Laserfiche WebLink
DESIGN CRITERIA: <br />STRUCTURAL SYSTEMS PRESENTED IN THESE PLANS HAVE BEEN DESIGNED TO MEET THE <br />REQUIREMENTS OF THE 2018 EDITION OF THE INTERNATIONAL BUILDING CODE & <br />INTERNATIONAL RESIDENTIAL CODE. <br />DESIGN LOADS: <br />LATERAL SEISMIC LOADS <br />LATERAL WIND LOADS: <br />ANALYSIS METHOD: SIMPLIFIED PROCEDURE <br />IE = 1.00, SEISMIC USE I, SITE CLASS D, <br />SEISMIC DESIGN CATEGORY D <br />LIGHT FRAME BEARING WALL w/ WOOD PANEL: R = 6.5 & Cs = 0.13 <br />Ss = 1.25 & S1 = 0.40 (PER 2002 USGS MAP w/ LAT. & LON.) <br />SDs=0.83&SDI =0.43 <br />WIND SPEED: 110 mph, EXPOSURE B, GCpi = ±0.18, Kzt = 1.00 <br />VERTICAL LOADS: ROOF LOADS FLOOR LOADS <br />DEAD LOAD 15 PSF 10 PSF <br />LIVE LOAD N/A 40 PSF <br />SNOW LOAD 25 PSF N/A <br />SOIL AND FOUNDATION: <br />DESIGN VALUES: <br />ALLOWABLE BEARING: 2000 PSF <br />COEFFICIENT OF FRICTION: 0.35 <br />ACTIVE PRESSURE: 35 PCF (UNRESTRAINED) <br />60 PCF (RESTRAINED) <br />PASSIVE PRESSURE: 300 PCF <br />ALL FOOTINGS SHALL BEAR UPON UNDISTURBED SOIL OR COMPACTED FILL AT LEAST 18" <br />BELOW FINISHED GRADE. <br />ALL WALLS SHALL BE ADEQUATELY BRACED PRIOR TO BACKFILLING. COMPACTED FILL SHALL <br />MATERIAL AND DEBRIS. FI L SHALL BE PLACED <br />BE FREE OF ORGANIC ED IN A MAXIMUM OF 8 INCH L C <br />LIFTS AND COMPACTED <br />0 <br />UM 95/o OF THE MAXIMUM DENSITY AS DETERMINED BY <br />TO A MINIM <br />ASTM D-1557. <br />CONCRETE: <br />CONCRETE SHALL BE OF THE FOLLOWING 28 DAY TEST STRENGTH AND MIX: <br />1) F'c = 3000 PSI <br />2) MAXIMUM SLUMP = 4" <br />3) MAX WATER/CEMENT RATIO = 0.53; 6 GALLONS PER SACK <br />4) MINIMUM ENTRAINED AIR CONTENT SHALL BE 4%± 1% <br />5) INCORPORATE NO CALCIUM CHLORIDE ADMIXTURES WHERE ALUMINUM ALLOY MATERIALS <br />ARE EMBEDDED. <br />DESIGN F'c = 2500 PSI WITH F'c = 3000 PSI SPECIFIED FOR WEATHERING PER IBC TABLE 1904.2. <br />NON -SHRINK 4000 PSI NON -SHRINK GROUT SHALL BE USED FOR ALL COLUMN BASE PLATES. <br />PROVIDE CONSTRUCTION JOINTS AT A MINIMUM OF 20'-0" TO MINIMIZE THE EFFECTS OF <br />CONCRETE SHRINKAGE DURING CURING. CONCRETE SHALL BE PROTECTED DURING CURING <br />TO MINIMIZE EVAPORATION AND MAINTAIN A MOIST CONDITION. <br />PIPES SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY <br />APPROVED BY THE DESIGN ENGINEER, WITH THE EXCEPTION OF ELECTRICAL CONDUIT. <br />REINFORCING STEEL: <br />REBAR: GRADE (PSI) <br />#4 & SMALLER 40 40,000 <br />#5 & LARGER 60 60,000 <br />CAST AGAINST EARTH: 3" <br />EXPOSED TO EARTH OR WEATHER: 2" <br />SLABS, WALLS AND JOISTS: 3/4" <br />BEAMS AND COLUMN: 1-1/2" <br />LAP ALL FIELD SPLICES 30 DIAMETERS UNLESS NOTED OTHERWISE. DOWEL ALL EXTERIOR <br />PROJECTIONS TO STRUCTURE WITH #4 BARS @ 12" HOOKED INTO WALL. <br />BEND WALL AND FOOTING BARS 18" AROUND CORNERS, OR USE CORNER BARS. <br />WELDED WIRE MESH SHALL CONFORM WITH ASTM A185 AND SHALL BE 6x6 W1.4x1 A UNLESS <br />NOTED OTHERWISE. PLACE AT MID -DEPTH OF SLAB AND PROVIDE ONE FULL MESH OVERLAP <br />AT SPLICES. <br />MANUFACTURED ROOF TRUSSES: <br />ROOF TRUSSES SHALL BE DESIGNED BY AN ENGINEER REGISTERED IN THE STATE OF <br />WASHINGTON AND FABRICATED FROM HIS/HER DESIGNS. THE SNOW LOAD SHALL BE NOTED <br />UNDER DESIGN LOADS AND VERIFIED PRIOR TO FABRICATION. TRUSS DESIGNS SHALL BE <br />SUBMITTED FOR REVIEW. BLOCK EDGES WHERE CALLED FOR IN PLANS. HANDLE AND INSTALL <br />IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. <br />1) WALLS: 7/16" APA RATED SHEATHING, 24/16, EXPOSURE, NAIL TO OUTSIDE FACE OF STUDS <br />WITH 8d NAILS @ 6" O.C. ALL PANEL EDGES AND AT 12" O.C. INFIELD AND PROVIDE SOLID a. COMMON NAILS (6d - 2" x 0.113", 8d - 2%2' x 0.131 ", 10d - 3" x 0.148") <br />BLOCKING AT ALL EDGES UNLESS NOTED OTHERWISE IN PLAN OR SHEARWALL SCHEDULE. b. FOR ALL CONNECTIONS NOT SHOWN, REFER TO IBC 2304.9.1, DETAILS AND SHEAR WALL <br />2) ROOF: 7/16" APA RATED SHEATHING, 24/16, EXPOSURE, NAIL TO OUTSIDE FACE OF SCHEDULE <br />RAFTERS/TRUSSES WITH 8d NAILS @ 6" O.C. ALL PANEL EDGES AND AT 12" O.C. IN FIELD <br />AND PROVIDE SOLID BLOCKING AT ALL EDGES UNLESS NOTED OTHERWISE IN PLAN OR <br />SHEARWALL SCHEDULE. <br />3) FLOORS: 3/4" APA RATED SHEATHING, 24/16, EXPOSURE, NAIL TO OUTSIDE FACE OF JOISTS <br />WITH 10d NAILS @ 6" O.C. ALL PANEL EDGES AND AT 12" O.C. IN FIELD AND PROVIDE SOLID <br />BLOCKING AT ALL EDGES UNLESS NOTED OTHERWISE IN PLAN OR SHEARWALL SCHEDULE. <br />WOOD FRAMING: <br />ALL GRADES SHALL CONFORM TO "WWPA GRADING RULES FOR WESTERN LUMBER, LATEST <br />EDITION" <br />BEAMS (4X AND GREATER) DF #1 OR BETTER <br />POSTS DF #1 OR BETTER <br />STUDS HF #2 / STUD <br />ALL OTHER LUMBER HF #2 OR BETTER <br />GLUE LAMINATED TIMBER: <br />MEMBER USE <br />SPAN TYPE <br />SPECIES <br />COMB. SYMBOL <br />Fbx + <br />Fbx - <br />BEAM <br />SIMPLE <br />DF/DF <br />24F V4 <br />2400 PSI <br />1850 PSI <br />BEAM <br />CANTILEVER <br />DF/DF <br />24F V8 <br />2400 PSI <br />2400 PSI <br />ALL EXTERIOR DECK FRAMING AND WOOD MEMBERS IN CONTACT WITH CONCRETE OR <br />MASONRY SHALL BE PRESSURE TREATED. FASTENERS FOR PRESERVATIVE -TREATED WOOD <br />(WITH THE EXCEPTION OF STEEL BOLTS ONE -HALF -INCH DIAMETER OR GREATER) SHALL BE <br />OF HOT -DIPPED ZINC COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON BRONZE OR <br />COPPER. WHEN USING STAINLESS STEEL OR HOT -DIPPED GALVANIZED CONNECTORS, THE <br />CONNECTORS AND FASTENERS SHOULD BE MADE OF THE SAME MATERIAL. FOLLOW <br />MANUFACTORERS RECOMMENDATIONS FOR CORROSION PROTECTION WHEN STEEL <br />HANGERS AND CONNECTORS ARE USED. <br />ALL DOOR AND WINDOW HEADERS NOT SPECIFICALLY CALLED OUT ON THE PLANS SHALL BE <br />(2) 2x8 DF #2 WITH ONE CRIPPLE AND ONE STUD FOR OPENINGS 6'-0" OR LESS AND TWO <br />CRIPPLE AND ONE STUD FOR OPENINGS MORE THAT 6'-0" WIDE. ALL COLUMNS NOT <br />SPECIFICALLY CALLED OUT ON THE PLANS SHALL BE (2) 2x(MATCH WALL STUDS) HF#2 NAILED <br />TOGETHER PER STRUCTURAL NOTES. <br />SPIKE LAMINATE 2x4 COLUMNS TOGETHER WITH 16d @ 9" O.C. STAGGERED. LAMINATE 2x6 <br />COLUMNS TOGETHER WITH (2) OFFSET ROWS OF 16d NAILS @ 9" O.C. DRIVE ADJACENT NAILS <br />FROM OPPOSITE SIDES OF THE COLUMN. EACH INDIVIDUAL STUD SHALL BE ATTACHED TO <br />THE ADJACENT STUD. <br />PROVIDE DOUBLE TOP PLATES AT ALL WALLS AND STAGGER SPLICES A MINIMUM OF 48". <br />ATTACH BOTTOM PLATE TO WOOD FRAMING BELOW WITH 16d @ 12" O.C. OR BOLT TO <br />CONCRETE WITH 1/2 DIAMETER ANCHOR BOLTS 48 O.C. EMBEDDED MIN UNLESS T C 7 U SS NOTED <br />OTHERWISE IN PLAN OR SHEARWALL SCHEDULE. <br />NON -BEARING WALLS MUST BE HELD AWAY FROM TRUSS BOTTOM CHORDS WITH AN <br />APPROVED FASTENER TO INSURE THAT THE TRUSS DOES NOT BEAR ON THE WALL, <br />CONNECTORS SHALL BE MANUFACTURED BY SIMPSON STRONG TIE COMPANY, INC., OR <br />APPROVED EQUIVALENT. CONNECTORS SHALL BE INSTALLED PER MANUFACTURERS <br />SPECIFICATIONS WITH ALL HOLES IN HANGERS TO BE NAILED, <br />SOLID BLOCKING OF 2" NOMINAL THICKNESS OR GREATER SHALL BE PROVIDED AT ENDS AND <br />AT ALL SUPPORTS OF JOISTS AND RAFTER. INSTALL BLOCKING OR BRIDGING AT 8'-0" O.C. FOR <br />FLOOR JOISTS AND 10'-0" O.C. FOR RAFTERS. PROVIDE SQUASH BLOCKING NEXT TO RIM JOIST <br />UNDER ALL PERIMETER POSTS AND COLUMNS CONSISTING OF A DOUBLE STUD OR GREATER, <br />BLOCKING TO MATCH THE AREA OF THE MEMBER ABOVE, UNLESS OTHERWISE SPECIFIED, <br />PROVIDE AN EQUIVALENT COLUMN OR SOLID BLOCKING TO SUPPORT OR FLOOR BELOW AT <br />ALL COLUMN LOCATIONS. <br />PROVIDE DOUBLE JOIST UNDER ALL INTERIORS WALLS THAT RUN PARALLEL TO JOIST <br />ORIENTATION. <br />GENERAL NOTES: <br />DO NOT SCALE DRAWINGS. USE ONLY WRITTEN DIMENSIONS. THE CONTRACTOR SHALL <br />VERIFY ALL DIMENSIONS AND ALL CONDITIONS AT THE SITE. CONFLICTS BETWEEN THE <br />DRAWING AND SITE SHALL BE REPORTED TO THE ENGINEER BEFORE PROCEEDING WITH THE <br />WORK. <br />REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND <br />WINDOW OPENINGS, FINISHES AND OTHER NON-STRUCTURAL ITEMS. <br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE DURING <br />CONSTRUCTION AND SHALL PROVIDE TEMPORARY BRACING AS REQUIRED UNTIL ALL <br />PERMANENT CONNECTIONS AND STIFFENERS HAVE BEEN INSTALLED. THE CONTRACTOR <br />SHALL COORDINATE WITH THE BUILDING DEPARTMENT FOR ALL BUILDING DEPARTMENT <br />REQUIRED INSPECTIONS. <br />THE DETAILS SHOWN ARE TYPICAL AND SHALL BE USED FOR SIMILAR CONDITIONS NOT <br />SHOWN. <br />PREFABRICATED ITEMS TO BE HANDLED AND INSTALLED PER MANUFACTURERS <br />RECOMMENDATIONS. <br />THIS DRAWING IS THE EXCLUSIVE PROPERTY OF THE ENGINEER AND CAN BE REPRODUCED <br />ONLY WITH THE PERMISSION OF THE ENGINEER, IN WHICH CASE THE REPRODUCTION MUST <br />BEAR THEIR NAMES AS ENGINEER. <br />TYPICAL AILING SCHEDULE <br />TYPICAL CONNECTION TYPE <br /># OF REQ'D <br />FASTENER <br />LOCATION <br />FASTENERS <br />JOIST TO SILL OR GIRDER <br />3 <br />8d COMMON (or) <br />TOENAIL <br />3" x 0.131" NAILS <br />(STAGGER) <br />BRIDGING TO JOIST <br />2 <br />8d COMMON (or) <br />TOENAIL EACH <br />3" x 0.131" NAILS <br />END <br />SOLE PLATE TO JOIST OR <br />TYPICAL FAGS <br />BLOCKING (WALL) <br />8" O.C. <br />3" x 0.131" NAILS <br />NAIL <br />TOP PLATE TO STUD, OR STUD <br />TO SOLE PLATE (WALL) <br />3 <br />3" x 0.131" NAILS <br />END NAIL <br />STUD TO SOLE PLATE (WALL) <br />4 <br />8d COMMON (or) <br />TOENAIL <br />3" x 0.131" NAILS <br />DOUBLE STUDS, OR MULTIPLE <br />LAM MEMBERS <br />g O.C. <br />3" x 0.131" NAILS <br />FACE NAIL <br />DOUBLE TOP PLATES <br />12" O.C. <br />3" x 0.131" NAILS <br />TYPICAL FACE <br />NAIL <br />BLOCKING BETWEEN JOISTS OR <br />RAFTERS TO TOP PLATE <br />3 <br />3" x 0.131" NAILS <br />TOENAIL <br />RIM JOIST TO TOP PLATE <br />6" O.C. <br />8" x 0.131" NAILS <br />TOENAIL <br />RAFTER TO TOP PLATE <br />RAFTER SPACING <br />SIMP. "W" CLIP <br />FILL ALL NAIL <br />HOLES PER SIMP. <br />JOIST TO RIM (BAND) JOIST <br />4 <br />16d COMMON (or) <br />FACE NAIL <br />3" x 0.131" NAILS <br />SHEAR WALL SCHEDULE <br />NAILING* <br />SHEAR FLOW NAILING <br />MARK <br />SHEATHING <br />EDGES <br />FIELD <br />BASE TOE NAIL <br />SILL PLATE <br />COMMON <br />BLOCKED <br />PLATE RIM/TOP <br />ANCHORS" <br />SWI <br />OSB <br />8d@6" <br />8d@12" <br />16d@8" <br />16d@5" <br />z 0A.6.@ <br />48 O.C. & <br />ONE SIDE <br />O.C. <br />O.C. <br />O.C. <br />O.C. <br />ENDS <br />/s' OSB <br />8d @ 4" <br />8d @ 12" <br />16d @ 5" <br />SIMP. LTP4 <br />@ <br />" <br />2 <br />ONE SIDE <br />O.C. <br />O.C. <br />O.C. <br />@ 20" O.C. <br />3 O.C. & <br />ENDS <br />USE COMMON NAILS FOR ALL NAILING. <br />'* ANCHOR BOLT WASHERS MUST BE 3" X 3" X 1/4" THICK <br />FLOORTIES & HOLDDOWNS <br />MARK <br />STRAP <br />NAILING <br />HOLDDOWN <br />STUD ANCHORAGE <br />ANCHOR <br />BOLTS <br />STHD8 <br />STHD8 <br />(24) 16D <br />N/A <br />STHD8RJ <br />SINKER <br />1) LOCATE HOLDOWN AT EACH END OF SHEARWALL <br />2) CRIPPLE WALL CONSTRUCT SAME AS S.W. ABOVE <br />3) EXTEND FOUNDATION AS REQ'D. FOR H.D. A.B. EMBEDMENT <br />4) THREADED ROD AND COUPLER AS REQUIRED <br />NOTE <br />FOR MONOPOUR CONSTRUCTION: IN LIEU OF THE REINFORCING SHOWN, THE FOUNDATION <br />MAY BE CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS AS OUTLINED IN THE 2012 <br />IRC, SECTION R404.1.4 & R403.1.3.1. THESE PROVISIONS OUTLINE THE REQUIREMENTS FOR <br />PLAIN CONCRETE FOUNDATION WALLS LOCATED IN SEISMIC DESIGN CATEGORIES DO, D1 & D2. <br />AS A RECAP OF THE CODE THE FOUNDATION SHALL COMPLY WITH THE FOLLOWING: <br />1. WALL HEIGHT SHALL NOT EXCEED 8 FT. <br />2. UNBALANCED BACKFILL HEIGHT SHALL NOT EXCEED 4 FT, <br />3. MINIMUM REINFORCEMENT FOR PLAIN CONCRETE FOUNDATION WALL SHALL CONSIST <br />OF ONE NO. 4 HORIZONTAL BAR LOCATED IN THE UPPER 12 INCHES OF OF THE WALL. <br />4. MINIMUM THICKNESS FOR PLAIN CONCRETE FOUNDATION WALL SHALL BE 7.5 INCHES <br />EXCEPT THAT 6 INCHES IS PERMITTED WHEN THE MAXIMUM HEIGHT IS 4 FT, 6 INCHES. <br />5. PER R403.1.3.1: FOUNDATIONS WITH STEM WALLS SHALL HAVE INSTALLED A MINIMUM OF <br />ONE NO.4 BAR WITHIN 12 INCHES OF THE TOP OF THE WALL AND ONE NO.4 BAR <br />LOCATED 3 INCHES TO 4 INCHES FROM THE BOTTOM OF THE FOOTING. <br />Simple Heating System Size: Washington State <br />This heating system sizing calculator is based on the Prescriptive Requirements of the 2012 Washington State Energy Code (WSEC) and ACCA <br />Manuals J and S. This calculator will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling <br />loads. <br />The glazing window and door portion of this calculator - <br />g g ( ) passumes the installed glazing and door products have an area weighted average U factor of <br />0.30. The incorporated insulation requirementsh are the minimum prescriptive amounts specified by the 2012 WSEC. <br />Please fill out all of the green drop -downs and boxes that are applicable to your project. As you make selections in the drop -downs for each section, <br />some values will be calculated for you. If you do not see the selection you need in the drop -down options, please call the WSU Energy Extension <br />Program at (360) 956-2042 for assistance. <br />Project Information Contact Information <br />PLAN #1866 PAUL BUSTARD <br />425-876-6551 <br />Heating System Type: Forced Air Furnace Heat Pump <br />To see detailed instructions for each section, place your cursor on the word "Instructions". <br />Design Temperature <br />Everett PaineAF6 - Design Temperature Difference (AT) <br />,T = Indoor (70 degrees) - Outdoor Design Temp <br />Area of Building <br />Conditioned Floor Area <br />Conditioned Floor Area (sq ft) <br />Average Ceiling Height <br />Average Ceiling Height (ft) <br />Glazing and Doors <br />Insulation <br />Attic <br />R-49 T <br />Single Rafter or Joist Vaulted Ceilings <br />Select R-Value v <br />Above Grade Walls (see Figure 1) <br />R 1 <br />Floors <br />R-30 w <br />Below Grade Walls (see Figure 1) <br />Select R-value <br />Slab Below Grade (see Figure 1) <br />Select conditioning v <br />Slab on Grade (see Figure 1) <br />Select R-Value <br />Location of Ducts <br />Unconditioned Space <br />2232 <br />Conditioned Volume <br />8.0 17,856 <br />U-Factor X Area = UA <br />0.30 - <br />U-Factor X Area = UA <br />0.026 <br />U-Factor <br />Area <br />No selection <br />U-Factor <br />Area <br />0.056 <br />U-Factor <br />Area <br />0.029 <br />- <br />U-Factor <br />Area <br />No selection <br />F-Factor <br />Length <br />No selection <br />F-Factor <br />Length <br />No selection <br />Duct Leakage Coefficient <br />1.10 <br />UA <br />UA <br />UA <br />UA <br />UA <br />UA <br />49 <br />2018 Washington State Energy Code - Residential <br />Prescriptive Energy Code Compliance for All Climate Zones in Washington <br />Single Family - New & Additions (effective February 1, 2021) Version 1.0 <br />These requirements apply to all IRC building types, including detached one- and two-family <br />dwellings and multiple single-family dwellings (townhouses). <br />Project Information Plan #2375 <br />Instructions: This single-family project will use the requirements of the Prescriptive Path below and <br />Incorporate the minimum values listed. Based on the size of the structure, the appropriate number of <br />additional credits are checked as chosen by the permit applicant. <br />Provide all information from the following tables as building permit drawings: Table R402.1 - Insulation and <br />Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. <br />All Climate Zones (Table R402.1.1) <br />R-Value a U-Factor a <br />Fenestration U-Factor b n/a 0.28 <br />Skylight U-Factor b n/a 0.50 <br />Glazed Fenestration SHGC Ue n/a n/a <br />Ceiling e 49 0.026 <br />Wood Frame Wall g'11 21 int 0.056 <br />Floor 38 0.029 <br />Below Grade Wall c'b 10/15/21 int + TB 0.042 <br />Slab d'f R-Value & Depth 10, 2 ft n/a <br />R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less <br />a than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix <br />Table A101.4 shall not be less than the R-value specified in the table. <br />b The fenestration U-factor column excludes skylights. <br />"10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on <br />the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at <br />c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on <br />the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" <br />means R-5 thermal break between floor slab and basement wall. <br />d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. <br />For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth <br />e extends over the top plate of the exterior wall. <br />R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter <br />f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall <br />meet the requirements for thermal barriers protecting foam plastics. <br />For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for <br />g climate zone 5 of [CC 400. <br />Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard <br />h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10 <br />insulation. <br />Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel <br />normalization credits) and Table 406.3 (energy credits) to achieve the following minimum number of <br />credits. To claim this credit, the building permit drawings shall specify the option selected and the <br />maximum tested building air leakage, and show the qualifying ventilation system and its control sequence <br />of operation. <br />1. Small Dwelling Unit: 3 credits <br />Dwelling units less than 1,500 sf in conditioned floor area with less than 300 sf of fenestration area. <br />Additions to existing building that are greater than 500 sf of heated floor area but less than 1,500 sf. <br />2. Medium Dwelling Unit: 6 credits <br />All dwelling units that are not included in #1 or #3 <br />3. Large Dwelling Unit: 7 credits <br />Dwelling units exceeding 5,000 sf of conditioned floor area <br />All Climate Zones <br />R-Valuea <br />U-Factora <br />Fenestration U-Factorb <br />n/a <br />0.28 <br />Skylight U-Factor <br />n/a <br />0.50 <br />Glazed Fenestration SHGCb,e <br />n/a <br />n/a <br />Ceiling <br />49j <br />0.026 <br />Wood Frame Wall g,k,l <br />21 int <br />0.056 <br />Mass Wall R-Valuei <br />21/21h <br />0.056 <br />Floor <br />38g <br />0.029 <br />Below Grade Wallc,k <br />10/15/21 int + TB <br />0.042 <br />Slabd R-Value & Depth <br />10, 2 ft <br />n/a <br />APPROVED <br />Economic Development <br />Dffice of Community Pllantift & E'co <br />PLANNING DEPARTMENT Ui <br />1I, <br />A DATE: <br />1�►��1�� D�P�.1�$p,� �1{�AL <br />� UES� � Sens <br />PR <br />Sansi�iiva <br />ems <br />i0lR10 RER � FencM .� <br />Landscaping Ares <br />entaltY <br />� Environrn <br />Conta S1, , <br />(4251'251 81 <br />it <br />CI-\f0FEIE 13 <br />Permit �eVi� <br />Permit if: <br />132112-033 <br />Site Address: <br />1023 100TH ST SW <br />Owner: <br />BUSTARD CUSTOM CONSTRUCTION INC <br />Tenant: <br />[TenNamej <br />App.Date: <br />12/10/2021 <br />Proposed Use: <br />NEW SINGLE FAMILY <br />Description: <br />CONSTRUCT NEW SFR, LOT 1 <br />Reviewed By:s <br />X Office Set Job Site Set <br />4. Additions less than 500 square feet. 1.5 credits <br />All other additions shall meet 1-3 above p05i'TIONPD AS <br />O I5 No- PLAN, <br />Summary of Table R406.2 iF BiJIL�E OI'7 APPrtOVEI7g �UBIv11"I <br />Heating Credits - select ONE INDICA" SITE PL) SHALL ILL <br />I II'iSI'EC'TION� W <br />Options Fuel Normalization Descriptions heating option TEDEIwvO I- ,� i'..-E O JEC-r UNTO THE <br />rdAl�`� 0, I'IIIS PR S BEEN APPPOV- <br />1 Combustion heating minimum NAECAb 0.0 REVISE THEE PLAN I- BLIG -�yOILI�S <br />2 Heat pump' 1.0 x D Wj BUIL <br />INGIPU <br />3 Electric resistance heat only - furnace or zonal -1.0 E <br />4 DHP with zonal electric resistance per option 3.4 0.5 DEP rS° ned <br />5 All other heating systems -1.0 <br />sum of UA - Energy Credits - select ONE <br />Envelo a Heat Load Options Energy Credit Option Descriptions energy option from each <br />p Btu /Hour <br />Sum of UA X dT <br />Air Leakage Heat Load - Btu / Hour <br />Volume X 0.8 X AT X .018 <br />1.1 <br />Building Design Heat Load Btu / Hour <br />1.2 <br />Air Leakage + Envelope Heat Loss <br />1.3 <br />Building and Duct Heat Load - Btu / Hour <br />1.4 <br />Ducts in unconditioned space: Sum of Building Heat Loss X 1. 10 <br />- Ducts in conditioned space: Sum of Building Heat Loss X 1 <br />1.5 <br />Maximum Heat Equipment Output - Btu / Hour <br />1.6 <br />Building and Duct Heat Loss X 1.40 for Forced Air Furnace <br />1.7 <br />Building and Duct Heat Loss X 1.25 for Heat Pump <br />Table R402.1.1 Footnotes <br />2.1 <br />For SI: 1 foot .= 304.8 mm, ci .= continuous insulation, int .= intermediate framing. <br />2.2 <br />a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity which is <br />2.3 <br />.4 <br />2.1a <br />less than the label or design thickness of the insulation, the compressed R-value of the insulation from <br />Appendix Table A101.4 shall not be less than the R-value specified in the table. <br />3.2 <br />b The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration. <br />3.3a <br />3.4 <br />Exception: Skylights may be excluded from glazed fenestration SHGC requirements in Climate Zones 1 <br />3.5 <br />through 3 where the SHGC for such skylights does not exceed 0.30. <br />3.6a <br />c "10/15/21.+TB" means R-10 continuous insulation on the exterior of the wall, or R-15 on the continuous <br />4.1 <br />4.2 <br />insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the <br />5.1d <br />basement wall at the interior of the basement wall. "10/15/21.+TB" shall be permitted to be met with R-13 <br />5.2 <br />cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or <br />5.3 <br />5.4 <br />exterior of the wall. "10/13" means R-10 continuous insulation on the interior or exterior of the home or R- <br />5.5 <br />13 cavity insulation at the interior of the basement wall. "TB" means thermal break between floor slab and <br />5.6 <br />basement wall. <br />6.1e <br />d R-10 continuous insulation is required under heated slab on grade floors. See R402.2.9.1. <br />7.1 <br />e There are no SHGC requirements in the Marine Zone. <br />f Basement wall insulation is not required in warm -humid locations as defined by Figure R301.1 and Table <br />a <br />R301.1. <br />g Reserved. <br />b• <br />h First value is cavity insulation, second is continuous insulation or insulated siding, so "13.+5" means R-13 <br />C. <br />cavity insulation plus R-5 continuous insulation or insulated siding. If structural sheathing covers 40 percent <br />or less of the exterior, continuous insulation R-value shall be permitted to be reduced by no more than R-3 in <br />e <br />the locations where structural sheathing is used to maintain a consistent total sheathing thickness. <br />f <br />i The second R-value applies when more than half the insulaJon is on the interior of the mass wall. <br />j For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38. <br />k Int. (intermediate framing) denotes standard framing 16 inches on center with headers insulated with a <br />minimum of R-10 insulation. <br />I Log and solid timber walls with a minimum average thickness of 3.5 inches are exempt from this insulation <br />requirement. <br />Table R402.1.3 Footnote <br />a Nonfenestration U-factors shall be obtained from measurement, calculation or an approved source or as <br />specified in Section R402.1.3. <br />category d <br />Efficient Building Envelope <br />0.5 <br />Efficient Building Envelope <br />1.0 <br />Efficient Building Envelope <br />0.5 x <br />Efficient Building Envelope <br />1.0 <br />Efficient Building Envelope <br />2.0 <br />Efficient Building Envelope <br />3.0 <br />Efficient Building Envelope <br />0.5 <br />Air Leakage Control and Efficient Ventilation <br />0.5 x <br />Air Leakage Control and Efficient Ventilation <br />1.0 <br />Air Leakage Control and Efficient Ventilation <br />1.5 <br />Air Leakage Control and Efficient Ventilation <br />2.0 <br />High Efficiency HVAC <br />1.0 <br />High Efficiency HVAC <br />1.0 <br />High Efficiency HVAC <br />1.5 <br />High Efficiency HVAC <br />1.5 <br />High Efficiency HVAC <br />1.5 x <br />High Efficiency HVAC <br />2.0 <br />High Efficiency HVAC Distribution System <br />05 x <br />High Efficiency HVAC Distribution System <br />1.0 <br />Efficient Water Heating <br />0.5 <br />Efficient Water Heating <br />0.5 <br />Efficient Water Heating <br />1.0 <br />Efficient Water Heating <br />1.5 x <br />Efficient Water Heating <br />2.0 <br />Efficient Water Heating <br />2.5 <br />Renewable Electric Energy (3 credits max) <br />1.0 <br />Appliance Package <br />0.5 x <br />Total Credits <br />6.0 <br />An alternative heating source sized at a maximum of 0.5 W/sf (equivalent) <br />of heated floor area or 500 W, <br />whichever is bigger, may be installed in the dwelling unit. <br />Equipment listed in Table C403.3.2(4) or C403.3.2(5) <br />Equipment listed in Table C403.3.2(1) or C403.3.2(2) <br />You cannot select more than one option from any category EXCEPT <br />in category 5. Option 5.1 may be combined <br />with options 5.2 through 5.6. See Table 406.3. <br />1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. <br />See the complete Table R406.2 for all requirements and option descriptions. <br />Use the single radiobutton in the upper right of the second column to deselect radiobuttons in that group. <br />dsslg <br />R©OIS trusses to be <br />by <br />and drawing <br />a state 110069- sir► tural <br />en0i040r= <br />Fire/Planning Set <br />PROPANE TANKS, HEAT PUMP( <br />0 T HER EQUIPMENT OR APPUP <br />MAY NOT BE LOCATED IN THE <br />AND SIDE SET6ACKS. PROP0 <br />FIRE DFPA� <br />REWIRE ADDITIONAL PERMIT <br />0 ET V PMINSTALIATION. <br />eke detectors Required <br />smoke In room, <br />In each sleeping ing access to a <br />® In each room g <br />sleeping room, <br />® Interconnected, <br />® Battery <br />® HardWlred. <br />permits Are RequireC, <br />Additional his project Tc� Include,'. <br />For T <br />_ n Sprinkler <br />Iplumbing <br />Mec'nanCal <br />Fire Alarm <br />Electrical <br />VE <br />THESE DOCUMENTS "A <br />NOT BEEN OF PUBL C WRKS, <br />ISSUANCE FIRE SUPPRESSION, <br />MECHANICAL, <br />ELECTRICAL OR PLUMBING PERMITS. <br />AS <br />., 0 <br />Beat 51 +``Mrs i - -- <br />It Is owners responsibility to establish and stake all EVERETT <br />CI-iY OF FOR �E���� <br />property lines- REVIEWED <br />W <br />Z <br />O <br />U) <br />w <br />Cr <br />O <br />0-Q <br />_O <br />U <br />U <br />of <br />w <br />O <br />❑ <br />U <br />N <br />� <br />Q <br />3 <br />r <br />❑ <br />A <br />it <br />M <br />M <br />?UJ <br />UJ <br />r ZIt <br />c`) uj <br />Q <br />U <br />Z <br />Q <br />J U <br />Z <br />O <br />O M <br />F-W4 <br />r" <br />rn <br />Q <br />1-- U <br />t (!� :D <br />2i 3� <br />w w <br />` W ® � Z <br />oil- <br />vt <br />- = � <br />rn m <br />3-14-22 <br />),1 MCC <br />pF WASyr,V <br />r� <br />��O C 38799 w� <br />SIDNAL <br />�C <br />\ND <br />ENANCES <br />I RONT <br />:TANKS <br />ISSUED <br />" MENT <br />0- <br />GENERAL NOTES <br />SCHEDULES <br />REVISION: <br />1 <br />DATE: <br />3-14-22 <br />DRAWN BY: <br />TJM <br />SCALE: <br />AS NOTED <br />PROJECT NOL.J <br />_ <br />W4737 <br />SHEET NO-, <br />1 <br />