THESE DRAWINGS ARE THE PROPERTY OF H2O, LLC. ANY REPRODUCTIONS MUST DE AUTHORIZED DY THE ARCHITECT AND MUST DEAR THE NAME OF THE ARCHITECT. O COPYRIGHT <br />2021 5Y H2O, LLC, THESE DRAWINGS ARE PROTECTED DY FEDERAL AND STATE COPYRIGHT LAWS. <br />1. CODES/REGULATIONS: <br />-CONSTRUCTION TO CONFORM TO THE 2015 INTERNATiONAL RESIDENTIAL CODE (1RC), WASHiNGTON STATE LAWS AND REGULATIONS, CURRENT WASHiNGTON STATE RESIDENTIAL <br />ENERGY CODE AND VARIOUS CODES IMPOSED DY LOCAL AUTHORITIES. <br />-A SEPARATE PERMIT MAY BE REQUIRED FOR PLUMBING, ELECTRICAL, AND/OR MECHANICAL WORK AS APPLICABLE. <br />-A COPY OF THE APPROVED PERMIT PLANS MUST DE ON THE JOB SiTE DURING CONSTRUCTION. <br />2. CONTRACTOR'S RESPONSIBILITY: <br />-PRIOR TO CONSTRUCTION, THE CONTRACTOR 15 TO VERIFY ALL DIMENSIONS AND STRUCTURAL MEM13EP SIZES. <br />-DO NOT SCALE CONTRACT DOCUMENTS. <br />-iF ANY DISCREPANCIES iN THE DRAWINGS OR FROM THE CODES ARE NOTED, ARCHITECT iS TO DE NOTIFIED IMMEDIATELY. <br />-ALL CHANGES MADE 5Y THE CONTRACTOR SHALL DE SUDMiTTED iN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION. <br />-THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS, SAFETY PRECAUTiONS, ACTS OR <br />OMISSIONS OR PERFORMANCE OF THE CONTRACTOR. <br />-CONTRACTOR SHALL DE RESPONSISLE FOR THE PERFORMANCE AND WEATHERPROOFING OF THE ENTIRE DUILDING, ITS COMPONENT EQUIPMENT, AND PARTS. <br />-ALL STRUCTURAL SYSTEMS SUCH AS WOOD TRUSSES WHICH ARE TO DE COMPOSED OF COMPONENTS TO DE FIELD ERECTED SHALL DE SUPERVISED BY THE SUPPLIER DURING <br />MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND ERECTION iN ACCORDANCE WiTH INSTRUCTIONS PREPARED DY THE SUFFLER. <br />-ALL WORK MUST FOLLOW CURRENT RRP RULES AND REQUIREMENTS AS DEFINED 5Y THE EPA AND THE STATE OF WASHiNGTON. <br />-ALL WASTE AND REFUSE CAUSED iN CONNECTION WiTH THE WORK SHALL DE REMOVED FROM THE PREMISES AND DISPOSED OF DY THE CONTRACTOR. THE PREMISES SHALL DE LEFT <br />CLEAR AND CLEAN TO THE SATISFACTION OF THE OWNER. <br />-CONTRACTOR SHALL DESIGN AND INSTALL SHORING AS REQUIRED TO PERFORM WORK. ENGINEERING, CONSTRUCTION AND SAFETY OF THE SHORING SHALL BE THE RESPON5151LiTY <br />OF THE CONTRACTOR. <br />-FOR ALL NEW CONSTRUCTION OR ADDITIONS DESIGNED WiTHiN 1'-0" OF THE HEIGHT LIMIT, THE CONTRACTOR SHALL DE RE5PON5iBLE FOR COORDINATING WiTH THE SURVEYOR TO <br />VERIFY THE ELEVATION OF THE STRUCTURE AS iT 15 DEiNG DUILT TO VERIFY ANY ELEVATION D15CRFANCiES THROUGHOUT CONSTRUCTION. ELEVATIONS SHOULD DE VERIFIED FOR <br />EACH FLOOR LEVEL PRIOR TO PROCEEDING WiTH THE NEXT FLOOR OF FRAMING: TOP OF FOUNDATION, TOP OF SUDFLOOR, TOP PLATE AND RiDG-E ELEVATIONS SHOULD DE VERIFIED <br />DURING CONSTRUCTION. CONSULT ARCHITECT FOR CLARIFICATION PRIOR TO CONSTRUCTION. <br />3. WiL <br />-FOUNDATION DESIGN 15 DASED ON AN ASSUMED AVERAGE SOiL DEARiNG OF 2,000 P5F OR PER GEOTECHNiCAL REPORT. ALL FOOTINGS SHALL DE CAST ON UNDI5TURDED FiRM <br />NATURAL SOiL OR COMPACTED 501L OF 2,000 PSF BEARING CAPACITY AT LEAST 1'-6" BELOW LOWEST ADJACENT GRADE, AND FREE OF ORGANIC MATERIALS. FOOTING EXCAVATION <br />SHALL DE FREE OF LOOSE SOILS, DEDRiS, AND FREE WATER AT ALL TIMES. THIS OFFICE TAKES NO RESPONSIBILITY iN VERIFYING THE ACCURACY OF ENGINEERING DATA SUPPLIED <br />BY OTHERS. <br />. ATTIC REQUIREMENTS: <br />-APPLY ROOFING iN ACCORDANCE WiTH IRC CHAPTER 9. PROVIDE ATTIC VENTILATION AS INDICATED ON DRAWINGS AND A5 OUTLINED iN 1RC SEC R806. <br />-THE NET FREE VENTILATING AREA SHALL DE NOT LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED, EXCEPT THAT THE AREA MAY 5E 1/300 PROVIDED AT LEAST 50 <br />PERCENT OF THE REQUIRED VENTILATING AREA 15 PROVIDED DY VENTILATION LOCATED iN THE UPPER PORTION ION OF THE SPACE TO DE VENTILATED AT LEAST 3 FEET ABOVE SAVE OF <br />CORNICE VENTS WiTH THE DALANCE OF THE REQUIRED VENTILATION PROVIDED DY EAVE OR CORNICE VENTS. (iRC SEC R806). <br />-ATTIC ACCESS: MINIMUM 22" x 30" WiTH MiNiMUM 30" HEADROOM, UNODSTRUCTED, READILY ACCESSi13LE OPENING, iRC SEC R807. ACCESS DOORS SHALL DE WEATHERSTRiFFED <br />AND INSULATED TO A LEVEL EQUIVALENT TO THE INSULATION ON THE SURROUNDING SURFACES. <br />1N ROOMS NOT PROVIDED WiTH AN OPERABLE WiNDOW OF 1.5 5Q. FT. OR GREATER, A MECHANICAL VENTILATION SYSTEM CAPABLE OF PROVIDING 5 AiR CHANGES PER HOUR SHALL DE <br />PROVIDED. <br />-VENT DRYER, BATH FANS, AND RANGES/OVENS TO THE OUTSIDE. <br />. VENTILATION: <br />-VENT FANS SHALL TERMINATE AT THE EXTERIOR OF THE BUILDING PER iRC SECTION M1502.3 AND iMC SECTION 501.3. <br />-INSULATE ALL DUCTS OUTSIDE OF CONDITIONED SPACE PER WA STATE ENERGY CODE. <br />-KITCHEN RANGE HOODS: RANGE HOODS CAPABLE OF EXHAUSTING MORE THAN 400 CFM REQUIRE MAKE-UP AiR PER IRG M1503.4. <br />6. GE IG: <br />-TO DE iN COMPLIANCE WiTH iRG SEC R308 AND WASHiNGTON STATE SAFETY GLASS LAW, EXCEPTIONS ARE AS OUTLINED 1N iRG SEC R308. <br />-GLAZING iN LOCATIONS SUBJECT TO HUMAN IMPACT SUCH AS GLASS iN DOORS, GLAZING WITHIN 24" ON EITHER SiDE OF A DOOR OPENING, GLAZING CLOSER THAN 18" TO A FLOOR, <br />SHOWER DOORS AND TUD ENCLOSURES SHALL BE WiRE REINFORCED, TEMPERED GLASS, LAMINATED SAFETY GLASS OR SHATTER RESISTANT PLASTIC. <br />-SLIDING GLASS DOORS TO DE SAFETY GLAZING, LAMINATED OR TEMPERED GLASS. <br />-SHOWER ENCLOSURES SHALL DE APPROVED WiRE REINFORCED, TEMPERED OR LAMINATED SAFETY GLASS OR 5HATTER RESISTANT PLASTIC. <br />-GLAZING WiTHiN 18" OF FLOOR AND GREATER THAN 18" iN LEAST DiMEN51ON SHALL COMPLY WiTH IMPACT LOADS. SEE PLANS. <br />-ALL EXTERIOR WALL GLAZING SHALL DE DOUBLE GLAZED, UNLESS NOTED OTHERWISE, AND COMPLY WiTH STATE OF WASHiNGTON ENERGY CODE. <br />-EGRESS iN EVERY SLEEPING ROOM SHALL HAVE A MiNiMUM NET CLEAR OPENING OF 5.7 5Q. FT. THE MiNiMUM NET CLEAR OPENING HEIGHT DIMENSION SHALL DE 24", MiNiMUM NET <br />CLEAR OPENING WIDTH OF 20" AND A FINISHED SiLL HEIGHT NOT MORE THAN 44" ABOVE THE FLOOR. iRC SEC R310. <br />7. ENERGY- <br />-ALL MATERIALS, WORKMANSHIP AND CONSTRUCTION SHALL CONFORM TO IRG REQUIREMENTS AND THE WASHiNGTON STATE ENERGY CODE, LATEST EDITION. VERIFY ALL CONDITIONS <br />BEFORE PROCEEDING WITH WORK. <br />-APPLICATION AND INSTALLATIONS OF INSULATION AND VAPOR BARRIERS SHALL COMPLY WiTH STATE OF WASHINGTON THERMAL INSULATION STANDARDS. <br />-BUILDING AIR LEAKAGE TESTING, PER SEC 502.4.5,15 REQUIRED PRIOR TO FINAL INSPECTION. THE TEST RESULTS SHALL DE POSTED ON THE RESIDENTIAL ENERGY COMPLIANCE <br />CERTIFICATE. <br />-EACH DWELLING UNiT 15 TO HAVE ONE PROGRAMMABLE THERMOSTAT FOR REGULATION OF TEMPERATURE PER SEC 503.8.1. <br />-A SIGNED AFFADAVIT DOCUMENTING THE DUCT LEAKAGE TEST RESULTS SHALL DE PROVIDED TO THE DUILDING INSPECTOR PRIOR TO AN APPROVED FINAL INSPECTION. <br />-DUCT LEAKAGE TEST RESULTS SHALL BE PROVIDED TO THE DUILDING INSPECTOR AND HOMEOWNER PRIOR TO AN APPROVED FINAL INSPECTION. <br />-MiNiMUM 75% OF PERMANENTLY INSTALLED LAMPS iN LIGHTING FIXTURES SHALL DE HiGH EFFICACY LAMPS PER SEC 404.1. <br />-WHERE THE PRIMARY HEATING SYSTEM 15 A FORCED-AiR FURNACE, AT LEAST ONE THERMOSTAT PER DWELLING UNIT SHALL DE CAPABLE OF CONTROLLING THE HEATING AND <br />COOLING SYSTEM ON A DAiLY SCHEDULE TO MAINTAIN DIFFERENT TEMPERATURE SET POINTS AT DIFFERENT TIMES OF THE DAY. THE THERMOSTAT SHALL ALLOW FO, AT A MINIMUM, <br />A 5-2 PROGRAMMABLE SCHEDULE (WEEKDAYS/WEEKENDS) AND BE CAPABLE OF PROVIDING AT LEAST TWO PROGRAMMABLE SETi3ACKS PER DAY. <br />. STAIRS- <br />-MINIMUM HEADROOM 6-8'; MiNiMUM TREAD 10"; MAXIMUM RISER 7 3/4" <br />-HANDRAIL: REQUIRED AT ALL STAIRS WiTH MORE THAN 4 FISERS PER iRC 311.7.8. MINIMUM 34" AND MAXIMUM 38" ABOVE TREAD NOSING. OPEN SIDES OF STAIRS MORE THAN 30" <br />ABOVE ADJACENT FLOOR SHALL HAVE HANDRAILS AND GUARDRAILS. HANDRAIL TO BE 1 1/4"-2" GROSS SECTIONAL DIMENSION AND 11/2" AWAY FROM WALL. <br />-GUARDRAIL: SHALL DE MiN 36" iN HEIGHT WHERE ADJACENT SURFACE OR GRADE 15 30" OR MORE DELOW. RAILINGS SHALL DE 5PACED TO NOT ALLOW THE PASSAGE OF A 4" <br />SPHERE PER iRC 312.1. <br />-INSTALL FiRE DLOCKiNG AT MiD-STRINGER SPAN AND AT WALL ALIGN STRINGER. <br />-COVER WALLS AND SOFFITS OF USABLE SPACE UNDER STAIR WiTH 5/8" TYPE "X" GYPSUM WALLDOARD. <br />9. INSULATION: <br />-INSULATION TO MEET THE CURRENT WASHINGTON STATE ENERGY CODE REQ'T5 FOR TABLE R402.1.1, TABLE R402.1.3 AND SECTION R402. REFER TO PRESCRIPTIVE TABLE ON SHEET <br />01. <br />-EXISTING WALL AND FLOOR CAVITIES EXPOSED DURING CONSTRUCTION FOUND UNIN5ULATED, OR WITH DAMAGED INSULATION (DISCOLORED, WET, DAMAGED, OR <br />DETERIORATED) SHALL BE FILLED WiTH R-15 INSULATION AT 2X4 FRAMING AND WiTH R-21 INSULATION AT 2X6 FRAMING. REF SEC R503.1.1-EXCEPTION 2.. <br />-WALLS TO DE INSULATED WiTH MiNiMUM R-21 INSULATION. BELOW GRADE WALLS TO DE INSULATED WITH MINIMUM R-21 INSULATION, ALLOW FOR THERMAL DREAK DE T WEEN FLOOR <br />SLAD AND BASEMENT WALL UNLESS NOTED OTHERWISE. <br />-ROOF AND CEILING INSULATED WiTH R-49 BLOWN-iN AT FLAT CEILINGS AND R-38 N.D. DATT AT VAULTED AREAS UNLESS NOTED OTHERWISE <br />-ROOF: ALLOW FOR A MiNiMUM 1" CLEAR DE T WEEN TOP OF INSULATION AND DOTTOM OF SHEATHING FOR VENTING UNLESS NOTED OTHERWISE. <br />-VENTING i5 REQUIRED iN EACH J015T SPACE. WHERE CONTINUOUS VENTING WiTH A J015T SPACE 15 INTERRUPTED DY A HEADER (FOR EXAMPLE AT A SKYLIGHT OR HiP), PROVIDE (2)1 <br />1/2" VENTING HOLES AT THE TOP OF THE RAFTER AT THE HEADER TO ALLOW FOP, CONTINUOUS THRU-VENTING INTO THE NEXT JOIST SPACE UNLESS NOTED OTHERWISE. <br />-FLOORS: INSULATED WiTH R-30 DATT INSULATION OVER UNHEATED SPACE UNLESS NOTED OTHERWISE <br />-SLAB-ON-GRADE: PROVIDE EXTRUDED RiGiD CLOSED CELL R-10 INSULATION. INSULATION TO PROVIDE THERMAL DREAK DETWEEN SLAD AND FOOTING AND RUN FROM THE TOP OF THE <br />SLAD TO THE DOTTOM OF THE FOOTING. INSULATION MAY DE INTERRUPTED FOR 6" EVERY 2-0" TO ALLOW FOP, DOWELING TO TiE SLAD AND FOOTING TOGETHER. UNLESS NOTED <br />OTHERWISE. <br />10. GA GE EPA T IQN: <br />-REQUiRES 1/2" GWD ON THE GARAGE SiDE. 5/8" TYPE'X' GWD WHERE THERE 15 LIViNG SPACE ABOVE. SUPPORTING COLUMNS, WALLS AND BEAMS USE 1/2" GWD PER iRC R302.6 <br />-OPENINGS INTO A GARAGE: OPENINGS INTO A GARAGE SHALL HAVE A SOLID WOOD OR HONEYCOMD-GORE STEEL DOOR NOT LESS THAN 1-3/8" THICK, OR 20-MiNUTE FiRE RATING. <br />DOORS SHALL DE EQUIPPED WiTH A SELF -CLOSING DEVICE PER IRG R302.5.1. <br />11. VAPOR BARRIERS: <br />-AN APPROVED VAPOR DARRiER SHALL BE INSTALLED AT EXTERIOR WALLS AND AT ALL ROOF DECKS, DELOW ENCLOSED JOIST SPACES WHERE CEILING FINISHES ARE DIRECTLY <br />INSTALLED TO JOISTS, AND ANY OTHER WALL OR CEILING SURFACES WHICH RECEIVE INSULATION. THiS VAPOR DARRiER MAY DE A COMPONENT OF THE INSULATION MATERIAL. <br />APPLICATION AND INSTALLATIONS OF INSULATION AND VAPOR DARRiERS SHALL COMPLY WiTH STATE OF WASHiNGTON THERMAL INSULATION STANDARDS. <br />12. FIRE SAFETY: <br />-SMOKE ALARMS/DETECTORS (S.R): SMOKE ALARMS/DETECTORS SHALL DE INSTALLED iN ALL SLEEPING ROOMS, iN THE AREA OUTSIDE THE SLEEPING ROOM AND iN OTHER <br />LOCATIONS PER iRC R314. POWER SOURCE AND INTERCONNECTION PER iRG. <br />CARBON MONOXIDE DETECTORS (C.M.D.): SHALL HAVE AN APPROVED CAR50N MONOXIDE ALARM INSTALLED OUT 51PE OF EACH SLEEPING AREA iN DWELLING UNITS AND iN EACH LEVEL <br />iN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS PER iRC315. SiNGLE STATION CARBON MONOXIDE ALARMS SHALL DE LISTED AS COMPLYING WiTH UL2034 AND SHALL <br />DE INSTALLED iN ACCORDANCE WiTH THiS CODE, NFPA 720-2012 AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br />-CARBON MONOXIDE DETECTION SYSTEMS PER 1RC 315.2 THAT INCLUDE GARDON MONOXIDE DETECTORS AND AUPIDLE NOTIFICATION APPLIANCES, INSTALLED AND MAINTAINED IN <br />ACCORDANCE WiTH THiS SECTION FOR CARBON MONOXIDE ALARMS AND NFPA 720-2012, SHALL DE PERMITTED. THE CARBON MONOXIDE DETECTORS SHALL DE LISTED AS COMPLYING <br />WiTH UL 2075. WHERE A HOUSEHOLD CARBON MONOXIDE DETECTION SYSTEM 15 INSTALLED, IT SHALL BECOME A PERMANENT FIXTURE OF THE OCCUPANCY. <br />13. CERTIFICATE & TESTING <br />- A PERMANENT CERTIFICATE SHALL DE COMPLETED AND POSTED ON OR WiTHiN THREE FEET OF THE ELECTRICAL PISTR1DUTiON PANEL DY THE DUiLDER OR REGISTERED DESIGN <br />PROFESSIONAL. THE CERTIFICATE SHALL BE COMPLETED DY THE DUiLDER OR REGISTERED DESIGN PROFESSIONAL AND SHALL NOT COVER OR ODSTRUCT THE VISi51LITY OF THE <br />CIRCUIT DIRECTORY LADEL, SERVICE DISCONNECT LADEL, OR OTHER REQUIRED LADELS. THE CERTIFICATE SHALL LiST THE PREDOMINANT R-VALUES OF INSULATION INSTALLED IN OR ON <br />CEILING/ROOF WALLS, FOUNDATION (SLAD, DELOW-GRADE WALL, AND/OR FLOOR) AND DUCTS OUTSIDE CONDITIONED SPACES; U-FACTOR5 FOR FENESTRATION AND THE RESULTS <br />FROM ANY REQUIRED DUCT SYSTEM AND DUILDING ENVELOPE AiR LEAKAGE TESTING DONE ON THE BUILDING. WHERE THERE 15 MORE THAN ONE VALUE FOR EACH COMPONENT, THE <br />CERTIFICATE SHALL LiST THE VALUE COVERING THE LARGEST AREA. THE CERTRiFICATE SHALL LIST THE TYPES OF EFFICIENCIES OF HEATING, COOLING, AND SERVICE WATER HEATING <br />EQUPPMEN I . <br />PROJECT OWNER: <br />PERRY & KATHY GRANT <br />522123RD AVE W <br />EVERETT WA 98203 <br />Permit#: R21-05-019 <br />Site Address: 522123RD AVE <br />Owner: GRANT PERKY & KATHY <br />Tenant: [l enNarnel <br />App. Date: 5/10/2021 <br />Proposed Use: RESIDENTIAL ALTERATIONS <br />Description: DECK ADDITION AND OUTDOOR COVERED <br />AREA AT NEW DECK <br />1 r <br />Reviewed BY' - D 0 / �( '. <br />,� <br />PROJECT ARCHITECT: <br />. <br />HEiD1 HELGESON <br />K, <br />ate` <br />Li i <br />PROJECT DESIGNERS: <br />LAUREN GROTH & LiSA MONTALVO Office Set <br />Jab Site Set <br />Fire/Planning <br />& <br />H2O ARCHITECTURE + DESIGN <br />23020 EDMONDS WAY, #113 <br />EDMONDS, WA 98020 <br />STRUCTURAL ENGINEER: <br />DENNiS T iTUS, PE, SE <br />GG ENGINEERING <br />250 4TH AVE 5, STE 200 <br />EDMONDS, WA 98020 <br />425.778.8500 <br />PROJECT DESCRIPTION: <br />DECK ADDITION AND OUTDOOR COVERED AREA <br />PROJECT APPRE55: <br />5221 23RD AVE W <br />TAX LOT NUMDER: <br />00734800002300 <br />LEGAL DESCRIPTION: <br />KENiLWORTH HILLS NO.5 BLK 000 D-00 - ALL TH PTN LOTS <br />UJ <br />23 & 24 SD PLAT LY 5 FDL;COM NE COR LOT 23 TH N29*30 <br />22W ALG E LN LOT 24 5D PLAT 20FT TO TP5 HEREIN DESC <br />LN TH 584*28 46W 170.91FT TAP ON WLY LN LOT 23 51) PT <br />BEING ON CRV RAP PTDEARS 573*14 01W 175FT 5D PT ALSO <br />LiES 4.12FT SELY FR NW GOP, LOT 23 AS MEAS ALG ARC 51) <br />CRV SD PT ALSO DE1NG TERM PT OF HEREIN DESC LN PER <br />DLA 1474 3-95 REC AF NO 9510300642 <br />LAND USE CODE COMPLIANCE T TI TI <br />UJ <br />ZONE: <br />R-5 <br />LOT COVERAGE: <br />LO T AREA: 25,700.4 SF (0.59 ACRES) <br />EXISTING HOUSE: 3,799.8 5F <br />EXISTING UNCOVERED DECK 01 180 SF <br />EXISTING UNCOVERED DECK & STAIRS 02 (DEMO) (303.3 SF) <br />NEW COVERED DECK: 616 SF <br />NEW UNCOVERED & STAIRS DECK: 1517 5F <br />EXi5TiNG & PROPOSED LOT COVERAGE: 6112.8 5F <br />ALLOWED LOT COVERAGE: 25,700.4 SF X 35% 8995.1 SF OK <br />REQ'D SET13ACKS: <br />FRONT: 20' <br />REAR SETBACK: 20' <br />SiDE SETBACK: 5' <br />PARKING: <br />3 EXISTING GARAGE PARKING SPACES TO REMAIN <br />DUILDING HEIGHT <br />DUILDING HEIGHT LIMiT = 30' <br />INFORMATION: <br />REFER TO SHEET A2.0 AND A2.1 FOP, DETAILED <br />�nchma � s Required On I. <br />c, V-.r1fy Approved Building <br />If" BUILDING IS NOT POSITIONED <br />INDICATED, ON APPROVED SITE PLAN, <br />A NEW SITE PLAN SHALL DE UBMX ' <br />APPROVEDICE MADE ON THIS PROJECT UNTIL THE <br />ice of Community, Planning & Economic Development REVISED SITE PLAN HAS,) P.RO <br />Vg <br />PLANNING DEPARTMENT ED - R <br />YS <br />DATE: J0_121UW4 <br />I <br />Additional Permits Are Required <br />For This Project To Include: <br />Plumbing Sprinkler <br />Mechanical Fire Alarm <br />I Electrical <br />PROPANE TANKS, HEAT PUMPS ARID <br />OTHER EQUIPMENT OR APPURTENANCES <br />MAY NOT BE LOCATED iN THE FRONT <br />AND SIDE SETBACKS. PROPANE TANKS <br />REQUIRE ADDITIONAL PERMITS ISSUED <br />BY THE EVERETT FiRE DEPARTMENT <br />PRIOR TO INSTALLATION. <br />THESE DOCUMENTS HAVE NOT BEEN <br />APPROVED FOR THE iSSiJANCE OF <br />PUBLIC WORKS, MECHANICAL, FIRE <br />SUPPRESSION, ftt�OTRICAL OR <br />PLUMING PERMITS. <br />CITY OF EVERETT <br />REVIEWED FOR PERMI-F <br />HEIGHT INFORMATION <br />CREDIT <br />ENERGY INFORMATION <br />NOT REQUIRED - NO NEW CONDITIONED SPACE PROPOSED <br />PRESCRIPTIVE REQUIREMENTS- ALL CLIMATE ZONES <br />LOCATION <br />R-VALUE <br />U-FACTOR <br />FENESTRATION U-FACTOR <br />N/A <br />0.30/0.28 <br />SKYLIGHT U-FACTOR <br />N/A <br />0.50 <br />GLAZED FENESTRATION SHGC <br />N/A <br />N/A <br />CEILING <br />49 <br />0.026 <br />WOOD FRAME WALL <br />211NT <br />OD56 <br />MA55 WALL R-VALUE <br />21/21 <br />0.056 <br />FLOOR <br />30/38 <br />0.029 <br />BELOW GRADE WALL <br />10/15/21 iNT + TD <br />0.042 <br />SLAB R-VALUE AND DEPTH <br />10, 2 FT - <br />N/A <br />01 PROJECT INFORMATION, VICINITY MAP, GENERAL NOTES, AS -BUILT PLANS <br />02 SiTE PLAN <br />A1.0 LOWER FLOOR DEMOLITION PLAN <br />A1.1 MAiN FLOOR DEMOLITION PLAN <br />A1.2 LOWER FLOOR PLAN <br />A1.3 MAiN FLOOR PLAN <br />A1.4 ROOF PLAN <br />A1.5 WINDOW AND DOOR SCHEDULES <br />A2.0 EXTERIOR ELEVATIONS <br />A3.0 DUILDING SECTIONS <br />A4.0 WALL SECTION AND DETAILS <br />A4:1 TYP. DETAILS <br />51.1 STRUCTURAL NOTES <br />51.2 STRUCTURAL SCHEDULES <br />52.1 FOUNDATiONPLAN <br />52.2 ROOF FRAMING PLAN <br />53.1 DECK FRAMING DETAILS <br />54.1 WOOD FRAMING DETAILS <br />55.1 ROOF FRAMING DETAILS <br />/7.77 <br />1 <br />1 <br />/ <br />I <br />W M JKI TEO BLVD <br />i <br />I <br />1 <br />I <br />z <br />�Iw <br />w <br />N <br />w <br />w <br />< <br />I <br /><I <br />w\ <br />� <br />� <br />1 <br />I <br />N <br />( <br />1 <br />o <br />z <br />! <br />/ <br />KENiLWOR <br />H 1 <br />1 <br />I <br />PL <br />1 <br />I <br />\� <br />I <br />I <br />SITE <br />i <br />0 <br />19716 REGISTERED <br />ARCHITECT <br />HEIDI MICHELLE HELGE50N <br />STATE OF VI�A�LIIPlGi0B <br />ARCHiTECTU R E <br />D E 9 I G N <br />23020 11 ,i ' <br />e 98020 <br />rn <br />DATE: 5/5/2021 <br />PERMIT SET <br />PROJECT INFORMATION, <br />VICINITY MAP, GENERAL <br />NOTES, AS -BUILT PLANS <br />AS BUILT - MAIN FLOOR AS BUILT - PARTIAL LOWER FLOOR <br />SCALE:1/8" = 1'-0" <br />SCALE:1/8' = 1'-0" <br />