GENERAL NOTE SPECIAL CONDITIONS <br />REMODEL CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND SHALL PROVIDE ADEQUATE <br />SHORING AND BRACING OF ALL STRUCTURAL MEMBERS DURING CONSTRUCTION. CONTRACTOR <br />THE FOLLOWING NOTES APPLY UNLESS NOTED OTHERWISE - ASTM'S NOTED ARE TO BE LATEST SHALL NOTIFY ENGINEER OF ALL FIELD CHANGES PRIOR TO INSTALLATION. <br />EDITION. <br />1. DESCRIPTION <br />Building Name & Site Location - Costco Wholesale - Everett, WA <br />2, DESIGN CODE AND STANDARDS <br />Applicable Code (Edition/Name) - 2015 International Building Code (IBC) <br />Other documents referenced by these notes shall be the specific edition referenced by the <br />~✓ v IV- v v \/' <br />DEFERRED SUBMITTALS <br />THE STRUCTURAL DESIGN FOR DEFERRED SUBMITTALS (BELOW SHALL FOLLOW THE DESIGN <br />LOADS INDICATED IN THIS GENERAL NOTE. <br />1. METAL INSULATED PANEL COMPRESSOR HOUSE. t <br />2. METAL GUARD RAIL AT CATWALK. <br />building code specified above, or if not specified, shall be the latest edition. <br />ABBREVIATIONS <br />ARCH. <br />ARCHITECT <br />ESIGN LO S <br />BAL. <br />BALANCE <br />a. Roof Snow Load 25 psf (snow drift is not required). 1 <br />B. OR BOT. <br />BTWN. <br />BOTTOM <br />BETWEEN <br />_ <br />BLDG. <br />(BUILDING <br />b. Slab Live Sac''" 250 psf <br />ERG. <br />BEARING <br />c. Seismic Risk Category 11 <br />C.I.P. <br />CAST IN PLACE <br />& M 1 A16, S, ® 0.544, le 1.0, Site Class "D" and <br />C.J. <br />CONSTRUCTION JOINT <br />S,S z 0.944, So, = 0.544. <br />CL <br />CENTERLINE <br />Seismic .Design Category y "D" <br />CLR. <br />CLEAR <br />d. Wind Load Risk Category 11 <br />CMU <br />CONCRETE MASONRY UNIT <br />Basic wind speed (3 sec. gust) VuLT= 110 mph , VASD : 85 mph <br />COL. <br />COLUMN <br />Exposure B <br />CONC. <br />CONCRETE. <br />Kzt=1.0 <br />C.S.J. <br />CLOSURE STRIP JOINT <br />!BC Load Cases per sec. 1605.2.1 or 1605.3.1 only Kd = 0.85 <br />EA. <br />EACH <br />Importance factor 1.0. <br />E.E. <br />EACH END <br />e. Load Combinations All Code required load combinations are to be used in the building design. <br />E.F. <br />EACH FACE <br />E.J. <br />EXPANSION JOINT <br />OSHASTANDARDS <br />EL. OR ELEV. <br />ELEVATION <br />THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PROVISIONS OF THE CURRENT <br />E.N.W. OR ENW ENGINEERS NORTHWEST <br />OSHA STANDARDS. THE GENERAL CONTRACTOR SHALL REVIEW THESE STRUCTURAL <br />EQ. <br />EQUAL <br />DRAWINGS FOR ANY NONCOMPLIANCE WITH OSHA STANDARDS, TAKING INTO ACCOUNT THE <br />E.S. <br />EACH SIDE <br />GENERAL CONTRACTOR'S MEANS AND METHODS. THE GENERAL CONTRACTOR SHALL INFORM <br />E.W. <br />EACH WAY <br />ENW OF ANY NONCOMPLIANCE SO THE DRAWINGS MAY BE MODIFIED FOR COMPLIANCE PRIOR. <br />F.O.C. <br />FACE OF CONCRETE <br />TO CONSTRUCTION. THE GENERAL CONTRACTOR IS TOTALLY RESPONSIBLE FOR MEANS AND <br />F.O.S. <br />FACE OF STUD <br />METHODS AS WELL AS JOBSITE SAFETY ON THIS PROJECT. <br />F.O.W. <br />FACE OF WALL <br />FTG. <br />FOOTING <br />CONCRETE <br />GA. <br />GAGE <br />F'c=4000 PSI. @a 28 DAYS 5-1/2 SACKS MINIMUM CEMENT PER CUBIC 'YARD FOR ALL CONCRETE <br />GALV, <br />HOT DIP GALVANIZED <br />SLABS. <br />G..B. <br />GYPSUM WALL BOARD <br />F'c=3000 PSI. @ 28 DAYS 5-1/2 SACKS MINIMUM CEMENT PER CUBIC YARD FOR ALL OTHER. <br />H. OR HORIZ. <br />HORIZONTAL <br />USE TYPE 1/11 CEMENT. FOR SPECIAL CONDITIONS ANOTHER TYPE CEMENT MAY BE REQUIRED. <br />I.B.C. <br />INTERNATIONAL BUILDING CODE <br />SUBMIT FOR APPROVAL. ULTIMATE STRENGTH DESIGN METHOD USED. MIXING AND PLACING OF <br />E.C.C. <br />INTERNATIONAL CODE COUNCIL <br />ALL CONCRETE AND SELECTION OF MATERIALS SHALL BE IN ACCORDANCE WITH THE ACI CODE <br />LF <br />INSIDE FACE <br />318. PROPORTIONING OF AGGREGATE TO CEMENT SHALL BE SUCH AS TO PRODUCE A DENSE <br />INC. <br />INCLUDING <br />WORKABLE MIX WITH 4" MAXIMUM SLUMP (UNLESS SUPERPLASTICIZERS ARE USED) WHICH CAN <br />K <br />KIP (1000 POUNDS) <br />BE PLACED WITHOUT SEGREGATION OR EXCESS FREE SURFACE WATER. FOR ADMIXTURES, <br />L.W. <br />LONG WAY <br />SEE. SPECIFICATIONS. MAXIMUM WATER/CEMENT RATIO = 0.49. 3/4" CHAMFER ALL EXPOSED <br />M.B.S. <br />METAL BLDG SUPPLIER <br />EDGES, UNLESS INDICATED OTHERWISE ON ARCHITECTURAL DRAWINGS. WATER CURING SHALL <br />N.F. <br />NEAR FACE <br />BE USED. AIR ENTRAIN ALL HORIZONTAL CONCRETE EXPOSED TO WEATHER WITH 3% TO 6% AIR <br />N.T.S. <br />NOT TO SCALE <br />BY VOLUME. LIMIT WATER CEMENT RATIO TO 0.45 AND USE TYPE V CEMENT WHERE SOILS <br />oc <br />ON CENTER <br />"WATER SOLUBLE SULFATE EXCEEDS 0.20 PERCENT BY WT. ADD NO WATER TO CONCRETE AT <br />O.F. <br />OUTSIDE FACE <br />SITE. IF INCREASED WORKABILITY IS REQUIRED, CONTRACTOR IS TO SUBMIT A MIX DESIGN <br />O.S. <br />OUTSIDE <br />THAT WILL ALLOW THE ADDITION OF A FIXED AMOUNT WATER REDUCING AGENT OFF A FIXED <br />O.T.O. <br />OUT TO OUT <br />AMOUNT OF SUPER -PLASTICIZER AT THE CONCRETE PLANT. DO NOT USE FLY ASH OR OTHER, <br />PL <br />PLATE <br />NON-PORTLAND CEMENT, CEMENTUOUS MATERIALS IN CONCRETE FOR THIS PROJECT. THE <br />REINF. <br />REINFORCING <br />TESTING LAB MUST APPROVE THE CONTRACTORS METHOD OF COMPLIANCE AND CERTIFY THEIR <br />REM. <br />REMAINDER <br />APPROVAL WITH EACH CONCRETE TEST CYLINDER THEY CAST. TESTING LAB TO NOTIFY THE <br />R.O. <br />ROUGH OPENING <br />ARCHITECT IMMEDIATELY BY FAX AND PHONE OF ANY NONCOMPLIANCE. <br />SECT. <br />SECTIONS <br />S(M. <br />SIMILAR <br />REINFORCING STEEL <br />S.J <br />SHRINKAGE JOINT <br />STL. <br />STEEL <br />ALL CONCRETE REINFORCING STEEL SHALL BE DEFORMED PER ASTM A615, GRADE 60 (fy=60,000 <br />SW <br />SHEARWALL <br />psi) LAP CONTINUOUS REINFORCING BARS 44 BAR DIAMETERS, V-10" MINIMUM UNLESS NOTED <br />SYMMETRICAL <br />OTHERWISE.. CORNER BARS (V-10" BEND) TO BE PROVIDED FOR ALL HORIZONTAL <br />T. <br />T. <br />TOP <br />REINFORCEMENT. DETAIL STEEL IN ACCORDANCE WITH "ACI MANUAL OF STANDARD PRACTICE <br />T . <br />TOP OF BEAM <br />OF DETAILING REINFORCED CONCRETE STRUCTURES". WELDED WIRE FABRIC (WWF) TO <br />T _F. <br />TOP OF FOOTING <br />CONFORM WITH ASTM A185. REINFORCING HOOKS TO COMPLY WITH STANDARD ACI HOOKS. <br />_ <br />TS• <br />TOP OF STEEL <br />COVER TO MAIN REINFORCEMENT TO BE: <br />TOP OF AB <br />BOTTOM OF FOOTINGS 3 INCHES <br />T <br />TOP OF WALL <br />AL <br />FORMED SURFACES WEATHER & EARTH FACE 1-1/2 INCHES <br />TYP. <br />. <br />TYPICAL AT ALL SIMILAR PLACES <br />FORMED SURFACES INTERIOR FACE 3/4 INCHES <br />U.N.O. <br />UNLESS NOTED OTHERWISE <br />V.E.F. <br />VERTICAL EACH FACE <br />SHOULD THE REINFORCING SUPPLIER AND/OR RETAILER CHOOSE TO USE SOFT METRIC, EACH <br />VERT. <br />VERTICAL <br />AND EVERY REBAR CALLOUT MUST BE INDICATED WITH BOTH SIZES WITH THE IMPERIAL SIZE <br />FIRST THUS: "4113" NO EXCEPTIONS. A CONVERSION TABLE ALONE IS UNACCEPTABLE. WE <br />V.F.F. <br />VERTICAL FAR FACE <br />VFY <br />VERIFY <br />WILL CHECK THE SHOP DRAWINGS TO THE IMPERIAL SIZES ONLY. IT WILL BE THE <br />V.N.F. <br />VERTICALEAINSIDE FACE <br />RESPONSIBILITY OF THE REINFORCING SUPPLIER AND THE GENERAL CONTRACTOR TO VERIFY <br />V.N.F. <br />N <br />VERTICAL NEAR FACT <br />THAT ALL CONVERSIONS TO METRIC SUPPLY AT LEAST THE SAME AREA OF STEEL AS THE <br />V.N.F. <br />VERTICAL OUTSIDE FACE <br />IMPERIAL. <br />W.A.B.O. <br />WASHINGTON ASSOC. OF BUILDING OFFICIALS <br />w/ <br />WITH <br />_STRUCTURAL STEEL AND MISCELLANEOUSL <br />w/o <br />WITH OUT <br />ALL WORK IN ACCORDANCE WITH "RISC SPECIFICATION FOR THE DESIGN, FABRICATION AND <br />W.H.S. <br />WELD HEAD STUD <br />ERECTION OF STRUCTURAL STEEL FOR BUILDINGS", AND THE "CODE OF STANDARD PRACTICE". <br />@ <br />AT <br />STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING STANDARDS: <br />- --- <br />WIDE FLANGE SHAPES ASTM A-992 (Fy =50,000 PSI) <br />-- <br />OTHER SHAPES AND PLATES ASTM A-36 (Fy=36,000 PSI) <br />TUBE COLUMNS ASTM A-500, GRADE B (Fy-46,000 PSI). <br />WELDHEAD STUDS ASTM A-108 (Fyp55,000 PSI) <br />20°-0" <br />ALL -THREAD ASTM F1554, GRADE 36 (Fy=36,000 PS() <br />-- --- -"--- <br />MACHINE BOLTS ASTtI A-307 <br />HIGH STRENGTH BOLTS ASTM A-325N (U.N.O.)' <br />ALL STRUCTURAL STEEL BOLTED CONNECTIONS AT MECHANICAL PLATFORMS ARE ASTM A-325 <br />� n <br />TYPE N CONNECTIONS - BEARING TYPE WITH THREADS INCLUDED IN SHEAR PLANE. <br />- - -- <br />CONNECTIONS ARE NON -SLIP CRITICAL AND BOLTS NEED TO BE TIGHTENED "SNUG -FIGHT" ONLY <br />EXCEPT AT FRAMES. PROVIDE WASHERS AT OUTER PLYS WITH SLOTTED HOLES. INSTALL A-325 <br />15'-4" <br />BOLTS IN ACCORDANCE WITH "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR <br />---- --_ `____ <br />A490 BOLTS" (11/13/85). PROVIDE MINIMUM EMBEDMENT FOR ANCHOR BOLTS AS NOTED ON <br />� s <br />DRAWINGS. ALL WELDING TO CONFORM WITH AWS D1.1 "CODE FOR WELDING IN BUILDING' <br />EXIST. 10" - <br />C.M.U. WALL <br />CONSTRUCTION". WELDS NOT SPECIFIED SHALL BE 1/4", CONTINUOUS FILLET MINIMUM. ALL <br />s < <br />WELDS BY CERTIFIED WELDERS. USE FRESH 70XX ELECTRODES FOR MANUAL SHIELDED <br />-- <br />METAL -ARC WELDING OR EQUAL ELECTRODES. WELDHEAD STUDS (WHS) ARE TO BE MACHINE <br />if - <br />- - _ <br />WELDED WITH PROPER EQUIPMENT. SEE SPECIFICATIONS FOR ITEMS TO BE GALVANIZED. <br />T � <br />CONCRETE AND MASONRY ANCHORS IqOLTS, THREADED <br />REBAR } <br />DRILLED IN EXPANSION_ ANCHORS: <br />O <br />CONCRETE HILTI KWIK BOLT TZ PER ESR-1917 <br />U_ <br />CMU HILTI KWIK BOLT 3 PER ESR-1385 <br />ADHESIVE ANCHORS: <br />1 - U) <br />It It <br />CONCRETE HILTI HIT -RE 500 V3 PER. ESR-3814 AND HILTI HIT HY 200-R PER ESR-3187 <br />U? - _ <br />CMU HILTI HIT-HY 270 PER ESR-4143 <br />,._ <br />� I T_ <br />UNREINFORCED <br />MASONRY HILTI HIT-HY 270 PER ESR-4144 <br />CAST IN PLACE ANCHORS: <br />t <br />E <br />CONCRETE EMBED PER FLANS AND SECTIONS <br />CiV1U EMBED PER PLANS AND SECTIONS <br />SCREW ANCHORS: <br />- <br />CONCRETE HILTI KWIK HUS-EZ (KH-EZ) AND HUS-EZ I (KH-EZ 1) PER ESR-3027 <br />cfs <br />CMU HILTI KWIK HUS-EZ <br />PER ESR-3056 <br />(KH-EZ) <br />-- -- -- - - <br />ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF <br />=— <br />INSTALLATION PER ACI 318 - 14 SECTION 17.1.2 INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR <br />-'' <br />7 <br />UPWARDLY INCLINED TO SUPPORT SUSTAINED TENSION LOADS SHALL BE PERFORMED BY CERTIFIED <br />c as <br />PERSONNEL IN CONFORMANCE TO ACI 318 - 14 SECTION 17.8.2.2. <br />2" 1 "-1 U, <br />sI1Qti�Y <br />4-11 0'- -- ---- ---i -- - <br />SECTION <br />5'-0" PER ARCH, FIELD VEY. <br />i <br />(N) 6" MECHANICAL SLAB PER PLAN z1 <br />(E) DOCK SLAB <br />4 <br />a 4 a . <br />CD FOLLOW INSTALLATION PROCEDURES OF ESR REPO RE 500 V3 PER ESR-3814RT AND MANUFACTURER'S STRONGBACK ELEVATION <br />4 18"oc EPDXY wl <br />HILTI 20OR EMBED 4" w/ <br />SPCL. INSP. TYP. <br />SECTION <br />L6x4x3/8 (L.L.V <br />EXTEND L <br />1" PAST H.S.S. <br />COPE HORN. L <br />AS REQUIRED <br />PER ELEV. <br />R.O. PER ELEV <br />DETAIL 3a <br />_ 3 <br />PER PLAN <br />NEW MECHANICAL HOUSE <br />BY OTHERS. ATTACHMENT <br />TO CONC. BY OTHERS. —� <br />6" CONC. SLAB <br />REINF. PER PLAN -- <br />2- #4 r@18"oc <br />0 ° <br />o� <br />a 0-o o. <br />O OQopp op <br />° <br />_ E <br />. C)R <br />O <br />4 ROWS #4 18"oc <br />EPDXY ,,v/ HILTI 20OR <br />EMBED 4" w/ SPCL INSP., TYP. <br />1/2"x4"xV-0" PLATE <br />2- 5/8" O ANCHORS <br />(EMBED 5 518" MIN. <br />SEE "NOTE" BELOW <br />ELEV. 1/S1.2, TYP. <br />LO <br />INSTRUCTIONS. PROVIDE SPECIAL INSPECTION AS NOTED AND/OR REQUIRED BY ESR REPORT. <br />SUBSTITUTIONS ARE NOT ALLOWED UNLESS WRITTEN APPROVAL BY ENW IS RECEIVED. SUBSTITUTIONS <br />1/4" = 1'-0" <br />V) <br />MUST BE SUBMITTED TO ENW FOR REVIEW PRIOR TO CONSTRUCTION. PROVIDE STAINLESS STEEL OR <br />NOTES: <br />GALVANIZED ANCHORS FOR EXTERIOR APPLICATIONS AS REQUIRED. ANCHORS RATED FOR DRY <br />1 } <br />CONCRETE ANCHORS: USE 5/8"0 ALL THREAD ROD vv/ HILTI HIT-HY 200-R ADHESIVE IN CONCRETE, <br />' <br />INTERIOR CONDITIONS MAY NOT BE USED FOR EXTERIOR APPLICATIONS PER ESR REPORT. <br />INSPECT PER I.C.C. ESR-3187, <br />2.) <br />MASONRY ANCHORS: USE 5/8"0 ALL THREAD ROD w/ HIT-HY 270 ADHESIVE IN MASONRY, INSPECT PER <br />SPECIAL INSPECTIONS <br />I.C.C.. ESR-4143. SOLID GROUT ALL CELLS THAT ARE TO RECEIVE ANCHORS PRIOR TO INSTALLATION <br />INSPECTIONS ARE TO BE PER THE CODE INDICATED ABOVE AND ARE TO BE BY AN INDEPENDENT <br />OF ANCHORS. GROUT TO BE F'c = 2,000 PSI MIN. <br />TESTING LAB APPROVED PRIOR TO STARTING CONSTRUCTION BY THE BUILDING DEPT. AND THE <br />3.) <br />CO NOT SUBSTITUTE OTHER ADHESIVES FOR THE HILTI HIT-HY 270 AND THE HILTI HIT-HY 200-R <br />r' <br />w <br />ARCHITECT. INSPECT ALL SHOP WELDING UNLESS THE SHOP IS CERTIFIED BY THE LOCAL <br />WITHOUT PRIOR WRITTEN AUTHORIZATION FROM E.N.W. <br />BUILDING DEPARTMENT. <br />4.) <br />DO NOT OVER CUT OPENINGS AT CORNERS, TYPICAL, <br />FOUNDATION: SOILS ENGINEER TO INSPECT FOOTING EXCAVATIONS AND PROVIDE <br />5.) <br />CONTRACTOR TO VERIFY THAT NO VERTICAL WALL JOINTS OCCUR WITHIN THE NEW OPENING AND <br />0 <br />COMPACTION TESTS AS NOTED ABOVE. <br />STRONGBACK SPACE. <br />o" <br />CONCRETE: TAKE CONCRETE CYLINDERS AS REQUIRED, VERIFY SLUMP AND <br />STRENGTH. SPECIAL INSPECTION IS REQUIRED DURING THE TAKING OF TEST <br />CU <br />SPECIMENS AND PLACING OF ALL REINFORCED CONCRETE <br />NEW BLAB EXIST. SLAB <br />REINFORCING: VERIFY ALL REINFORCING IS PLACED IN ACCORDANCE WITH THESE <br />DRAWINGS. CHECK FOR REQUIRED COVER, SIZE, SPACING, LAP AND GRADE. <br />SPECIAL INSPECTION 1S REQUIRED DURING THE PLACING OF REINFORCING LIGHTLY GREASE DOWEL <br />STEEL. THIS SIDE PRIOR TO <br />CONS. EXPANSION POUR & AFTER EPDXY <br />0 & MASONRY ANCHORS <br />& DRILLED -IN DOWELS: COPY OF ICC REPORT FOE ANCHORS OR ADHESIVE SYSTEM USED TO EXIST. SLAB� I <br />MUST BE AVAILABLE AT JOB SITE. VERIFY ANCHORS OR ADHESIVE <br />SYSTEM INSTALLATION IN ACCORDANCE WITH REPORT. NEW 6" CONCRETE <br />> STEEL: IN ACCORDANCE WITH TABLE 1704.3 OF IBC AND REFERENCED STANDARDS. SLAB ON GRADE w/ 1 <br />CONTINUOUS INSPECTION: #4 '18"oc EACH <br />� SLIP -CRITICAL (SC) HIGH STRENGTH BOLTED CONNECTIONS. WAY CENTERLINE <br />V) <br />0 COMPLETE AND PARTIAL PENETRATION GROOVE WELDS. NON-DESTRUCTIVE <br />0 TESTING PS REQUIRED FOR ALL COMPLETE PENETRATION WELDS - SHOP AND VFY, <br />FIELD. -- -- - - — - -- <br />TO MATCH EXIST. <br />MULTIPASS FILLET VVE( DS. - - <br />n SINGLE -PASS FILLET WELDS GREATER THAN 5/16-INCH. 4 _- <br />WELDING OF REINFORCING IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, ' p. <br />n BOUNDARY ELEMENTS OF SPECIAL REINFORCED CONCRETE SHEAR WALLS°q0 OC,o0 pro a° <br />.00 AND SHEAR REINFORCEMENT. Q ° n o <br />e poo O o n _1c c> o <br />E PERIODIC INSPECTION: COMPACTED I I —I i i—i i i a l l - i I <br />E VERIFY HIGH -STRENGTH BOLT IDENTIFICATION MARKINGS CONFORM TO SUBG DE BY =1 I I `)1 �— I 1—I M-1 I I— <br />OTHERS I! I —I I[=1 I I I I I E I 1=1 11 <br />SPECIFIED ASTM STANDARDS, REVIEW OF MANUFACTURER'S CERTIFICATE OF <br />COMPLIANCE. <br />r6 INSTALLATION OF BEARING -TYPE BOLTED CONNECTIONS, <br />0 SINGLE -PASS FILLET WELDS 5/16-INCH OR LESS. <br />_ FLOOR AND ROOF DECK WELDS. <br />COLD -FORMED STEEL FRAME WELDING, <br />M . WELDING OF STAIRS AND RAILINGS. <br />WELDING OF STUDS. <br />4i1 VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN ASTMSECTION <br />i WELDING OF REINFORCING STEEL OTHER THAN THAT REQUIRING CONTINUOUS (4 a ------ <br />-- > <br />18"0 x " SMOOTH ROUND <br />DOWELS @ 18"° oc. EPDXY TO <br />EXIST. SLAB w/ HILTI HIT-HY <br />200-R ADHESIVE, EMBED 4 1/" <br />w/ SPECIAL INSPECTION, ORIENT <br />PERPENDICULAR TO EXIST. <br />SLAB SAW CUT EDGE AND <br />LEVEL w/ HORIZONTAL PLANE <br />1 /2"xH. S <br />w/ 2- 5/8 <br />DETAIL 3c <br />3/4" = 1'-0" <br />/// (N) CONC. RAMP w/ <br />4 @ 18"oc EACH WAY <br />SEE SECTION 4 FOR <br />SLAB REPAIR DETAIL <br />3/4" 1,-0„ <br />EXIST. <br />MASOI <br />WALL. <br />PER E <br />(E) 6" CONC. SLAB <br />(E) 10" CMU MALL <br />SUB -GRADE <br />BY OTHERS <br />8" C.I.P. w/ #4 <br />12"oc HORN., TYP. <br />EXIST. CURB <br />TO REMOVE. <br />#4 12"00 <br />EPDXY & EMBED <br />4" TYP. <br />(E) FOOTING <br />1/2"0 ANCHORS <br />24"oc SEE <br />MOTES BELOW <br />3/S1 A TYP. <br />ANGLE PER <br />DETAIL 3a <br />EXIST. WALL TO <br />BE REMOVED <br />I ONLY AFTER, <br />LINTEL ANGLE <br />IS IN PLACE <br />DETAIL 3d <br />MAXIMUM SPACING & USE P.N.A. PD3 BASKET ASSEMBLY OR <br />LOCATION PER FDN. FLAN <br />,APPROVED EQUAL, W1DOV'VELS @ 24°'oc. <br />V4 x 1/8" SOFT -CUT JOINT — SPACING MAY BE INCREASED TO 26°" IF <br />SUPPORTING DATA CAN PROVE THAT A <br />REINF. WHERE SUPPORTING <br />SPACING CAN BE USED WITH <br />APPLICABLE PER PLAN COTCO FORKLIFTS. BASKET SHOULD BE <br />SLAB PER PLAN —� MANUFACTURED TO HOLD PLATES AT 1/4" <br />OF SLAB CTR. <br />°4 4 <br />a, 4 <br />° -. I <br />HOLD 7" co ( 2o <br />q 0 <br />4� a 0Soo CLR. MAX. 0c°,oCIO E— <br />®I NOTE: <br />III —I (I —I I f= 1,) SEE ARCH. DTLS, FOR SPECIAL JOINT FINISH, <br />2.) SOIL SUBGRADE PER SOILS REPORT. <br />3,) USE OF OTHER JOINT SYSTEMS NOT ALLOWED. <br />5 � <br />s <br />OINT m (S.J. <br />3/4" <br />1F_011 <br />1 1,2" 1"-1" 1 1/2" <br />TYP. E.W. P. E.W TYP. E.W. <br />9 <br />CQ <br />1/2" BRG. PLATE <br />w/ 4- 3/4"0 HEADED 1 COLUMN PER PLAN <br />BOLTS OR ALL -THREAD <br />(EMBED 4" MIN.) j <br />I I SLAB PER PLAN <br />1 <br />4' <br />� <br />.Q <br />a <br />4 <br />4' <br />SECTION <br />MAXIMUM SPACING & <br />LOCATION PER FDN. PLAN -r <br />REINF. WHERE <br />APPLICABLE PER PLAN <br />SLAB PER PLAN <br />3/4ot = 11_01i <br />— P.N.A. DIAMOND DOWEL OR APPROVED <br />EQUAL, @ 24"oc MAX. LOCATE ± 1/8" OF <br />MID. POINT OF SLAB. MOVE REBAR IF <br />NEEDED. HOLM 12" FROM <br />PERPENDICULAR JOINTS <br />a <br />a <br />*0 <br />yma� <br />� e <br />4. <br />JOINT (C.J. <br />3/4" 1'-0" <br />PARTIAL FOUNDATION PLAN v <br />NOTES. 1/4" -- 1 -01t <br />1.) ALL ITEMS ARE EXISTING (E) UNLESS NOTED AS NEW (N). <br />2.) FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO CONSTRUCTION. NOTIFY ENW <br />IF EXISTING DIMENSIONS AND EXISTING CONDITIONS ARE NOT AS SHOWN ON PLANS AND SECTIONS. <br />3.) VERIFY ALL DIMENSIONS w/ ARCH. <br />4.) { ) INDICATES TOP OF FOOTING RELATIVE TO FINISH FLOOR. <br />5.) VERIFY SLAB JOINT LOCATIONS WITH ARCH. <br />{ <br />d <br />JOB NO: <br />95052031 <br />ENGINEER: <br />R. ZHU <br />DRAVVNI: <br />P. PATEL <br />DATE: <br />12-12-2018 <br />SHEET NO: <br />INSPECTION. <br />STEEL- .iOINTS AND CONNECTIONS FOR COMPLIANCE WITH PLANS <br />314" = 1'-0" <br />dIN <br />5j <br />:ads '-:.- <br />�s a <br />