<br />LIGHTING CONTROL AND CONTROLLED
<br />RECEPTACLES SCHEDULE
<br />MOTION SENSOR
<br />OCCUPANT CONTROL, "ON'
<br />LOCAL SWITCH
<br />RECEPTACLE
<br />CONTROL ZONES WITHIN ROOM
<br />DAYLIGHT ZONE
<br />THRESHOLD (FC)
<br />NOTES
<br />USAGE I�D.
<br />USAGE DESCRIPTION
<br />TYPE
<br />FUNCTION
<br />CAPABILITIES
<br />CONTROLS
<br />N/A — AMBIENT LIGHTING,
<br />TYPE B4, A7 AND AMBIENT LIGHTING CAN USE SAME
<br />LOCATE DIMMER SWITCHES
<br />WITH PILOT INDICATOR LIGHTS
<br />A
<br />ATRIUM
<br />PIR
<br />AUTO 'ON'
<br />CONTINUOUS DIMMING
<br />N/A
<br />MOTION SENSOR,
<br />20
<br />AT RECEPTION DESK®
<br />DISPLAY/ACCENTS
<br />ALL CONTROL ZONES
<br />HAVE SEPARATE DIMMER SWITCHES
<br />B
<br />AUDITORIUM
<br />PIR
<br />AUTO 'ON'
<br />CONTINUOUS DIMMING
<br />N/A
<br />STAGE LIGHTING NORMALLY OFF, AMBIENT STADIUM
<br />'ON'.
<br />20
<br />LOCATED IN BOOTHS
<br />(291, 292). ARCH TO DETERMINE
<br />SEATING AND FLOOR LIGHTING ARE AUTO
<br />WHICH ROOM,
<br />C
<br />BREAKROOM/LOUNGE
<br />DT
<br />AUTO 50% 'ON',
<br />MANUAL 100% 'ON'
<br />ON/OFF
<br />OCCUPANCY
<br />AUTO 50% 'ON' FOR AMBIENT LIGHTING.
<br />UNDERCABINET LIGHTING HAS OWN ON/OFF WALL SWITCH.
<br />20
<br />D
<br />CLASSROOM/TRAINING
<br />DT
<br />AUTO 50% 'ON',
<br />MANUAL 100%
<br />CONTINUOUS DIMMING
<br />OCCUPANCY
<br />ALL CONTROL ZONES HAVE SEPARATE DIMMER SWITCHES.
<br />40
<br />E
<br />CONFERENCE/MELTING
<br />DT
<br />AUTO 50% 'ON',
<br />CONTINUOUS DIMMING
<br />OCCUPANCY
<br />ALL CONTROL ZONES HAVE SEPARATE DIMMER SWITCHES.
<br />40
<br />MANUAL 100% ON
<br />F
<br />COPY/PRINT ROOM
<br />DT
<br />MANUAL 'ON'
<br />ON/OFF
<br />OCCUPANCY
<br />AMBIENT AND UNDERCABINET LIGHTING HAVE SEPARATE
<br />40
<br />ON/OFF WALL SWITCHES®
<br />CORRIDOR
<br />DT
<br />AUTO 'ON'
<br />N/A
<br />OCCUPANCY
<br />EACH CONTROL ZONE CONTROLLED BY ITS OWN MOTION
<br />20
<br />FLOOR LAMPS HAVE OWN ON/OFF SWITCH AND POWERED
<br />G
<br />COMPUTER ROOM
<br />DT
<br />AUTO 50% 'ON',
<br />'ON'
<br />ON/OFF
<br />N/A
<br />SENSOR.
<br />40
<br />BY CONTROLLED RECEPTACLES.
<br />SET MOTION SENSOR
<br />TIME OUT DELAY TO 30 MINUTES.
<br />H
<br />MANUAL 100%
<br />ELECTRICAL/MECHANICAL
<br />N/A
<br />MANUAL 'ON'/OFF
<br />ON/OFF
<br />N/A
<br />MANUAL LINE VOLTAGE TOGGLE SWITCH FOR EACH TYPE
<br />OF POWER (NORMAL AND EMERGENCY)
<br />30
<br />FOOD PREPARATION (KITCHENETTE)
<br />FOOD PREPARATION (KITCHEN, CATERING)
<br />DT
<br />DT
<br />MANUAL 'ON'
<br />AUTO 'ON'
<br />ON/OFF
<br />ON/OFF
<br />N/A
<br />N/A
<br />AMBIENT AND UNDERCABINET LIGHTING HAVE SEPARATE 60
<br />ON/OFF WALL SWITCHES.
<br />AMBIENT AND UNDERCABINET LIGHTING HAVE SEPARATE 60
<br />ON/OFF WALL SWITCHES.
<br />SET MOTION SENSOR
<br />TIME OUT DEL( 'TO 30 MINUTES,
<br />J2
<br />AUTO 50% 'ON%
<br />AUTO 50% 'ON' FOR AMBIENT LIGHTING,
<br />K
<br />LIBRARY
<br />DT
<br />MANUAL 100% 'ON'
<br />ON/OFF
<br />OCCUPANCY
<br />TABLE LAMPS HAVE OWN ON/OFF SWITCH AND POWERED
<br />40
<br />RECEPTION
<br />OFFICE, ENCLOSED
<br />DT
<br />DT
<br />AUTO 'ON'
<br />MANUAL 'ON'
<br />CONTINUOUS DIMMING
<br />CONTINUOUS DIMMING
<br />N/A
<br />OCCUPANCY
<br />BY CONTROLLED RECEPTACLES.
<br />SEPARATE DIMMER SWITCHES FOR EACH CONTROL GROUP.
<br />25
<br />40
<br />SET MOTION '-SENSOR
<br />TIME OUT DELAY TO 30 MINUTES.
<br />L
<br />M
<br />N
<br />OFFICE, OPEN PLAN
<br />DT
<br />AUTO 50% 'ON',
<br />MANUAL 100% 'ON'
<br />ON/OFF
<br />OCCUPANCY
<br />40
<br />SET MOTION SENSOR
<br />TIME OUT DELAY TO 30 MINUTES,
<br />01
<br />RESTROOM (TOILETS, VANITIES)
<br />RESTROOM (SHOWERS)
<br />DT
<br />PIR
<br />AUTO 'ON'
<br />AUTO 'ON'
<br />N/A
<br />ON/OFF
<br />N/A
<br />N/A
<br />PROVIDE WET LOCATION MOTION SENSOR FOR EACH
<br />30
<br />30
<br />SET MOTION SENSOR
<br />ION SENSOR
<br />SET MOTION
<br />TIME OUT DELAY TO 30 MINUTES,
<br />TIME OUT DELAY TO 30 MINUTES.
<br />02
<br />STAIRWELL
<br />DT
<br />50% ALWAYS 'ON'
<br />'ON'
<br />N/A
<br />N/A
<br />SHOWER STALL.
<br />40
<br />TYPE 85 HAS INTEGRAL MOTION SENSOR AND STEP
<br />p
<br />STORAGE/JANITORIAL
<br />DT
<br />100% AUTO
<br />MANUAL 'ON'
<br />ON/OFF
<br />N/A
<br />20
<br />DIMMING.
<br />Q
<br />GYMNASIUM
<br />DT
<br />AUTO 50% 'ON',
<br />'ON'
<br />ON/OFF
<br />N/A
<br />30
<br />R
<br />MANUAL 100%
<br />PHYSICAL THERAPY
<br />DT
<br />AUTO 50% 'ON',
<br />'ON'
<br />ON/OFF
<br />OCCUPANCY
<br />30
<br />FLOOR LAMPS HAVE OWN ON/OFF SWITCH AND POWERED
<br />MANUAL 100%
<br />BY CONTROLLED RECEPTACLES.
<br />T
<br />POST OFFICE/MAIL ROOM
<br />LAUNDRY/WASHING
<br />DT
<br />DT
<br />AUTO 50% 'ON',
<br />MANUAL. 100% 'ON'
<br />AUTO 50% 'ON',
<br />'ON'
<br />ON/OFF
<br />ON/OFF
<br />N/A
<br />N/A
<br />AUTO 50% 'ON' FOR AMBIENT LIGHTING,
<br />UNDERCABINET LIGHTING HAS OWN ON/OFF WALL SWITCH.
<br />40
<br />40
<br />U
<br />EXTERIOR: WALKWAYS , PARKING AND
<br />EXTERIOR
<br />PHOTOCELL AND
<br />MANUAL 100%
<br />AUTO 'ON'/OFF
<br />N/A
<br />N/A
<br />ALL NORMAL EXTERIOR LIGHTING CONTROLLED TOGETHER,
<br />10
<br />x
<br />DRIVES, PLAZA
<br />TIMECLOCK
<br />AND TURNED OFF BETWEEN MIDNIGHT AND 6:00 kMv
<br />FIXTURE WITH INTEGRAL PHOTOCELL, FIXTURE OFF DURING
<br />xx
<br />EXTERIOR: ENTRIES
<br />PIR, PHOTOCELL
<br />AUTO 'ON'/OFF
<br />N/A
<br />N/A
<br />DAYLIGHT HOURS, 50% DIMMING AT NIGHT WITH MOTION
<br />SENSOR TO FULL LIGHT OUTPUT AND 15 MINUTE TIME
<br />10
<br />FIXTURE ABOVE DOORS SHALL HAVE UNSWITCHED
<br />EMERGENCY POWER.
<br />DELAY TO DIMMED STATE.
<br />ME MR. IMAM! MEMO! �11 I 111'1W`
<br />FOR LIGHTING CONTROLS THAT INCLUDE DAYLIGHT OR OCCUPANT
<br />SENSING AUTOMATIC CONTROLS, AUTOMATIC SITU T—OFF CONTROLS,
<br />OCCUPANCY SENSORS, OR AUTOMATIC TIME SWITCHES: THE
<br />LIGHTING CONTROLS SHALL BE TESTED, CALIBRATED AND ADJUSTED,
<br />SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT
<br />THEY OPERATE IN ACCORD WITH SPECIFICK-11IONS AND APPROVED
<br />PLANS, AND A COMPLETE REPORT OF TEST PROCEDURES AND
<br />RESULTS SHALL BE FILED WITH THE OWNER IN ACCORDANCE WITH
<br />WASHINGTON STATE ENERGY CODE SECTION C408, COMMISSIONING
<br />TO BE PERFORMED BY A QUALIFIED COMMISSIONING AUTHORITY.
<br />ALL PHOTOELECTRIC CONTROLLER COMMISSIONING SHALL BE
<br />PERFORMED WITHOUT EXTERIOR NATURAL LIGHT CONTRIBUTION.
<br />FOR ALL SPACES INDICATED ON THE LIGHTING CONTROL
<br />SCHEDULE, DESIGN AND PROVIDE A COMPLETE AND FULLY
<br />FUNCTIONING LIGHTING CONTROL SYSTEM. EACH SPACE
<br />SHALL INCLUDE SUFFICIENT QUANTITY OF CONTROL DEVICES,
<br />INCLUDING BUT NOT LIMITED TO SWITCHES, DIMMERS,
<br />PHOTOCELLS, OCCUPANCY SENSORS, CONTACTORS,
<br />TIMECLOCKS AND POWER PACKS, TO MEET ALL OF THE
<br />LIGHTING CONTROL SCHEDULE REQUIREMENTS.
<br />2. ALL MOTION SENSORS TO TIME OFF AFTER 15 MINUTES OF
<br />NON —ACTIVITY UNLESS OTHERWISE NOTED.
<br />3, ALL LIGHTING CONTROL EQUIPMENT SHALL BE COMPLIANT
<br />WITH CURRENT WASHINCTON STATE ENERGY CODE (WSEC)
<br />REQUIREMENTS.
<br />4, ENSURE DIMMING FIXTURE'S DRIVER/POWER SUPPLY IS
<br />COMPATIBLE WITH LIGHTING CONTROL SYSTEM FOR OPTIMAL
<br />PERFORMANCE.
<br />6. PROVIDE POWER PACK RELAY WHEN ONLY ON/OFF LIGHTING
<br />CONTROL IS REQUIRED FOR ONE SWITCHLEG WITH MOTION
<br />SENSING.
<br />7, PROVIDE ROOM CONTROLLER WHEN DIMMING (STEP OR
<br />0-10V), DAYLIGHT HARVESTING, AND/OR MULTIPLE
<br />SWITCHLEGS ARE REQUIRED WITH MOTION SENSING.
<br />8. ALL DIMMING CONTROL NOT INTEGRAL TO THE FIXTURE
<br />REQUIRES A ROOM CONTROLLERA
<br />9s ALL LOW VOLTAGE SWITCHES REQUIRE A POWER PACK OR
<br />ROOM CONTROLLER.
<br />10. MOTION SENSORS AND/OR PHOTOCELL CONTROLS INTEGRAL
<br />TO THE FIXTURE PROVIDED BY LIGHT FIXTURE
<br />MANUFACTURER UNLESS NOTED OTHERWISE. SEE LUMINAIRE
<br />SCHEDULE.
<br />11. DAYLIGHT SENSING CONTROLS SHALL DIM CONTINUOUSLY
<br />AND COMPLETELY SHUT OFF ALL CONTROLLED LIGHTS IN
<br />THE LIGHTING ZONE®
<br />12. PROVIDE DEDICATED NEUTRAL FOR EACH LIGHTING CIRCUIT.
<br />SHARING NEUTRALS SHALL NOT BE ALLOWED.
<br />11 LOCATE ALL POWER PACK RELAYS/LOW VOLTAGE ROOM
<br />CONTROLLERS FOR ROOMS IN CLOSEST ACCESSIBLE CEILING
<br />AREA NEAR THE ROOM DOORWAY. POWER PACK
<br />RELAYS/LOW VOLTAGE ROOM CONTROLLERS FOR HALLS ARE
<br />LOCATED NEAR THE MOTION SENSOR IN THE CLOSEST
<br />DOORWAY WITH AN ACCESSIBLE CEILING AREA, THESE
<br />LOCATIONS ARE FOR EASE OF LOCATING FOR MAINTENANCE
<br />PURPOSES.
<br />14o ALL DUAL —TECHNOLOGY MOTION SENSORS SHALL BE WALL
<br />MOUNTED. POSITION SENSOR TO AVOID CABLE
<br />TRAY/DUCTWORK FOR A CLEAR VIEW OF THE ROOM. ALSO
<br />AIM SENSOR TO ONLY REGISTER ACTIVITY WITHIN THE ROOM
<br />(AVOID PIR VIEWING THROUGH DOORWAY).
<br />15. LIGHTING CONTROL SYSTEM PROGRAMMING AND OWNER
<br />TRAINING SHALL BE INCLUDED AS PART OF THE
<br />CONTRACTOR BASE BID.
<br />91
<br />PIR
<br />US
<br />SD
<br />CONT
<br />N/A
<br />FC
<br />DUAL TECHNOLOGY (INFRARED/ULTRASONIC) MOTION
<br />SENSOR
<br />PASSIVE INFRARED MOTION SENSOR
<br />ULTRASONIC MOTION SENSOR
<br />STEP —DIMMING (STEP —DIM DRIVER OR MULTIPLE DRIVERS)
<br />CONTINUOUS DIM
<br />NOT APPLICABLE
<br />FOOTCANDLE
<br />Otak Architects, Inc
<br />808 SW Third Avenue, Suite 800
<br />Portland, R97204
<br />main 503.287.6825
<br />www.otak.com
<br />(206) 243-5022 www.elcon.com
<br />16300 CHRISTENSEN ROAD, STE 330
<br />SEATTLE, WA 98188
<br />CONSULTANT
<br />_TITLE
<br /># DATE DESCRIPTION
<br />REVISIONS
<br />CMS SAB
<br />DRAWN BY CHECK BY
<br />100% ISSUE SET/BID SET
<br />STATUS
<br />4/17020
<br />DATE
<br />328801
<br />PROJECT NUMBER
<br />E8w0l
<br />@ 2020 OTAK, INC,
<br />ITO,
<br />If this drawing is not 24" x 36", it has been
<br />reduced/enlarged. Scale accordingly.
<br />
|