01
<br />GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL ISSUE A CHANGE ORDER PROPOSAL ON FORM ACCEPTABLE TO
<br />OWNER TO THE ARCHITECT AND OWNER FOR SIGNATURE. FIELD DIRECTIVES AND/OR CHANGES SHALL NOT BE INCLUDED IN THE
<br />WORK UNTIL THE ARCHITECT AND OWNER HAVE SIGNED THE CHANGE ORDER. NO WORK IS TO BE DONE AT THE REQUEST OF
<br />THE WAREHOUSE MANAGER.
<br />B. THE GENERAL CONTRACTOR IS THE PROJECT COORDINATOR, AND SHALL PROVIDE COORDINATION AND CONTROL FOR ALL WORK
<br />OF THE ENTIRE CONTRACT INCLUDED IN THESE CONTRACT DOCUMENTS AND SPECIFIED HEREIN.
<br />014000 - QUALITY REQUIREMENTS
<br />A. COSTS FOR INSPECTIONS AND TESTS REQUIRED BY BUILDING OFFICIALS AND REQUESTED BY OWNER ON EARTHWORK, STEEL
<br />WORK, AND CONCRETE PLACED ON THE SITE WILL BE PAID BY THE OWNER.
<br />B. COSTS FOR RE -INSPECTIONS AND RE -TESTS, AND ADDED COSTS FOR INSPECTIONS AND TESTS DUE TO POOR WORKMANSHIP,
<br />NON-COMPLIANCE WITH THE CONTRACT DOCUMENTS, LATE SCHEDULING, CANCELLATIONS, OR ILL-TIMED NOTICES ARE THE
<br />RESPONSIBILITY OF THE CONTRACTOR.
<br />1. WHEN INITIAL TESTS DISPLAY NON-COMPLIANCE WITH THE CONTRACT DOCUMENTS, THE SAME TESTING AGENCY THAT
<br />PERFORMED THE INITIAL TESTS SHALL DO THE WORK OF RE -INSPECTION OR RE -TESTING THE EARLIER TESTS.
<br />2. PAYMENT FOR RE -INSPECTION OR RE -TEST COSTS WILL BE MADE TO THE TESTING AGENCY BY THE OWNER, BUT THE CONTRACT
<br />SUM IN THE AGREEMENT BETWEEN OWNER AND CONTRACTOR WILL BE ADJUSTED BY CHANGE ORDER TO RECOVER THE COST.
<br />C. COMPLY WITH MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF MATERIALS AND EQUIPMENT.
<br />015000 - TEMPORARY FACILITIES
<br />A. TEMPORARY UTILITIES: USE OF OWNER'S EXISTING ELECTRICAL, SEWAGE, AND WATER WILL BE PERMITTED WITHOUT METERING.
<br />CONTRACTOR SHALL PROVIDE SAFE TEMPORARY CONNECTIONS AND MAINTAIN CONDITIONS ACCEPTABLE TO THE OWNER.
<br />B. SANITARY FACILITIES: USE OF OWNER'S EXISTING TOILET FACILITIES WILL BE PERMITTED, AS LONG AS FACILITIES ARE CLEANED
<br />AND MAINTAINED IN A CONDITION ACCEPTABLE TO OWNER. AT SUBSTANTIAL COMPLETION, RESTORE THESE FACILITIES TO
<br />CONDITION EXISTING BEFORE INITIAL USE.
<br />C. TEMPORARY PARTITIONS: PROVIDE DUSTPROOF PARTITIONS TO LIMIT DUST AND DIRT MIGRATION AND TO SEPARATE AREAS
<br />OCCUPIED BY OWNER FROM FUMES AND NOISE.
<br />1. INSULATE PARTITIONS TO CONTROL NOISE TRANSMISSION TO OCCUPIED AREAS.
<br />2. SEAL JOINTS AND PERIMETER. EQUIP PARTITIONS WITH GASKETED DUSTPROOF DOORS AND SECURITY LOCKS WHERE
<br />OPENINGS ARE REQUIRED.
<br />3. PROTECT AIR -HANDLING EQUIPMENT.
<br />4. PROVIDE WALK -OFF MATS AT EACH ENTRANCE THROUGH TEMPORARY PARTITION.
<br />5. PLASTIC SHEETING USED SHALL BE FLAME RESISTANT.
<br />D. BARRICADES, WARNING SIGNS, AND LIGHTS:
<br />1. PROVIDE FENCES AND SAFEGUARDS NECESSARY FOR THE CONVENIENCE AND PROTECTION OF THE PUBLIC, AS REQUIRED BY
<br />CODE AND LAW ENFORCEMENT REGULATIONS.
<br />017329 - CUTTING AND PATCHING
<br />A. CUTTING: CUT EXISTING CONSTRUCTION BY SAWING, DRILLING, BREAKING, CHIPPING, GRINDING, AND SIMILAR OPERATIONS,
<br />INCLUDING EXCAVATION, USING METHODS LEAST !LIKELY TO DAMAGE ELEMENTS RETAINED OR ADJOINING CONSTRUCTION.
<br />1. IN GENERAL, USE HAND OR SMALL POWER TOOLS DESIGNED FOR SAWING AND GRINDING, NOT HAMMERING AND CHOPPING.
<br />CUT HOLES AND SLOTS AS SMALL AS POSSIBLE, NEATLY TO SIZE REQUIRED, AND WITH MINIMUM DISTURBANCE OF ADJACENT
<br />SURFACES. TEMPORARILY COVER OPENINGS WHEN NOT IN USE.
<br />2. EXISTING FINISHED SURFACES: CUT OR DRILL FROM THE EXPOSED OR FINISHED SIDE INTO CONCEALED SURFACES.
<br />3. CONCRETE, MASONRY: CUT USING A CUTTING MACHINE, SUCH AS AN ABRASIVE SAW OR A DIAMOND CORE DRILL.
<br />4. MECHANICAL AND ELECTRICAL SERVICES: CUT OFF PIPE OR CONDUIT IN WALLS OR PARTITIONS TO BE REMOVED. CAP, VALVE,
<br />OR PLUG AND SEAL REMAINING PORTION OF PIPE OR CONDUIT TO PREVENT ENTRANCE OF MOISTURE OR OTHER FOREIGN
<br />MATTER AFTER CUTTING.
<br />B. PATCHING: PATCH CONSTRUCTION BY FILLING, REPAIRING, REFINISHING, CLOSING UP, AND SIMILAR OPERATIONS FOLLOWING
<br />PERFORMANCE OF OTHER WORK. PATCH WITH DURABLE SEAMS THAT ARE AS INVISIBLE AS POSSIBLE. PROVIDE MATERIALS AND
<br />COMPLY WITH INSTALLATION REQUIREMENTS SPECIFIED IN OTHER SECTIONS OF THESE SPECIFICATIONS.
<br />1. EXPOSED FINISHES: RESTORE EXPOSED FINISHES OF PATCHED AREAS AND EXTEND FINISH RESTORATION INTO RETAINED
<br />ADJOINING CONSTRUCTION IN A MANNER THAT WILL ELIMINATE EVIDENCE OF PATCHING AND REFINISHING.
<br />2. FLOORS AND WALLS: WHERE WALLS OR PARTITIONS THAT ARE REMOVED EXTEND ONE FINISHED AREA INTO ANOTHER, PATCH
<br />AND REPAIR FLOOR AND WALL SURFACES IN THE NEW SPACE. PROVIDE AN EVEN SURFACE OF UNIFORM FINISH, COLOR,
<br />TEXTURE, AND APPEARANCE. REMOVE EXISTING FLOOR AND WALL COVERINGS AND REPLACE WITH NEW MATERIALS, IF
<br />NECESSARY, TO ACHIEVE UNIFORM COLOR AND APPEARANCE.
<br />3. WHERE PATCHING OCCURS IN A PAINTED SURFACE, APPLY PRIMER AND INTERMEDIATE PAINT COATS OVER THE PATCH AND
<br />APPLY FINAL PAINT COAT OVER ENTIRE UNBROKEN SURFACE CONTAINING THE PATCH. PROVIDE ADDITIONAL COATS UNTIL
<br />PATCH BLENDS WITH ADJACENT SURFACES.
<br />4. CEILINGS: PATCH, REPAIR, OR RE -HANG EXISTING CEILINGS AS NECESSARY TO PROVIDE AN EVEN PLANE SURFACE OF UNIFORM
<br />APPEARANCE.
<br />33300 - CONCRETE FLOOR AND CURBS
<br />A. PROPORTIONING AND DESIGN OF CONCRETE MIXES:
<br />1. PREPARE DESIGN MIX FOR 3500 PSI STRENGTH CONCRETE BY EITHER LABORATORY TRIAL BATCH OR FIELD EXPERIENCE
<br />METHODS AS SPECIFIED IN ACI 301. IF TRIAL BATCH METHOD USED, USE AN INDEPENDENT TESTING FACILITY FOR PREPARING
<br />AND REPORTING PROPOSED MIX DESIGNS. THE TESTING FACILITY SHALL NOT BE THE SAME AS USED FOR FIELD QUALITY
<br />CONTROL TESTING.
<br />2. USE NO FLY ASH IN CONCRETE.
<br />3. USE NO AIR ENTRAINMENT.
<br />B. CONCRETE SLAB REPAIR PRODUCT: TWO-PART HYBRID URETHANE THAT COMBINES WITH SAND TO FORM ATOUGH INSTANT
<br />POLYMER CONCRETE.
<br />1. ACCEPTABLE PRODUCT: "10-MINUTE CONCRETE MENDER" (VOC 5.5 G/L) MANUFACTURED BY ROADWARE INC., 2100
<br />WENTWORTH AVE., SOUTH SAINT PAUL, MN S5075; PHONE: (800) 5227623 OR (651) 457-6122; FAX: (651) 457-1420;
<br />WWW.CONCRETEMENDER.COM.
<br />051200- STRUCTURAL STEEL FRAMING
<br />A. STEEL MATERIALS: STRUCTURAL QUALITY, OF SIZES AND TYPES NOTED ON STRUCTURAL DRAWINGS.
<br />1. CARBON STEEL SHAPES, PLATES AND BARS ASTM A 36/A 36M.
<br />2. STEEL TUBE SECTIONS: ASTM A 500/A 500M, GRADE B.
<br />B. WELDED, RIVETED OR BOLTED CONNECTIONS IN ACCORDANCE WITH AISC CODE.
<br />1. WELDING IN ACCORDANCE WITH CURRENT "CODE FOR ARC AND GAS WELDING IN BUILDING CONSTRUCTION" OF AMERICAN
<br />WELDING SOCIETY.
<br />2. HOLES PUNCHED OR DRILLED; CUTTING TORCH NOT PERMITTED.
<br />054000 - COLD FORMED METAL FRAMING
<br />A. WALL FRAMING: MANUFACTURER'S STANDARD STEEL STUDS, OF WEB DEPTHS INDICATED, WITH STIFFENED FLANGES,
<br />COMPLYING WITH ASTM C 955, AND AS FOLLOWS:
<br />1. MINIMUM UNCOATED -STEEL THICKNESS: 18 GAUGE 0.0428 INCH.
<br />2. FLANGE WIDTH: 1-5/8 INCHES (41 MM).
<br />3. TRACK: MANUFACTURER'S STANDARD U-SHAPED STEEL TRACK, UNPUNCHED, WITH STRAIGHT FLANGES, COMPLYING WITH
<br />ASTM C 955, MANUFACTURER'S STANDARD FLANGE WIDTH, AND MINIMUM UNCOATED -STEEL THICKNESS MATCHING STEEL
<br />STUDS.
<br />B. JOIST FRAMING: MANUFACTURER'S STANDARD C-SHAPED STEELJOISTS, OF WEB DEPTHS INDICATED, UNPUNCHED, WITH
<br />STIFFENED FLANGES, COMPLYING WITH ASTM C 955. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, USE THE FOLLOWING:
<br />1. MINIMUM UNCOATED -STEEL THICKNESS: 16 GAUGE 0.0538 INCH.
<br />2. FLANGE WIDTH: 1-5/8 INCHES (41 MM), MINIMUM.
<br />3. TRACK: MANUFACTURER'S STANDARD U-SHAPED STEEL JOIST TRACK, OF WEB DEPTHS INDICATED, UNPUNCHED, WITH
<br />UNSTIFFENED FLANGES, COMPLYING WITH ASTM C 955, AND AS FOLLOWS:
<br />a. MINIMUM UNCOATED -STEEL THICKNESS: MATCHING STEELJOISTS.
<br />b. FLANGE WIDTH: 1-5/8 INCHES (41 MM), MINIMUM.
<br />C. ACCESSORIES:
<br />1. FABRICATE STEEL -FRAMING ACCESSORIES OF THE SAME MATERIAL AND FINISH USED FOR FRAMING MEMBERS, WITH
<br />MINIMUM YIELD STRENGTH OF 33,000 PSI, OF MANUFACTURER'S STANDARD THICKNESS AND CONFIGURATION, UNLESS
<br />OTHERWISE INDICATED.
<br />2. EXPANSION ANCHORS: FABRICATED FROM CORROSION -RESISTANT MATERIALS, WITH CAPABILITY TO SUSTAIN, WITHOUT
<br />FAILURE, A LOAD EQUAL TO 5 TIMES DESIGN LOAD, AS DETERMINED BY TESTING PER ASTM E 488 CONDUCTED BY A QUALIFIED
<br />INDEPENDENT TESTING AGENCY.
<br />068316 - FIBERGLASS REINFORCED PANELS
<br />A. ACCEPTABLE PRODUCTS: PROVIDE FRPP HAVING UL (ULC) CLASSIFIED CLASS A INTERIOR FINISH MATERIAL PER ASTM E 84, 3/32
<br />(.090) INCH THICK, WITH SIZE OF 4 x 8 FEET OR 4 x 10 FEET.
<br />1. CRANE COMPOSITES; FIRE-X GLASBORD WITH SURFASEAL, PRODUCT CODE 6226, CLASS A, WITH EMBOSSED TEXTURE.
<br />a. COLOR: #85 WHITE.
<br />2. NUDO FIBERLITE FRP PANELS, CLASS A, WITH PEBBLE TEXTURED SURFACE.
<br />a. COLOR: 050 WHITE.
<br />3. MARLITE STANDARD FRP PANELS, CLASS A, WITH PEBBLE TEXTURED SURFACE.
<br />a. COLOR: P199 BRITE WHITE.
<br />D. ACCESSORIES:
<br />1. ADHESIVE: PROVIDE PANEL ADHESIVE AS RECOMMENDED BY PANEL MANUFACTURER.
<br />2. TRIM AND SEAM TREATMENT: EXTRUDED PVC CORNER MOLDINGS, DIVISION BARS, END TRIM AND CAP.
<br />a. COLOR: WHITE TO MATCH PANEL COLOR.
<br />079200 - JOINT SEALANTS
<br />A. INTERIOR JOINTS BETWEEN PLUMBING FIXTURES AND ADJOINING WALLS, FLOORS, AND COUNTERS; AND BETWEEN POLYMER
<br />FLOOR BASE AND MIP / FRPP: USE SINGLE -COMPONENT MILDEW -RESISTANT ACID -CURING SILICONE SEALANT. USE WHITE COLOR
<br />AT PORCELAIN FIXTURES, GREY COLOR AT STAINLESS STEEL, OR OTHER APPROPRIATE COLOR TO MATCH ADJACENT SURFACE
<br />FINISHES.
<br />1. ACCEPTABLE PRODUCTS:
<br />a. 786 MILDEW RESISTANT (VOC 33 G/L) BY DOW CORNING CORP., 2200 W. SALZBURG ROAD, MIDLAND, MI 48686-0994, PH:
<br />(800) 248-2481 OR (989) 496-4400, FAX: (989) 496-4393, HTTP://WWW.DOWCORNING.COM.
<br />b. SANITARY SCS1700 (VOC 20 G/L) BY GE CONSTRUCTION SEALANT, 9930 KINCEY AVENUE, HUNTERSVILLE, NC 28078, PH: (800)
<br />255-8886 OR (877) 943-7325, FAX: (304) 746-1654, HTTP://WWW.GESEALANTS.COM.
<br />2. TYPE AND GRADE: S (SINGLE COMPONENT) AND NS (NONSAG).
<br />3. CLASS: 25.
<br />4. USE RELATED TO EXPOSURE: NT.
<br />092116 -GYPSUM BOARD ASSEMBLIES
<br />A. STEEL FRAMING, GENERAL: COMPLY WITH ASTM C 754 AND ASTM C 840 FOR CONDITIONS INDICATED.
<br />1. STEEL SHEET COMPONENTS: METAL COMPLYING WITH ASTM C 645 REQUIREMENTS.
<br />2. PROTECTIVE COATING: ASTM A 653 / A 653M, G60, HOT -DIP GALVANIZED ZINC COATING.
<br />B. INTERIOR GYPSUM WALLBOARD: COMPLYING WITH ASTM C 36/C 36M OR ASTM C 1396/C 1396M, AS APPLICABLE TO TYPE OF
<br />GYPSUM BOARD INDICATED AND WHICHEVER IS MORE STRINGENT.
<br />1. USE 5/8-INCH THICK, TYPE X, WITH LONG EDGES TAPERED, TYPICAL.
<br />C. BEHIND WALL TILE, STAINLESS STEEL WALL LINING, FIBERGLASS REINFORCED PLASTIC PANELS (FRPP) IN FOOD PREPARATION
<br />AREAS: PROVIDE 5/8 INCH THICK, GYPSUM FIBER INTERIOR PANELS WITHOUT FACE PAPER.
<br />1. ACCEPTABLE PRODUCT: "FIBEROCK BRAND AQUA TOUGH INTERIOR PANELS" MANUFACTURED BY USG.
<br />096700 - POLYMER FLOORING
<br />A. THE OWNER HAS A NATIONAL ACCOUNT WITH HTI POLYMER, INC. TO SUPPLY ALL PRODUCTS SPECIFIED IN THIS SECTION.
<br />HTI POLYMER, INC.
<br />18732 142ND AVE NE
<br />WOODINVILLE, WA 98072
<br />CONTACT: CHRIS CAMPTON
<br />PHONE: (425) 487-8911 / (866) 930-8911
<br />FAX: (425) 487-0915
<br />EMAIL: CHRIS@HTIPOLYMER.COM
<br />B. A FOUR -WEEK NOTICE IS REQUIRED PRIOR TO INSTALLATION OF POLYMER FLOORS.
<br />C. PF-A: GENERAL POLYMERS FASTOP 12 TC URETHANE CEMENT SYSTEM:
<br />1. PENETRATING, MOISTURE TOLERANT TWO -COMPONENT EPDXY WATER EMULSION PRIMER, APPLIED AT 250-300 SQ. FT. / GAL.
<br />a. APPROVED PRODUCT: GENERAL POLYMERS 3477.
<br />2. THREE -COMPONENT URETHANE CEMENT SLURRY, APPLIED AT 40 SQ. FT. PER MIXED UNIT (NOMINAL 1/4-INCH THICK FOR THIS
<br />MORTAR LAYER COMPONENT OF THE SYSTEM).
<br />a. APPROVED PRODUCT: GENERAL POLYMERS FASTOP 12 S.
<br />3. THREE -COMPONENT URETHANE CEMENT TOPCOAT SEALER, APPLIED WITH A SPRAYER APPARATUS.
<br />a. APPROVED PRODUCT: GENERAL POLYMERS FASTOP TC.
<br />b. COLOR: MATCH EXISTING.
<br />D. HONOR ALL CONTROL JOINTS IN THE CONCRETE SLAB BY CUTTING THROUGH THE URETHANE CEMENT FLOOR AND INSTALLING A
<br />JOINT FILLER.
<br />a. APPROVED PRODUCT: METZGER MCGUIRE SPAL-PRO RS 88 POLYUREA JOINT' FILLER.
<br />b. COLOR: GRAY.
<br />097000 - STAINLESS STEEL PANELS
<br />A. STAINLESS -STEEL SHEET: USE 20 GAUGE (0.036 INCH) (0.91 MM) ASTM A 666, TYPE 304 STAINLESS STEEL SHEETS.
<br />1. GENERAL: COMPLY WITH SSINA'S "FINISHES FOR STAINLESS STEEL" FOR RECOMMENDATIONS FOR APPLYING AND
<br />DESIGNATING FINISHES.
<br />2. REMOVE TOOL AND DIE MARKS AND STRETCH LINES OR BLEND INTO FINISH. GRIND AND POLISH SURFACES TO PRODUCE
<br />UNIFORM, DIRECTIONALLY TEXTURED, POLISHED FINISH INDICATED, FREE OF CROSS SCRATCHES. RUN GRAIN WITH LONG
<br />DIMENSION OF EACH PIECE.
<br />3. STAINLESS -STEEL FINISHES:
<br />a. EXPOSED SURFACES: ASTM A 480 / A 480M, NO. 4 FINISH.
<br />b. CONCEALED SURFACES: ASTM A 480 / A 480M, NO. 2B FINISH (BRIGHT, COLD -ROLLED, UNPOLISHED FINISH).
<br />4. FABRICATE THE FOLLOWING WALL PANEL JOINT CONNECTORS AND COVERS USING MATCHING MATERIAL:
<br />a. PANEL CORNER, CENTER, AND END SLIP JOINTS, CLEATS, AND MOLDINGS
<br />b. TOP, BOTTOM, AND END PANEL EDGE COVERS AND FLASHINGS.
<br />c. FORMED AND MATCHING END TRIM.
<br />099100 - PAINTING
<br />A. UN -GALVANIZED AND GALVANIZED STEEL:
<br />1. SHERWIN-WILLIAMS:
<br />a. FIRST COAT: PRO INDUSTRIAL PRO-CRYL UNIVERSAL WATER BASED PRIMER B66-310 SERIES (2.0-4.0 MILS DRY) (VOC < 100
<br />G/L)
<br />b. SECOND AND THIRD COATS: PROMAR 200 ZERO VOC INTERIOR LATEX B31-2600 SEMIGLOSS B31WO2651 (1.6 MILS DRY PER
<br />COAT).
<br />2, PPG:
<br />a. FIRST COAT: 90-912 PITT TECH PLUS DTM ACRYLIC PRIMER (2.0-4.0 MILS DRY).
<br />b. SECOND AND THIRD COATS: 6-4510 SERIES SPEEDHIDE INTERIOR ZERO VOC LATEX SEMIGLOSS (1.3 MILS DRY PER COAT).
<br />3. COLOR TO MATCH SHERWIN-WILLIAMS SW 7030 "ANEW GRAY".
<br />B, GYPSUM WALLBOARD:
<br />1. SHERWIN-WILLIAMS:
<br />a. FIRST COAT: PROMAR 400 ZERO VOC INTERIOR LATEX PRIMER B28WO4600 (1.1 MILS DRY PER COAT).
<br />b. SECOND AND THIRD COATS: PROMAR 200 ZERO VOC INTERIOR LATEX B20-2600 EG-SHEL B20W12651 (1.7 MILS DRY PER
<br />COAT).
<br />2. PPG:
<br />a. FIRST COAT: 6-2 SPEEDHIDE INTERIOR LATEX PRIMER (1.2 MILS DRY) (VOC < 46 G/L).
<br />b. SECOND AND THIRD COATS: 6-4310 SERIES SPEEDHIDE INTERIOR ZERO VOC LATEX EGGSHELL (1.5 MILS DRY PER COAT) (VOC
<br />0 G/L).
<br />3. COLOR OF GENERAL WALLBOARD APPLICATIONS: COLOR TO MATCH SHERWIN-WILLIAMS SW 7003 "TOQUE WHITE", EXCEPT
<br />WHERE NOTED ON DRAWINGS.