P26 PUMP BUILDING ELECTRICAL BUILDING 3" SPARE C35 ASD N3 CONTROL PANEL 1" CAT SE
<br /> P27 PUMP BUILDING ELECTRICAL BUILDING 3" SPARE C36 CONTROL PANEL PUMP ER VALVES 1" (12)414 SOLENOIDS,PRESSURE SW,LIMIT SW
<br /> P28 C41 ASO N4 PUMP d4 MOTOR BEARINGS 3/4" (4)414
<br /> P29 C42 ASO N4 PUMP N4 MOTOR THERMAL 3/4" (2)PIN
<br /> P30 PANEL A f LOW METER CABINET 1" (2)N12 AWG,N12 AWG G C43 ASO N4 CONTROL PANEL 1" (8)1114
<br /> P31 PANEL A ASD NI 1' (2)NIO AWN,NIO AWG G ASO CONTROL POWER C44 ASO 44 CONTROL PANEL 1" (3)TSP N18
<br /> P32 PANEL A ASO 112 I" (2)1110 AWG,NIO AWG G ASO CONTROL POWER CPS ASO N4 CONTROL PANEL 1" CAT SE
<br /> P33 PANEL A ASO N3 1" (2)NIO AWG,N10 AWG G ASD CONTROL POWER CAN CONTROL PANEL PUMP 06 VALVES 1" (12)N14 SOLENOIDS,PRESSURE SW,LIMIT SW
<br /> P34 PANEL A ASOd4 1" (2)N10 AWG,NID AWG G ASO CONTROL POWER C51 ASO NS PUMP PS MOTOR BEARINGS 3/4" (4)Nl4
<br /> P35 PANEL A ASD PS 1" (2)NIO AWG,410 AWG G ASD CONTROL POWER C52 ASO N5 PUMP N5 MOTOR THERMAL 3/4" (2)P14
<br /> P36 PANEL A MTS 1" (2)410 AWG,NIOAWG G PANEL HEATER C53 ASO ES CONTROL PANEL 1" (8)PM
<br /> R P37 PANEL A FUTURE GENERATOR 1" FUTURE BATTERY CHARGER.RECEPTS C54 ASO PS CONTROL PANEL 1" (3)TSP p18
<br /> S P38 PANELA FUTURE GENERATOR 11/2" FUTURE OIL HEATERS C5S ASO NS CONTROL PANEL 1" CAT SE
<br /> P39 PANEL A FLOW METER 1" (2)1110 AWG.AIOAWG G C56 CONTROL PANEL PUMP P5 VALVES 1" (12)N14 SOLENOIDS,PRESSURE SW,LIMIT SW
<br /> 4 P40 C60 EX FIBER HANDHOLE COMM PANEL 3" EX FIBER
<br /> PSI COMM PANEL CAMERAS PUMP BUILDING 2" (6)CAT 6(OUTSIDE PLANT)
<br /> 3 TRANSFORMER SCHEDULE C62 COMM PANEL CAMERAS ELECT BUILDING 1" 12)CAT 6
<br /> TAG KVA PRI SEC EFFICIENCY NOTES
<br /> C63
<br /> A 112.5 2400 V 200Y/120V 97.5% DOUBLE INCOMING LUGS C64 COMM PANEL HANDHOLE 41 2" FIBER OPTIC CABLE
<br /> 6 GEN 1500 480 V 2400V/ 97.5% STEP UP APPLICATION C65 CONTROL PANEL HANDHOLE II1 2" (24)414
<br /> C66 CONTROL PANEL HANDHOLE NI 2" (2)TSP N18
<br /> 1 i C6]
<br /> i^ MOTOR SCHEDULE C68 ATSA FUTURE GENERATOR 2" CAP BEYOND EDGE OF PAVEMENT
<br /> TAG HP VOLT EFFICIENCY NOTES C69 ATSB FUTURE GENERATOR 2'
<br /> L i ODU-1 (2)ID 200V.3PH 94% C70 CONTROL PANEL ATS A I"
<br /> 1 4' ODU-2 (2)10 208V,3PH 31°i. •' - - 4.0100.11101.1.0
<br /> 3R IOU-1 0.3 208V.1PH 92% CBI SWITCHGEAR B ASO N] 3/4" • ',
<br /> IOU-2 0.3 208V,1PH 92% 2 C82 SWITCHGEAR A ASO N2 3/4" (6)N14 SHUNT TRIP,SPARES
<br /> .13 IOU-3 0.3 200V,1PH 92% CO3 SWITCHGEAR R ASO n3 3/4" (6)P14 SHUNT TRIP,SPARES
<br /> :i IDU4 0.3 208V,1PH 92% C84 SWITCHGEAR A ASO. 3/4" 16)P14 SHUNT TRIP,SPARES
<br /> 6 CBS SWITCHGEAR A ASD N5 3/4" (6)P14 SHUNT TRIP,SPARES
<br /> E`2
<br /> x µ\♦, I.,,, . IIII. EVERETT EVERGREEN PUMP STATION ELECTRICAL E11
<br /> 3 Lj OE0322 . ADDENDUM NO o"•., r.«i.� Oar p bhc5 BHCC I( LLC PUBLIC
<br /> 5t.��1
<br /> i La II RV J `d\ [ PUBLIC WORKS MODIFICATIONS
<br /> € ID. DATE APRYo ADDENDUM SUE a/ CONDUIT,TRANSFORMER50 PLANS ISSUED FOR 1 WORK ORDER UP3747-3 //_
<br /> i a Blo AC
<br /> Recono 1{{ AND MOTOR SCHEDULES " 59
<br /> ACTION DATE I APR.i ACTION GATE 1 APAVO ACTION DATE APRVD ,
<br />
|