CONTRACTOR NOTES:
<br />THE ARCHITECTS/ENGINEERS HAVE MADE EVERY EFFORT TO SET FORTH IN THE
<br />CONSTRUCTION AND CONTRACT DOCUMENTS THE COMPLETE SCOPE OF WORK.
<br />CONTRACTORS BIDDING THE JOB ARE NEVERTHELESS CAUTIONED THAT MINOR OMISSIONS
<br />OR ERRORS IN THE DRAWINGS AND OR SPECIFICATIONS SHALL NOT EXCUSE SAID
<br />CONTRACTOR FROM COMPLETING THE PROJECT AND IMPROVEMENTS IN ACCORDANCE WITH
<br />THE INTENT OF THESE DOCUMENTS. THE BIDDER SHALL BEAR THE RESPONSIBILITY OF
<br />NOTIFYING (IN WRITING) THE ARCHITECT/ENGINEER OF ANY CONFLICTS, ERRORS, OR
<br />OMISSIONS PRIOR TO THE SUBMISSION OF CONTRACTOR'S PROPOSAL. IN THE EVENT OF
<br />DISCREPANCIES THE CONTRACTOR SHALL PRICE THE MORE COSTLY OR EXTENSIVE WORK,
<br />UNLESS DIRECTED OTHERWISE.
<br />DRAWINGS ARE NOT TO BE SCALED, WRITTEN DIMENSIONS TAKE PRECEDENCE, AND THIS
<br />SET OF PLANS IS INTENDED TO BE USED FOR DIAGRAMMATIC PURPOSES ONLY, UNLESS
<br />NOTED OTHERWISE. THE GENERAL CONTRACTOR'S SCOPE OF WORK SHALL INCLUDE
<br />FURNISHING ALL MATERIALS, EQUIPMENT, LABOR, AND ANYTHING ELSE DEEMED NECESSARY
<br />TO COMPLETE INSTALLATIONS AS DESCRIBED HEREIN.
<br />PRIOR TO THE SUBMISSION OF BIDS, THE CONTRACTORS INVOLVED SHALL VISIT THE JOB
<br />SITE AND FAMILIARIZE THEMSELVES WITH ALL CONDITIONS AFFECTING THE NEW PROJECT,
<br />WITH THE CONSTRUCTION AND CONTRACT DOCUMENTS, FIELD CONDITIONS AND CONFIRM
<br />THAT THE PROJECT MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH
<br />CONSTRUCTION. ANY ERRORS, OMISSIONS, OR DISCREPANCIES ARE TO BE BROUGHT TO
<br />THE ATTENTION OF THE ARCHITECT/ENGINEER IN WRITING.
<br />THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN AUTHORIZATION 10 PROCEED WITH
<br />CONSTRUCTION PRIOR TO STARTING WORK ON ANY ITEM NOT CLEARLY DEFINED BY THE
<br />CONSTRUCTION DRAWINGS/CONTRACT DOCUMENTS.
<br />THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT DESCRIBED HEREIN. THE
<br />CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS,
<br />TECHNIQUES, SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL PORTIONS OF
<br />THE WORK UNDER THE CONTRACT.
<br />THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS ACCORDING TO
<br />MANUFACTURER'S/ VENDOR'S SPECIFICATIONS UNLESS NOTED OTHERWISE OR WHERE
<br />LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
<br />ALL WORK PERFORMED ON PROJECT AND MATERIALS INSTALLED SHALL BE IN STRICT
<br />ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND ORDINANCES. CONTRACTOR
<br />SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS
<br />AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY, MUNICIPAL AND UTILITY COMPANY
<br />SPECIFICATIONS, AND LOCAL AND STATE JURISDICTIONAL CODES BEARING ON THE
<br />PERFORMANCE OF THE WORK.
<br />TIGHTEN ALL BOLTS FOR EQUIPMENT SUPPORTING FRAMES & ALL OTHER STRUCTURES
<br />MOUNTED / CONNECTED TO POLES, TOWERS, PARAPETS, ETC., FIRST TO RISC SNUG
<br />REQUIREMENTS & THEN TO AISC "TURN OF THE NUT" METHOD.
<br />CONNECTION BOLTS SUBJECT TO DIRECT TENSION SHALL BE INSTALLED & TIGHTENED AS
<br />PER SECTION 8.2.1 OF THE AISC SPECIFICATION FOR STRUCTURAL JOINTS USING A325 OR
<br />A490 BOLTS, LOCATED IN THE AISC MANUAL OF STEEL CONSTRUCTION.
<br />THE INSTALLATION PROCEDURE IS PARAPHRASED AS FOLLOWS:
<br />FASTENERS SHALL BE INSTALLED IN PROPERLY ALIGNED HOLES & TIGHTENED BY ONE OF
<br />THE METHODS DESCRIBED IN SUBSECTION 8.2.1 THROUGH 8.2.4.
<br />8.2.1 TURN -OF -THE -NUT TIGHTENING:
<br />BOLTS SHALL BE INSTALLED IN ALL HOLES OF THE CONNECTION & BROUGHT TO A SNUG
<br />TIGHT CONDITION AS DEFINED IN SECTION 8.1, UNTIL ALL THE BOLTS ARE
<br />SIMULTANEOUSLY SNUG TIGHT & THE CONNECTION IS FULLY COMPACTED. FOLLOWING THIS
<br />INITIAL OPERATION ALL BOLTS IN THE CONNECTION SHALL TIGHTENED FURTHER BY THE
<br />APPLICABLE AMOUNT OF ROTATION SPECIFIED ABOVE. DURING THE TIGHTENING OPERATION
<br />THERE SHALL BE NO ROTATION OF THE PART NOT TURNED BY THE WRENCH. TIGHTENING
<br />SHALL PROGRESS SYSTEMATICALLY FROM THE MOST RIGID PART OF THE JOINT IN A
<br />MANNER THAT WILL MINIMIZE RELAXATION OF PREVIOUSLY PRETENSIONED BOLTS.
<br />ALL OTHER BOLTED CONNECTIONS SHALL BE BROUGHT TO A SNUG TIGHT CONDITION AS
<br />DEFINED IN SECTION 8.1 OF THE SPECIFICATION.
<br />METAL NOTES:
<br />PART 1 - GENERAL
<br />1. SECTION INCLUDES:
<br />STRUCTURAL STEEL FRAMING MEMBERS, BASE PLATES, PLATES, BARS AND GROUTING
<br />UNDER BASE PLATES.
<br />2. SUBMITTALS:
<br />SHOP DRAWINGS: INDICATE SIZES, SPACING, AND LOCATIONS OF STRUCTURAL
<br />MEMBERS, OPENINGS, CONNECTIONS, CAMBERS, LOADS, AND WELDED SECTIONS.
<br />3. QUALITY ASSURANCE
<br />A. FABRICATE STRUCTURAL STEEL MEMBERS IN ACCORDANCE WITH AISC
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL
<br />STEEL FOR BUILDINGS.
<br />B. PERFORM DESIGN UNDER DIRECT SUPERVISION OF A PROFESSIONAL STRUCTURAL
<br />ENGINEER LICENSED IN THE STATE.
<br />THE STRUCTURAL COMPONENTS OF THIS PROJECT SITE/FACILITY ARE NOT TO BE ALTERED
<br />BY THIS CONSTRUCTION PROJECT UNLESS NOTED OTHERWISE. PART 2 - PRODUCTS
<br />ANTENNA SUPPORTING POLE IS UNDER A SEPARATE CONTRACT. THE CONTRACTOR, SHALL 1. MATERIAL
<br />ASSIST ANTENNA INSTALLATION SUB -CONTRACTOR IN TERMS OF COORDINATION AND SITE
<br />ACCESS. ERECTION SUB -CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF A. STRUCTURAL STEEL MEMBERS: ASTM A572, GRADE 50
<br />PERSONNEL AND PROPERTY FROM HAZARDOUS EXPOSURE TO OVERHEAD DANGERS. B. STRUCTURAL TUBING: ASTM A500, GRADE B
<br />C. PIPE: ASTM A53, TYPE E OR S, GRADE B
<br />GENERAL CONTRACTOR SHALL PROVIDE AT THE PROJECT SITE A FULL SET OF D. BOLTS, NUTS, AND WASHERS: ASTM A325
<br />CONSTRUCTION DOCUMENTS UPDATED WITH THE LATEST REVISIONS AND ADDENDA OR E. ANCHOR BOLTS: ASTM A307
<br />CLARIFICATIONS FOR THE USE BY ALL PERSONNEL INVOLVED WITH THE PROJECT. F. WELDING MATERIALS: AWS D1.1, TYPE REQUIRED FOR
<br />MATERIALS BEING WELDED
<br />DETAILS INCLUDED HEREIN ARE INTENDED TO SHOW END RESULT OF DESIGN. MINOR
<br />MODIFICAIIONS MAY BE REQUIRED TO SUIT JOB CONDITIONS OR SITUATIONS, AND SUCH
<br />MODIFICATIONS SHALL BE INCLUDED AS PART OF THE SCOPE OF WORK.
<br />THE CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO PROTECT EXISTING
<br />IMPROVEMENTS, EASEMENTS, PAVING, CURBING, ETC. DURING CONSTRUCTION UPON
<br />COMPLETION OF WORK. CONTRACTOR SHALL REPAIR ANY DAMAGE THAT MAY HAVE
<br />OCCURRED DUE TO CONSTRUCTION ON OR ABOUT THE PROPERTY.
<br />CONTRACTOR SHALL ENSURE THE GENERAL WORK AREA IS KEPT CLEAN AND HAZARD FREE
<br />DURING CONSTRUCTION AND DISPOSE OF ALL DIRT, DEBRIS, RUBBISH AND REMOVE
<br />EQUIPMENT NOT SPECIFIED AS REMAINING ON THE PROPERTY, PREMISES SHALL BE LEFT
<br />IN CLEAN CONDITION AND FREE FROM PAINT SPOTS, DUST, OR SMUDGES OF ANY NATURE,
<br />THE CONTRACTOR SHALL COMPLY WITH ALL LOCAL AND NATIONAL CODES, REGULATIONS
<br />AND SAFETY REGULATIONS, ALL OSHA REGULATIONS, ALL PUBLIC AND MUNICIPAL
<br />AUTHORITIES, AND ANY UTILITY COMPANIES' REGULATIONS AND DIRECTIVES.
<br />THE DRAWINGS AND SPECIFICATIONS ARE A GENERAL DIRECTIVE FOR THE SCOPE OF
<br />WORK. EXACT DIMENSIONS AND LOCATIONS MAY CHANGE IN THE FIELD. THE CONTRACTOR
<br />IS TO VERIFY THE DIMENSIONS AND LOCATIONS AND REPORT ANY AND ALL DISCREPANCIES
<br />TO REPRESENTATIVE. ANY MINOR ERRORS AND OMISSIONS IN THE DRAWINGS AND
<br />SPECIFICATIONS DOES NOT EXCUSE THE CONTRACTOR FROM COMPLETING THE PROJECT
<br />AND IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OF THESE DOCUMENTS.
<br />CONTRACTOR IS RESPONSIBLE FOR FIELD MEASUREMENTS TO CONFIRM LENGTHS OF CABLE
<br />TRAYS AND ELECTRICAL LINES AND ANTENNA MOUNTING.
<br />VERIFICATION THAT EXISTING TOWER/POLE/STRUCTURE CAN SUPPORT THE PROPOSED
<br />ANTENNA, COAX & ADDITIONAL EQUIPMENT LOADING IS TO BE DONE BY OTHERS.
<br />SPECIAL INSPECTIONS & STRUCTURAL OBSERVATIONS SHALL BE REQUIRED FOR ALL HIGH
<br />STRENGTH NUTS & BOLTS & ALL OTHER HIGH STRENGTH BOLTED CONNECTIONS & AS
<br />OTHERWISE REQUIRED BY 2015 IBC CHAPTER. 17.
<br />ITEMS TO BE INSPECTED SHALL INCLUDE BUT NOT BE LIMITED TO:
<br />1. HIGH STRENGTH BOLTS (REFER TO STRUCTURALS).
<br />2. CONCRETE EMBEDDED BOLTS (REFER TO STRUCTURALS).
<br />3. OTHER HIGH STRENGTH STEEL CONNECTION COMPONENTS (REFER TO STRUCTURALS).
<br />SPECIAL INSPECTIONS IN ACCORDANCE WITH IBC 110 & 1704 SHALL BE PERFORMED (AS
<br />REQUIRED) BY QUALIFIED TESTING AGENCY APPROVED BY THE
<br />ARCHITECT/ENGINEER. SPECIAL INSPECTION AGENCY SHALL BE RETAINED BY PROJECT
<br />OWNER OR THEIR RESPONSIBLE CHARGE. ARCHITECT, ENGINEER OF RECORD, & BUILDING
<br />DEPARTMENT SHALL RECEIVE COPIES OF ALL INSPECTION & TEST RESULTS. REFER TO
<br />DOCUMENTS FOR SPECIFIC INFORMATION.
<br />ALL A36 THREADED ROD & U-BOLTS SHALL BE TIGHTENED TO AISC SNUG REQUIREMENTS
<br />THE SNUG TIGHT CONDITION IS DEFINED AS THE TIGHTNESS THAT EXISTS WHEN ALL PLIES
<br />IN A JOINT ARE IN FIRM CONTACT. THIS MAY BE ATTAINED BY A FEW IMPACTS OF AN
<br />IMPACT WRENCH OR THE FULL EFFORT OF A MAN USING AN ORDINARY SPUD WRENCH.
<br />A36 NUT & BOLT TIGHTENING DOES NOT REQUIRE SPECIAL INSPECTION.
<br />A325 &/OR A490 NUTS & BOLTS TIGHTENING REQUIRE SPECIAL INSPECTION.
<br />ALL BOLTS FOR EQUIPMENT SUPPORT FRAMES & ALL OTHER STRUCTURES
<br />MOUNTED/CONNECTED TO POLES, TOWERS, PARAPETS, ETC. SHALL BE A325 HIGH
<br />STRENGTH (OR A490 HIGH STRENGTH AS REQUIRED) UNO.
<br />TIGHTEN ALL BOLTS SUPPORTING ALL ANTENNAS, RRUS, OVPS, ETC., TO AISC SNUG
<br />REQUIREMENTS.
<br />� awl -4111"leml
<br />G. GROUT: NON -SHRINK TYPE, PREMIXED
<br />COMPOUND CONSISTING OF
<br />NONMETALLIC AGGREGATE, CEMENT,
<br />WATER REDUCING AND PLASTICIZING
<br />ADDITIVES, CAPABLE OF DEVELOPING
<br />A, MINIMUM COMPRESSIVE STRENGTH
<br />OF 7000 PSI AT 28 DAYS.
<br />H. SHOP AND TOUCH-UP PRIMER: SSPC 15, TYPE 1, RED OXIDE
<br />L TOUCH-UP PRIMER FOR GALV.
<br />J. SURFACES: ZINC RICH TYPE
<br />2, FABRICATION
<br />CONTINUOUSLY SEAL JOINTED MEMBERS BY CONTINUOUS WELDS. GRIND
<br />EXPOSED WELDS SMOOTH.
<br />3. FINISH
<br />A. PREPARE STRUCTURAL COMPONENT SURFACES IN ACCORDANCE WITH SSPC
<br />SP-1 TO SP-10 PROCEDURES.
<br />B. STRUCTURAL STEEL MEMBERS SHALL BE HOT DIPPED GALVANIZED.
<br />PART 3 - EXECUTION
<br />1. EXAMINATION AND PREPARATION: VERIFY THAT THE FIELD CONDITIONS ARE
<br />ACCEPTABLE.
<br />2. ERECTION:
<br />A. ALLOW FOR ERECTION LOADS. PROVIDE TEMPORARY BRACING TO MAINTAIN
<br />FRAMING IN ALIGNMENT UNTIL COMPLETION OF ERECTION AND
<br />INSTALLATION OF PERMANENT BRIDGING AND BRACING.
<br />B. FIELD WELD COMPONENTS INDICATED ON SHOP DRAWINGS.
<br />C. DO NOT FIELD CUT OR ALTER STRUCTURAL MEMBERS WITHOUT APPROVAL C
<br />THE ARCHITECT/ENGINEER.
<br />D. AFTER ERECTION, TOUCH-UP WELDS, ABRASIONS, AND SURFACES NOT SHOP
<br />PRIMED OR GALVANIZED WITH TOUCH-UP PRIMERS AS SPECIFIED UNDER
<br />SECTION 05000,-METALS, PART 2 - PRODUCTS, H & is SURFACES TO BE IN
<br />CONTACT WITH CONCRETE NOT INCLUDED.
<br />3. FIELD QUALITY CONTROL:
<br />FIELD INSPECTION OF MEMBERS, CONNECTIONS, WELDS AND TORQUING.
<br />TELECOMMUNICATIONS WIRING COMPONENTS
<br />(COAXIAL ANTENNA CABLE)
<br />1 GENERAL
<br />A. ALL MATERIALS, PRODUCTS OR PROCEDURES INCORPORATED INTO WORK SHALL
<br />BE NEW AND OF STANDARD COMMERCIAL QUALITY.
<br />B. CERTAIN MATERIALS AND PRODUCTS WILL BE SUPPLIED BY THE OWNER (REFER
<br />TO GENERAL CONDITIONS FOR THE LIST OF OWNER FURNISHED EQUIPMENT,
<br />MATERIALS AND SUPPLIES FOR THESE ITEMS). THE CONTRACTOR IS
<br />RESPONSIBLE FOR PICKUP AND DELIVERY OF ALL SUCH MATERIALS.
<br />C. ALL OTHER MATERIALS AND PRODUCTS SPECIFIED IN THE CONTRACT DOCUMENTS
<br />SHALL BE SUPPLIED BY THE CONTRACTOR.
<br />2. MATERIALS:
<br />A. COAXIAL CABLE:
<br />a. INSTALL COAXIAL CABLE AND TERMINATIONS BETWEEN ANTENNAS AND
<br />EQUIPMENT PER MANUFACTURER'S RECOMMENDAT IONS WITH COAXIAL
<br />CABLES SUPPORTED AT NO MORE THAN 3'-0" O.C. WEATHERPROOF ALL
<br />CONNECTORS BETWEEN THE ANTENNA AND EQUIPMENT PER
<br />MANUFACTURERS' REQUIREMENTS. TERMINATE ALL COAXIAL CABLE THREE
<br />(3) FEET IN EXCESS OF EQUIPMENT LOCATION UNLESS OTHERWISE
<br />STATED.
<br />b. ALL COAX RUN LENGTHS GREATER THAN 143 FEET SHALL BE 1-5/8" AND
<br />IN LENGTH LESS THAN OR EQUAL TO 143 FEET SHALL BE 7/8".
<br />3. ANTENNA AND COAXIAL CABLE GROUNDING
<br />A. ALL COAXIAL CABLE GROUNDING KITS ARE TO BE INSTALLED ON STRAIGHT RUNS
<br />OF COAXIAL CABLE (NOT WITHIN BENDS)
<br />4. COAXIAL CABLE IDENTIFICATION
<br />A. TO PROVIDE EASY IDENTIFICATION AND UNIFORM MARKING OF ANTENNA CABLING,
<br />PLASTIC TAGS SHALL BE USED AT THE FOLLOWING LOCATIONS-.
<br />a. FIRST LOCATION IS AT THE END OF THE COAX NEAREST THE ANTENNA
<br />(WHERE THE COAXIAL CABLE AND JUMPER ARE CONNECTED).
<br />b. SECOND LOCATION IS INSIDE THE EQUIPMENT SHELTER NEAR THE
<br />WAVEGUIDE ENTRY PORT.
<br />B. USE ANDREW CABLE TIES (PT.# 27290) TO SECURE IDENTIFICATION TAGS.
<br />5. TESTING
<br />VERIZON WIRELESS SHALL PROVIDE AN INDEPENDENT TESTING AGENCY TO PERFORM THE
<br />COAXIAL SWEEP TEST & REPORT. THE CONTRACTOR IS TO PROVIDE CLIMBER / QUALIFIED
<br />PERSONNEL TO ASSIST IN ANY REPAIRS AND WEATHERPROOFING ONCE THE TEST IS
<br />COMPLETE. THE CONTRACTOR IS TO PROVIDE VERIZON WIRELESS A MINIMUM OF 48
<br />HOURS NOTICE PRIOR TO THE TIME OF THE SWEEP TEST.
<br />ELECTRICAL MOTES:
<br />INSTALLATION OF SECONDARY POWER AND CONNECTION TO METER SHALL BE COMPLETED
<br />IN COMPLIANCE WITH NATIONAL ELECTRIC CODE, NFPA 70, AND THE STATE LAWS, RULES
<br />AND REGULATIONS FOR INSTALLING ELECTRIC WIRES & EQUIPMENT, ALL LATEST ISSUE,
<br />AND WITH SPECIFICATIONS PER A.S.T.M. B 231, B 400, LC.E.A. S651 -401 , LC.E.A.
<br />P81570, & LOCAL PUD.
<br />PROVIDE A, METER BASE PER LOCAL UTILITY STANDARDS. MOUNT ON SIDE OF OWNER
<br />FURNISHED BACK BOARD.
<br />UNDERGROUND CONDUIT SHALL BE RIGID POLYVINYL CHLORIDE CONDUIT: SCHEDULE 40,
<br />TYPE 1, CONFORMING TO UL ARTICLE 651 : WESTERN PLASTICS OR CARTON
<br />MANUFACTURER. COUPLINGS SHALL BE SLIP-ON, SOLVENT SEALED T PIPE: SOLVENT,
<br />WESTERN TYPE COMPATIBLE WITH PVC DUCT. ALL BENDS SHALL BE "WIDE SWEEP" TYPE
<br />WITH A 24" MINIMUM RADIUS, ALL CONDUIT UNDER ROADS SHALL BE RGS, (OR PVC
<br />ENCASED IN 8"X18" RED CONCRETE DUCTBANK).
<br />CONDUIT USED INDOORS SHALL BE E.M. T ., AND RIGID GALVANIZED STEEL FOR OUTDOORS.
<br />COUPLINGS SHALL BE RIGID STEEL AND COMPRESSION TYPE FOR E.M.T. SET SCREW
<br />FITTINGS ARE NOT PERMITTED. FOR ALL STUBS -UPS, USE RIGID GALVANIZED STEEL
<br />CONDUIT.
<br />WIRE AND CABLE SHALL BE OF THE TYPE AND SIZE AS REQUIRED BY NEC. THERE WILL
<br />BE NO SPLICES ALLOWED. PROVIDE HDPE PULLING HAND HOLES AS NEEDED.
<br />CONTRACTOR SHALL PROVIDE TEST OF THE GROUNDING SYSTEM BY CERTIFIED TESTING
<br />AGENT. PROVIDE INDEPENDENT TEST RESULTS TO THE PROJECT MANAGER FOR REVIEW.
<br />GROUNDING SYSTEM RESISTANCE TO GROUND SHALL NOT EXCEED 5 OHMS. ALL ABOVE
<br />GRADE INTERIOR GROUNDING CONNECTORS SHALL BE DOUBLE -LUG COMPRESSION TYPE.
<br />ALL BELOW GRADE AND EXPOSED EXTERIOR GROUNDING CONNECTIONS TO PERMANENT
<br />EQUIPMENT AND FIXED BUILDING ELEMENTS SHALL BE CADWELD TYPE, CARE SHALL BE
<br />TAKEN TO REVIEW CONNECTION LOCATIONS AND MATERIAL TYPES TO AVOID POSSIBLE
<br />GALVANIC CORROSION. ALL EXPOSED GROUNDING CONNECTIONS TO BE COATED WITH
<br />ANTI -CORROSIVE AGENT SUCH AS "NO-OXY", "NOAOLX" OR "PENETROX". VERIFY
<br />PRODUCT WITH PROJECT MANAGER. ALL BOLTS, WASHERS AND NUTS USED ON
<br />GROUNDING CONNECTIONS SHALL BE STAINLESS STEEL.
<br />ALL EXTERIOR GROUND BARS SHALL BE COATED WITH ANTI -CORROSIVE AGENT SUCH AS
<br />LPS-3 OR AS PER NOTE 6 ABOVE.
<br />ALL JUNCTION AND OUTLET BOXES TO BE LABELED WITH KROY TAPE, OR EQUAL,
<br />DESIGNATING ALL CIRCUIT NUMBERS CONTAINED IN EACH BOX.
<br />CONTRACTOR TO ENSURE ILC PROVIDED WITH (2) INTERNAL TVSS,
<br />CONTRACTOR SHALL COORDINATE WITH SITE SURVEY TO LOCATE EXISTING UNDERGROUND
<br />UTILITIES. WHEREVER POTENTIAL CONFLICTS/ INTERFERENCES EXIST, HAND EXCAVATE TO
<br />AVOID DAMAGE. CONTACT ALL UTILITIES TO LOCATE UNDERGROUND PIPING IN PUBLIC
<br />ROW.
<br />VERIFY THAT A.I.C. OF THE UTILITY DOES NOT EXCEED THE A.LC, RATING OF THE
<br />PROVIDED EQUIPMENT SHELTER PACKAGE. IF OVER 10KAIC, PROVIDE FUSIBLE SERVICE
<br />ENTRANCE SWITCH AND CONFIRM LOWERING OF AIC TO ACCEPTABLE LEVELS.
<br />UTILITY POINTS OF SERVICE AND WORK / MATERIALS SHOWN ARE BASED UPON
<br />PRELIMINARY INFORMATION PROVIDED BY THE UTILITY COMPANIES AND ARE FOR BID
<br />PURPOSES ONLY.
<br />CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FOR FINAL AND EXACT WORK f
<br />MATERIALS REQUIREMENTS AND CONSTRUCT TO UTILITY COMPANY ENGINEERING PLANS AND
<br />SPECIFICATIONS ONLY. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, PULL
<br />ROPES, CABLES, PULL BOXES, CONCRETE ENCASEMENT OF CONDUIT (IF REQUIRED),
<br />TRANSFORMER PAD, BARRIERS, POLE RISERS, TRENCHING, BACKFILL, PAY ALL UTILITY
<br />COMPANY FEES AND INCLUDE ALL REQUIREMENTS IN SCOPE OF WORK.
<br />�t1�11�T�11��7LCs�7
<br />1. 1ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE DESIGN
<br />AND CONSTRUCTION SPECIFICATIONS AND ALL APPLICABLE LOCAL CODES.
<br />2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT
<br />ACCESS TO EQUIPMENT IS NOT BLOCKED.
<br />3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND
<br />UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN . THE
<br />GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT.
<br />4. ALL GROUND CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC (CADWELD)
<br />5. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR & EXTERIOR) SHALL BE FORMED
<br />USING TWO (2) HIGH PRESS CRIMPS.
<br />6. ALL EXOTHERMIC CONNECTIONS TO THE GROUND RODS SHALL START AT THE TOP &
<br />HAVE A VERTICAL SEPARATION OF 6" FOR EVERY ADDITIONAL CONNECTION.
<br />7. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION
<br />RESISTANT MATERIAL.
<br />8. ALL EXTERIOR GROUND CONDUCTORS SHALL BE #2 AWG TIN PLATED COPPER UNLESS
<br />OTHERWISE INDICATED.
<br />9. GROUND RODS SHALL BE STAINLESS STEEL OR COPPER CLAD STEEL, 5/8" 0 10-FT.
<br />LONG (OR NOTED OTHERWISE ON PLANS), AND SHALL BE DRIVEN VERTICALLY WITH THEIR
<br />TOPS 18" BELOW FINAL GRADE OR 6" BELOW FROST LINE FOR MAXIMUM DEPTH.
<br />10. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED. BACK
<br />TO BACK CONNECTIONS ON OPPOSITE SIDES OF THE GROUND BUS ARE PERMITTED.
<br />1 1 . USE OF 90 BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED
<br />WHEN 45° BENDS CAN BE ADEQUATELY SUPPORTED.
<br />12. GROUND RING SHALL BE LOCATED A MINIMUM OF 24" BELOW GRADE OR 6" MINIMUM
<br />BELOW THE FROST LIME.
<br />13. INSTALL GROUND CONDUCTORS AND GROUND ROD MINIMUM OF 1'0" FROM
<br />EQUIPMENT CONCRETE PAD, SPREAD FOOTING, OR FENCE.
<br />14. EXOTHERMIC WELD GROUND CONNECTION TO FENCE POST: TREAT WITH A COLD
<br />GALVANIZED SPRAY,
<br />15, OBSERVE N,E.C. AND LOCAL UTILITY REQUIREMENTS FOR ELECTRICAL SERVICE
<br />GROUNDING
<br />16. GROUNDING ATTACHMENT TO TOWER SHALL BE AS PER MANUFACTURER'S
<br />RECOMMENDATIONS OR AT GROUNDING POINTS PROVIDED (2 MINIMUM)
<br />17. MAXIMUM RESISTANCE OF THE COMPLETED GROUND SYSTEM SHALL NOT EXCEED 5
<br />OHMS.
<br />18. CONTRACTOR TO VERIFY CURRENT GROUNDING STANDARDS PRIOR TO CONSTRUCTION
<br />k
<br />CA.$
<br />ASSOCIATES
<br />19401 40TH AVE. W., SUITE 304
<br />LYNNWOOD, WA 93036
<br />PHONE: (425) 740-6392
<br />WWW.CAMPASSOC.COM
<br />SKS
<br />12/27/18
<br />ISSUED FOR PERMIT
<br />SKS
<br />12/20/18
<br />ISSUED FOR PRELIM REVIEW
<br />
|