Laserfiche WebLink
1 . ALL MATERIALS, DE51GN AND CONSTRUCTION SHALL CONFORM TO DRAWINGS, SPECIFICATIONS, THE <br />INTERNATIONAL BUILDING CODE IBC 2016. <br />RISK CATEGORY II <br />2. DE51GN DEAD LOADS <br />ROOF 15 P5F <br />FLOOR 13 P5F <br />3. DESIGN LIVE LOADS <br />ROOF 20 P5F <br />FLOOR 40 P5F <br />4. DE51GN SNOW LOAD <br />FLAT ROOF SNOW LOAD 25 P5F <br />SNOW EXPOSURE FACTOR 1.0 <br />SNOW LOAD IMPORTANCE FACTOR 1.0 <br />THERMAL FACTOR 1.0 <br />5. WIND DE51GN DATA <br />PROCEDURE <br />BA51C WIND SPEED <br />WIND EXPOSURE <br />Kzt FACTOR <br />GCpi <br />G. SEISMIC DE51GN DATA <br />SEISMIC DESIGN CATEGORY <br />SITE 501L CLA551FICATION <br />SEISMIC IMPORTANCE FACTOR <br />DA51C 5FR5 <br />RESPONSE MODIFICATION COEF. <br />ANALY515 PROCEDURE <br />55 <br />51 <br />5d5 <br />5d1 <br />5E15M RESPONSE COEF C5, ULT/ALL <br />DESIGN BASE SHEAR, ULT <br />DIRECTIONAL <br />98 MPH <br />D <br />1.0 <br />0.16 <br />SEE CALC5, SHEET L- I <br />D - DEFAULT <br />1.0 <br />LIGHT FRAMED 5HEARWALL5 <br />G.5 <br />ELF <br />1.338 <br />0.474 <br />1.077 <br />0.577 <br />0.1G5/0.1 15 <br />1.97 K <br />1. THE FOLLOWING SHALL APPLY U.N.O ON THE DRAWINGS. <br />2. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL AND MECHANICAL <br />DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS <br />FOR COMPATIBILITY AND SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. <br />3. STRUCTURAL ELEMENTS NOT DIMEN51ONED ON STRUCTURAL PLANS SHALL BE LOCATED DY THE <br />ARCHITECTURAL PLANS AND DETAILS. ELEVATIONS OF STRUCTURAL ELEMENTS SHALL BE DETERMINED BY THE <br />ARCHITECTURAL WALL SECTIONS, BUILDING SECTIONS AND BUILDING ELEVATIONS. <br />4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND SHALL <br />CHECK ALL DIMENSIONS. ALL D15CKEPANCIE5 SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER AND BE <br />RESOLVED BEFORE PROCEEDING WITH THE WORK, <br />5. COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR 51ZE AND LOCATION OF ALL <br />OPENINGS REQUIRED FOR DUCTS, PIPES, PIPE SLEEVES, ELECTRICAL CONDUITS, AND OTHER ITEMS TO BE <br />EMBEDDED IN CONCRETE OR OTHERWISE INCORPORATED IN STRUCTURAL WORK. <br />G. CONTRACTOR SHALL PROVIDE ALL TEMPORARY BRACING FOR ALL STRUCTURAL COMPONENTS UNTIL FINAL <br />CONNECTIONS HAVE BEEN COMPLETED, <br />7. ALL ERECTION PROCEDURES SHALL CONFORM TO 05HA STANDARDS. ANY DEVIATION MUST BE <br />APPROVED BY 05HA PRIOR TO ERECTION. <br />8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION PROCEDURES INCLUDING <br />LAGGING, SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES IN <br />ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL SAFETY ORDINANCES. <br />9. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL <br />ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. <br />10. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT <br />5PECIFICALLY INDICATED BUT ARE OF 51MILAK CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF <br />CONSTRUCTION SHALL BE USED SUBJECT TO REVIEW BY THE ENGINEER. <br />1 1. ALL DETAILS DESIGNATED AS STANDARD OR TYPICAL SHALL OCCUR IN ADDITION TO ANY OTHER <br />SPECIFIC DETAIL CALLED OUT. <br />1 2. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS 15 GIVEN AS THE BEST <br />PRESENT KNOWLEDGE BUT WITHOUT GUARANTEE OF ACCURACY. WHERE ACTUAL CONDITIONS CONFLICT <br />WITH THE DRAWINGS, THEY SHALL BE REPORTED TO THE ENGINEER 50 THAT THE PROPER REVISIONS MAY BE <br />MADE. MODIFICATION TO DETAILS OF CONSTRUCTION SHALL NOT BE MADE WITHOUT PRIOR WRITTEN <br />APPROVAL OF THE ENGINEER. <br />RENOVATION <br />1. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, MEMBER SIZES AND CONDITIONS BEFORE <br />COMMENCING CONSTRUCTION AND/OR DEMOLITION. 5HOKING SHALL BE INSTALLED TO SUPPORT EXISTING <br />STRUCTURE AS REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. DEMOLITION DEBRIS <br />SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EX15TING STRUCTURE, LIMIT CONSTRUCTION <br />LOADING I(NCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS TO 20 P5F. <br />2. CONTRACTOR SHALL CHECK FOR DRY ROT AT ALL AREAS OF NEW WORK. ALL ROT SHALL DE REMOVED <br />AND DAMAGED MEMBERS SHALL BE REPLACED OR REPAIRED AS DIRECTED BY THE STRUCTURAL ENGINEER <br />OR ARCHITECT, <br />ERAMINC LUMBER <br />1. WOOD FRAMING SHALL CONFORM TO IBC CHAPTER 23 "WOOD",NDS 2018, 5DPW5 2015 AND SHALL BE <br />MARKED IN CONFORMANCE WITH WCLIB STANDARDS:' <br />SAWN LUMBER, TYP U.N.O. <br />JOISTS <br />2x, 3x <br />HEM FIR NO.2, Fb--850 P51 <br />BEAMS <br />4x <br />DOUGLAS FIR/LAKCH NO.2, Fb=900 P51 <br />Gx <br />DOUGLAS FIR/LARCH NO.2, Fb=875 P51 <br />POSTS <br />4x <br />DOUGLAS FIR/LAKCH NO.2, Fc= 1350 P51 <br />Gx <br />DOUGLAS FIR/LAKCH NO.2, Fc=700 P51 <br />TOP AND DOT, PLATES <br />2x, 3x <br />HEM FIR NO.2 <br />5TUD5, BLOCKING <br />2x, 3x <br />HEM FIR NO.2 <br />2. STRUCTURAL SHEATHING SHALL BE APA RATED PLYWOOD GRADE C-D, EXTERIOR GLUE OR STRUCTURAL I, <br />EXTERIOR GLUE IN CONFORMANCE WITH DOC P5-1 OR P5-2. ORIENTED STRAND BOARD (055) OF <br />EQUIVALENT THICKNESS, EXPOSURE RATING AND PANEL INDEX MAY DE SUBSTITUTED FOR PLYWOOD <br />5T UCTURALSHEATHING, TYP U.N.O. <br />LOCATION THICKNESS SPAN INDEX PANEL GRADE EXPOSURE <br />ROOF 1 5/3 2" 3 2/ I G C-D 1 <br />FLOOR 3/4 TAG 48/24 C-D -- - I <br />WALLS 1 5/32" 24/ 1 G C-D I <br />3. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED UNLESS SPECIFICALLY DETAILED OR APPROVED IN <br />WRITING BY THE STRUCTURAL ENGINEER. <br />4. MAXIMUM MOISTURE CONTENT SHALL NOT EXCEED 19 % FOR ALL STRUCTURAL MEMBERS. <br />5. PROVIDE PROPERLY SIZED WASHERS UNDER HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING <br />ON WOOD. <br />G. BOLT HOLES SHALL BE NOMINAL DIAMETER OF BOLT PLUS 1 / 1 6" UNLE55 OTHERWISE NOTED. LAG BOLT <br />PILOT HOLES SHALL BE PRE -DRILLED TO GO% OF THE NOMINAL DIAMETER OF THE LAG DOLT UNLE55 <br />OTHERWISE NOTED, <br />7. ALL FRAMING LUMBER IN CONTACT WITH MASONRY OR CONCRETE SHALL BE PRESSURE TREATED PER <br />AWPA STANDARDS OR WRAPPED WITH (2) LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER. ALL <br />FASTENERS AND CONNECTORS FOR PRESSURE TREATED WOOD SHALL BE CORROSION RESISTANT PER IBC <br />2304. 10.5. <br />8. FRAMING ANCHORS FOR JOISTS, PUKLIN5 AND POSTS SHALL BE "SIMPSON", OR APPROVED EQUAL. <br />APPROVAL MUST BE OBTAINED IN WRITING PRIOR TO INSTALLATION. FILL ALL FASTENER HOLES WITH <br />FASTENER TYPES (NAILS, BOLTS, ETC.), SIZES, AND QUANTITIES AS SPECIFIED DY THE MANUFACTURER. ALL <br />2x JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH 51MP50N "LU5" HANGER. ALL HANGER SHALT_ HAVE <br />MAX NAILING AS SPECIFIED BY SIMPSON. <br />9. WHERE STRAP CONNECTS (2) MEMBERS - CENTER IT ON THE JOINT AND PLACE ONE-HALF OF THE NAILS <br />OR BOLTS IN EACH MEMBER. <br />10. RIM J015T 15 TO BE 2x HF#2 MINIMUM <br />1. CONSTRUCTION SHALL CONFIRM TO IDC 2306 AND AITC "TIMBER CONSTRUCTION MANUAL U.N.O. REFER <br />TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, ELEVATIONS AND OFENING5. <br />2. ROOF AND FLOOR FRAMING. <br />PROVIDE DOUBLE JOISTS AROUND ALL OPENINGS AND UNDER PARALLEL PARTITIONS U.N.O. USE SOLID <br />BLOCKING UNDER PARTITIONS PERPENDICULAR TO JOISTS. PROVIDE SOLID BLOCKING AT ALL BEARING <br />POINTS. REFER TO PLANS AND DETAILS FOR ATTACHMENT OF JOISTS AND RAFTERS TO SUPPORTS AND <br />FLUSH BEAMS. USE 51MP50N J015T HANGERS IN ACCORDANCE WITH PLANS, DETAILS AND NOTES. NAIL ALL <br />MULTI-J015T5 DEAM5 TOGETHER WITH I Od AT 1 2" O.C. STAGGERED. PROVIDE I Od AT 6" O.C. AT RIM TO <br />TOP PLATE CONNECTION. PROVIDE (3) 1 Od AT EA BLOCK BETWEEN JOISTS TO TOP PLATE. <br />PLYWOOD ROOF AND FLOOR SHEATHING SHALL BE LAID UP WITH GRAIN PERPENDICULAR TO SUPPORTS <br />AND NAILED WITH 8d NAILS AT Of O.C. TO FRAMED PANEL EDGES AND 1 2" O.C. TO INTERMEDIATE FRAMING <br />5UPPORT5 - REFER TO PLANS AND DETAILS FOR ADDITIONAL REQUIREMENTS, PROVIDE APPROVED PLYWOOD <br />EDGE CLIPS CENTERED BETWEEN JOISTS AT UNBLOCKED ROOF SHEATHING EDGES. ALL FLOOR SHEATHING <br />EDGES SHALL HAVE APPROVED TAG JOINTS OR SHALL BE SUPPORTED BY 50LID BLOCKING. PROVIDE <br />MINIMUM OF 3/8" EDGE DISTANCE ON ALL NAILS AND 1 /8" EXPANSION J015T DETWEEN ALL PANEL EDGES AND <br />PANEL ENDS OF ROOF AND FLOOR SHEATHING. <br />3. WALL FRAMING. <br />ALL EXTERIOR WALLS SHALL BE 2xG AT 16" O.C. MAX U.N.O, INTERIOR BEARING WALLS SHALL BE 2xG <br />AT 24" O.C. OR 2x4 AT I Of O.C. MAX U.N.O, INTERIOR NON -BEARING WALLS SHALL BE 2x4 AT 24" O.C. <br />U.N.O. PROVIDE (2) STUDS MIN AT THE ENDS OF ALL WALLS, AT EA SIDE OF ALL OPENINGS AND AT BEAM <br />BEARING LOCATIONS. NAIL INDIVIDUAL MEMBERS OF BUILT-UP POSTS WITH (2) ROWS OF I Od AT 1 2" O.C. <br />PROVIDE (2)2x8 MIN HEADERS AT ALL OPENINGS IN STRUCTURAL WALLS U.N.O. SISTER MULTI-MEMDEK <br />HEADERS WITH I Od AT 1 2" O.C. PROVIDE SOLID BLOCKING THROUGH FLOORS TO 5UPPORT5 DELOW AT ALL <br />WOOD POSTS LOCATIONS. ALL STUDS OVER 10'-0" IN HEIGHT SHALL BE BLOCKED WITH CONTINUOUS 50LID <br />BLOCKING AT MID -HEIGHT. <br />ALL WALLS SHALL HAVE DOUBLE TOP PLATES AND SINGLE BOTTOM PLATES. NAIL PLATES TO STUDS <br />WITH (3)1 Od END NAILS. REFER TO TYPICAL DETAIL FOR TOP PLATE NAILING. NAILING AT TOP PLATE SPLICES <br />MAY BE ELIMINATED W/ C5 I Gx32"(L) CENTERED ON THE SPLICE. PROVIDE (3) 1 Od FACE NAILS AT ALL TOP <br />PLATE INTERSECTIONS. <br />ATTACH ALL BOTTOM PLATE5 OF ALL STUD WALLS TO WOOD FRAMING BELOW WITH I Gd NAILS AT 12 <br />O.C. OR 5/8"0 A.B. AT 48" O.C. EMBED 7" MIN IN CONCRETE BELOW, TWO ANCHOR BOLT5 MIN PER WALL <br />U.N.O. LOCATE ONE ANCHOR BOLT BETWEEN 4-1/2" AND 1 2" OF EA END OF PLATE SECTION. PROVIDE <br />3"x3"xO.229" WASHERS AT ALL ANCHOR DOLTS. <br />PROVIDE STRUCTURAL SHEATHING PER NOTES ON EXTERIOR 5URFACE AND GYPSUM WALLBOARD ON <br />INTERIOR 5URFACE U.N.O. REFER TO 5HEARWALL SCHEDULE FOR NAILING REQUIREMENTS FOR STRUCTURAL <br />SHEATHING. FASTEN GWB TO ALL STUDS, POSTS, PLATES AND DLOCKING WITH #Gx I -1 /4 TYPE 5 OR W <br />SCREWS AT 1 2" O.C. PROVIDE 1 /6" EXFAN51ON JOIST BETWEEN ALL PANEL EDGES AND PANEL ENDS OF WALL <br />SHEATHING. <br />WOOD fA5TENEK5 <br />I . FASTENERS AND CONNECTORS SHALL CONFIRM TO IBC 2304. 10 U.N.O. <br />2, NAIL SIZES SPECIFIED ON THE PLANS AND DETAILS ARE DA5ED ON THE FOLLOWING SPECIFICATIONS: <br />5 1 Z E <br />8d <br />TYPE <br />COMMON <br />LENGTH <br />2-1 /2" <br />0 <br />0. 1 3 1 " <br />I Od <br />COMMON <br />3" <br />0.146 <br />1 2d <br />COMMON <br />3-1/4" <br />0. 146" <br />I Gd <br />COMMON <br />3-1/2 <br />0. 1 G2" <br />3. ALTERNATE NAILS SHALL BE SUBMITTED TO ENGINEER FOR REVIEW AND APPROVAL PRIOR TO <br />CONSTRUCTION. <br />4. STRUCTURAL SHEATHING: NAILS SHALL BE DRIVEN FLUSH WITH FACE OF SHEATHING; NO <br />COUNTERSINKING IS PERMITTED. <br />EOUNDATION5 <br />1. THE FOUNDATION DE51GN 15 BASED ON THE RECOMMENDATION IN THE INTERNATIONAL BUILDING CODE <br />TADLE 180G.2. FOUNDATION WORK SHALL BE PERFORMED IN ACCORDANCE WITH CHAPTER 18 OF THIS <br />CODE, <br />2. THE FOUNDATION DE51GN 15 BASED ON THE FOLLOWING VALUES: <br />ALLOW. SOIL BEARING 1 500 P5F <br />501L FRICTION .35 <br />EQUIV. FLUID PRESSURES <br />ACTIVE PRESSURE N/A <br />PASSIVE PRESSURE N/A <br />3. ALL FOOTINGS SHALL BE FOUNDED AT LEAST 1 8" BELOW THE UNDISTURBED GROUND 5URFACE OR TO <br />FROST DEPTH. ALL FOOTINGS SHALL BE FOUNDED ON COMPACTED FILL OR UND15TUKDED NATURAL GRADE <br />UNLESS OTHERWISE NOTED. <br />4. COMPACTION: MATERIAL FOR FILLING AND DACKFILLING SHALL CON515T OF THE EXCAVATED MATERIAL <br />AND/OR IMPORTED BORROW AND SHALL BE FREE OF ORGANIC MATTER, TRASH, LUMBER, OR OTHER DEBRIS. <br />ALL WALLS SHALL BE ADEQUATELY BRACED PRIOR TO BACKFILLING. FILL AND BACKFILL SHALL BE DEPOSITED <br />IN LAYERS NOT TO EXCEED 8 INCHES THICK, PROPERLY M015TENED TO APPROXIMATE OPTIMUM <br />REQUIREMENTS AND THOROUGHLY ROLLED OR COMPACTED WITH APPROVED EQUIPMENT IN SUCH A <br />MANNER AND EXTENT AS TO PRODUCE A RELATIVE COMPACTION OF 90% OF MAXIMUM P0551DLE DENSITY <br />A5 DETERMINED BY A5TM D 1557. HAND TAMPERS SHALL WEIGH AT LEAST 50 POUNDS EACH AND SHALL <br />HAVE A FACE AREA NOT IN EXCESS OF G4 SQUARE INCHES. NAND TAMPERS MAY BE OPERATED EITHER <br />MANUALLY OR MECHANICALLY AND SHALL BE USED WHERE LARGER POWER DRIVEN COMPACTION EQUIPMENT <br />CANNOT BE USED. STRUCTURAL FILL OVER 1 2" DEEP SHALL COMPLY WITH A GEOTECHNICAL REPORT, <br />5. IF 501L5 ARE FOUND TO BE OTHER THAN ASSUMED, NOTIFY THE STRUCTURAL ENGINEER. <br />I. ALL CONCRETE UNLESS OTHERWISE NOTED SHALL BE REGULAR WEIGHT HARD ROCK TYPE ( 150 PCF) <br />AGGREGATES SHALL CONFORM TO ASTM C33 WITH PROVEN SHRINKAGE CHARACTERISTICS OF LE55 THAN <br />0.05%. <br />2. ALL CONCRETE DESIGN 15 BASED ON A 28 DAY COMPRESSIVE STRENGTH (f'c) OF 2500 PSI. WHERE <br />3000 PSI CONCRETE IS REQUIRED BY THE BUILDING DEPARTMENT FOR WEATHERING PURPOSES ONLY, NO <br />SPECIAL INSPECTION 15 REQUIRED. <br />3. CONCRETE EXPOSURE CATEGORIES ARE F 1, 50, WO, C 1. <br />4. CEMENT SHALL CONFORM TO ASTM C 150, TYPE I, C5A NORMAL.. <br />5. MAXIMUM SLUMP SHALL NOT EXCEED 4 INCHES IN FLATWORK. <br />G. MIXING, PROPORTIONING AND PLACEMENT OF CONCRETE SHALL DE IN CONFORMANCE WITH ACI 3 16 AND <br />ACI 301 . <br />7. MINIMUM CONCRETE COVERAGE OF REINFORCING STEEL FOR FORMED WORK SHALL BE AS FOLLOWS: <br />EXTERIOR WALLS, EXPOSED TO WEATHER: I %2" <br />EXP05ED TO EARTH OR WEATHER (#5 OR SMALLER): I %2" <br />EXP05ED TO EARTH OR WEATHER (#G OR LARGER): 2" <br />NOTE: CONCRETE CAST AGAINST GROUND SHALL HAVE 3" MINIMUM COVERAGE <br />8. PIPES OTHER THAN ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE EXCEPT <br />WHERE 5PECIFICALLY APPROVED. <br />9. CONCRETE MIXES SHALL BE PROVIDE RD 1N ACCORDANCE WITH ACI 3 18 (WHEN STRENGTH DATA FROM <br />TRIAL BATCHES OR FIELD EXPERIENCE ARE NOT AVAILADLE). <br />CEMENT CONTENT <br />SACKS PEP, <br />LDS/CUBIC YARD CUBIC YARD <br />F'c (P51) (MINIMUM) (MINIMUM) <br />2500 (no special inspection) 5 1 7 5-1/2 <br />MIXES SHALL BE PROPORTIONED TO PRODUCE A SLUMP OF 5" OR LESS. NO MORE THAN A I " PLUS <br />TOLERANCE SHALL BE ALLOWED. <br />DESIGN MIX (OTHER THAN AS SPECIFIED IN THIS TABLE) SHALL BE SUBMITTED TO THE BUILDING OFFICIAL <br />TWO WEEKS PRIOR TO FIR5T USE. <br />a,o*stb' 3y: <br />ME <br />� O <br />v <br />S�N__ n <br />E <br />O <br />O <br />w <br />O <br />z <br />CJ <br />0 <br />n <br />Lu <br />Lu <br />Lu <br />wa <br />u Al', <br />,UP <br />k <br />& <br />EXP.07/17/2022 <br />DATE: <br />1 -""7/2 <br />PROJECT #: <br />GENERAL <br />5TRUCTURAL <br />T <br />5-1.0 <br />3Gx24 (Arch D) <br />