Does side sewer have slope: Yes 1 ck <br /> Depth of side sewer 10ft from house: 8' 2" <br /> Depth of side sewer at proposed backwater valve installation spot: Outside location <br /> depth of 8' <br /> Any additional comments: Toilet was removed to gain access to system as the clean <br /> out would not open. During this process it was noticed that the toilet flange was not <br /> secured correctly. Homeowners were informed of this. <br /> Problems Identified <br /> 1) Problem: No backwater valve on side sewer. <br /> Solution: Install backwater valve in front yard in flower bed located on the south <br /> west side of the house. Side were runs parallel to the south side of the house. <br /> 2) Problem: Due to down spouts being disconnected from this house and neighbors <br /> house on up-hill side, water has started to run through the basement wall causing <br /> issues. <br /> Solution: Pipe down spouts to back yards and away from houses and their <br /> foundations. <br /> Solution: Install French drain between the two houses with pipes to carry the <br /> down spout and ground water away from the houses and their foundations to the <br /> back yard. <br /> As-Built of Sewer and Plumbing <br /> See attached drawing: <br /> Comments <br /> Has begun to remove dry wall in basement in order to apply a sealant to the foundation <br /> walls to prevent water from seeping into the basement. <br /> Additional Photos and Descriptions <br />