Laserfiche WebLink
Reference Drawing in Response to Comment Uv <br />a <br />tB1z. <br />Al A <br />SCALE: 1/8" ®1' 0" 0 4' 8' 16' <br />0 SHEET KEYNOTES: <br />1. DOMESTIC WATER LINES ROUTED UP INSIDE PLUMBING CHASE TO <br />SERVE UPPER LEVEL RESTROOMS. <br />2. LAUNDRY ROOM SHALL INCLUDE WASHING MACHINE (WITH PLUMBING <br />CONNECTIONS) AND CLOTHING DRYER (WITH EXHAUST DUCT ROUTED <br />TO OUTDOORS). <br />3. RELOCATE 1-112" COMPRESSED AIR PIPING TO AVOID NEW <br />STRUCTURAL SHEAR WALL. MINIMIZE AND COORDINATE OUTAGE <br />WITH BUILDING OWNER. <br />4, SEE DIAGRAM 4/P7.01 FOR WORK IN FIRE RISER ROOM 077, <br />5. WASTE STANCHION FOR FIRE RISER TEST DRAIN. <br />6. 2" OVERFLOW RAINLEADER. <br />7. SEE SHEET E7.04 FOR PLUMBING DIAGRAMS. <br />3. DO NOT PLACE ANY PIPING IN DATA CENTER OR UPS. <br />9. DISCHARGE VIA AIR GAP INTO FLOOR SINK. <br />10. DISCHARGE INTO TAILPIECE OF SINK. <br />11. 3/4"HW DN TO SERVE PJA SINK AND DISH WASHER. SEE 3/P5.01 FOR <br />DISHWASHER DETAIL. <br />12. TIE WASTE FROM DISH WASHER INTO TAILPIECE OF PJA SINK VIA AIR <br />GAP FITTING. SEE 3/P5.01 FOR DISH WASHER DETAIL. <br />LEVEL 01 -A <br />z <br />SCALE: NONE <br />Otak Architects, Inc. <br />306 SW Third Avenue, Suite 300 <br />Portland, OR 97204 <br />plain 503.287.6825 <br />vvww.otak.com <br />n <br />2020/04/17 <br />CONSULTANT <br />r"r <br />WIN <br />E <br />TITLE <br />9 DATE DESCRIPTION <br />1 04/17/2020 100% Issue Set/Bid Set <br />0 2020 OTAK, INC. <br />If this drawing is not 24" x 36", it has been <br />reduced/enlarged. Scale accordingly. <br />