4/13/2022 City of Everett Page <br /> 6:39:05AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. P2005-028 Site Address 323 ROCKEFELLER AVE <br /> Applied 5/26/2020 Applicant NW BATHWORKS LLC Lot <br /> Approved 5/26/2020 Owner STDENIS NORMAN&GLORIA Block <br /> Issued 10/1/2020 Contractor NW BATHWORKS LLC Tract <br /> Parent Permit No. Description Plumbing—Hot Water Tank Replacement <br /> Notes Replace Hot Water Tank"Like for Like" <br /> Scheduled Completed Tyne Inspector Result Remarks Inspector's Comments <br /> 3/22/2021 3/22/2021 PERMIT KLC EXTENSION A COVID <br /> EXTENSION EXTENSION <br /> 7/23/2021 7/23/2021 PERMIT KLC EXTENSION A COVID <br /> EXTENSION EXTENSION <br /> 3/16/2022 3/16/2022 PLUMB 07-FINAL JJM CORRECTION Gloria 425-252-2890 <br /> (3/16/2022 10:51 AM JJM) <br /> -Per the UPC section 608.0 relief valve <br /> discharge must grade downward to an <br /> approved indirect waste receptor or to the <br /> exterior of the building.The exception for <br /> the discharge to run directly to within 6" <br /> and 24"of the floor is only if an existing <br /> drain was never provided.In this case there <br /> is an existing discharge line. <br /> -The other option is to install a secondary <br /> T&P rated at 125 PSI/210 degrees,on the <br /> water system,preferably from a tee off the <br /> copper hot outlet from the tank that is <br /> above the existing relief discharge allowing <br /> gravity drainage.The existing T&P would <br /> then run to within 6"and 24"of the floor. <br /> 4/12/2022 4/12/2022 PLUMB 07-FINAL BGA APPRVD-PERN <br /> INSP12 <br />