4/6/2022 Page 1 <br /> City of Everett <br /> 7:03:43AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E2201-108 Site Address 7414 HEATHER WAY <br /> Applied 1/17/2022 Applicant SEATOWN ELECTRIC(ELEC)CORP Lot <br /> Approved 1/18/2022 Owner WALKER JAREN/WALKER EDISON R JR&ROBIN Block <br /> Issued 1/18/2022 Contractor SEATOWN ELECTRIC(ELEC)CORP Tract <br /> Parent Permit No. Description Partial Rewire of Circuits,Power to Outbuilding <br /> Notes Kitchen,Bathroom and Exterior Circuits <br /> Scheduled Completed Tune Inspector Result Remarks Inspector's Comments <br /> 2/28/2022 2/28/2022 ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection 2/24/2022 1:57 PM SEATOWN <br /> Request ELECTRIC(ELEC)CORP <br /> (360)551-1776 <br /> Contact Name:Riley Curtis-Stroder <br /> Site Address:7414 HEATHER WAY <br /> Phone:3605511776 <br /> e-Mail:permits@seatownservices.com <br /> (2/28/2022 1:23 PM SKB) <br /> Lights and outside receptacle can't be on <br /> with the 2 small appliance circuits in the <br /> kitchen.Outside front receptacle should be <br /> GFCI protected.Living room and living <br /> room receptacle should be AFCI protected. <br /> Not sure about second kitchen. <br /> 2/28/2022 2/28/2022 ELEC 02-GROUND SKB APPROVAL (2/28/2022 1:23 PM SKB) <br /> WORK House to shed. <br /> 4/5/2022 4/5/2022 ELEC 09-FINAL SKB APPRVD-PERK as noted 4/1/2022 9:51 AM SEATOWN <br /> ELECTRIC(ELEC)CORP <br /> Contact Name:Riley Curtis-Stroder <br /> Site Address:7414 HEATHER WAY <br /> Phone:3605511776 <br /> e-Mail:permits@seatownservices.com <br /> (4/5/2022 1:14 PM SKB) <br /> Second kitchen status unresolved. <br /> INSP12 <br /> SYSTEMS <br />