4.7. Retaining Walls <br /> 4.7.1.Lateral Soil Pressures <br /> The lateral soil pressures acting on retaining walls will depend on the nature and density of the soil behind <br /> the wall, the amount of lateral wall movement that occurs as backfill is placed, and the inclination of the <br /> backfill surface. For walls that are free to yield at the top at least two-thousandths of the height of the wall <br /> (i.e., wall height times 0.002), soil pressures will be less than if movement is restrained. We recommend <br /> that"free" walls supporting horizontal backfill be designed using an equivalent fluid density of 35 pcf, and <br /> restrained walls be designed using an equivalent fluid density of 55 pcf. The above-recommended lateral <br /> soil pressures do not include the effects of sloping backfill surfaces or surcharges such as traffic loads or <br /> other surface loading.The equivalent fluid density should be increased to 50 pcf fora 2H:1V sloping backfill <br /> for unrestrained walls. <br /> We recommend a rectangular seismic surcharge;of 8H psf and 15H psf for the yielding and non-yielding <br /> wall conditions, respectively,where H is the height of the wall. <br /> 4.7.2.Wall Backfill <br /> All backfill for retaining walls should consist of structural fill as described previously with the exception that <br /> care should be taken to prevent the buildup of excessive lateral soil pressures due to overcompaction of <br /> the backfill behind the wall.This can be accomplished by placing the backfill located within about 5 feet of <br /> the wall in lifts not exceeding 6 inches in loose thickness and compacting this zone with hand-operated <br /> compaction equipment. <br /> 4.7.3.Wall Drainage <br /> The recommended equivalent fluid density assumes a free-draining condition behind the wall. Permanent <br /> drainage systems should be provided to collect water and prevent the buildup of hydrostatic pressure <br /> against the wall.We recommend that the drainage system consist of(1)a 2-foot-wide zone of free-draining <br /> backfill against the back of the wall or(2)a prefabricated geocomposite wall drain.The free-draining backfill <br /> should consist of Gravel Backfill for Drains as shown in Figure 3.A perforated drainpipe having a minimum <br /> diameter of 4 inches should be placed in the granular fill or in the bottom of the prefabricated drain at the <br /> base of walls for the entire length. <br /> 4.8. Pavement Considerations <br /> The pavement subgrade area should be proofrolled and evaluated by the geotechnical engineer prior to <br /> placing base course. It is critical that all construction traffic be kept off the silty subgrade soils during wet <br /> weather to prevent disturbance(rutting and weaving)from occurring.We recommend the minimum 6-inch- <br /> thick gravel base contain less than 5 percent passing the U.S. No.200 sieve to perform as a drainage layer <br /> between the silty soils and the pavement section. The minimum thickness is not intended to serve as a <br /> working surface for construction traffic during wet weather. Additional subbase will likely be required if <br /> earthwork and site grading is not completed during the dry season. <br /> GEOENGINEERS� November 14,2019 Page 10 <br /> File No.2095-019-07 <br />