<br />PENETRATIONREMOVE EXISTING KITCHEN HOOD INCLUDING
<br />ANSUL SYSTEM, GREASE DUCT, AND EXHAUST FAN
<br />ON ROOF, CAP AND SEAL ROOF
<br />U2 REMOVE EXHAUST FAN ON ROOF AND ALL
<br />ASSOCIATED DUCTWORK. CAP WEATHER TIGHT.
<br />AND SEAL WEATHER TIGHT,
<br />REMODEL PLAN MOTES
<br />ANSUL SYSTEM CONTROL AUTOMAN WITH AGENT TANK ENCLOSED. MOUNT
<br />CONTROL BOX TIGHT TO FINISHED CEILING. SEE 2/M103.
<br />0 MANUAL PULL STATION FOR ANSUL SYSTEM, MOUNT AT 48" AFF.
<br />GREASE DUCTWORK SERVING TYPE 1 HOOD SHALL BE CAPTIVE AIRE DOUBLE
<br />WALL, INSULATED GREASE DUCT MODEL DW-3R OR APPROVED EQUIVALENT.
<br />0 8x8 EXHAUST DUCT UP TO EF-3 ON ROOF. SEE 4/M102.
<br />ENERGY MANAGEMENT SYSTEM CONTROL CABINET. SEE 3/M103
<br />ENERGY MANAGEMENT SYSTEM USER INTERFACE. MOUNT AT 48" AFF, SEE
<br />2/M 102.
<br />0 ADJUST SUPPLY DIFFUSER AIR PATTERN TO DISCHARGE AWAY FROM HOOD.
<br />08 NEW MAKE UP AIR UNIT ON ROOF, LOCATE UNIT SO AIR INTAKE WILL BE MINIMUM
<br />10' AWAY FROM ANY BUILDING EXHAUST OR PLUMBING VENTS.
<br />EXTEND 28" SUPPLY DUCT FROM MAU-1 OUTLET A MINIMUM OF 7 FEET
<br />VERTICALLY ICALLY PRIOR TO 3 90' ELBOW PER MANUFACTURER'S INSTRUCTIONS.
<br />10 DUCT MOUNTED SUPPLY GRILLE USED TO PROVIDE ADDITIONAL MAKEUP /
<br />VENTILATION AIR INTO BUILDING.
<br />EXHAUST FAN SCHEDULE (FURNISHED BY OWNER/ CONTRACTOR INSTALLED)
<br />GRILLES, REGISTERS, AND DIFFUSESCHEDULE
<br />PLAN MFGR MODEL SERVICE TYPE DRIVE CFM RPM E.S.P. dip WEIGHT
<br />POWER (V/Ph)
<br />ACCESSORIES
<br />PLAN
<br />MFGR MODEL
<br />FACE SIZE ] NECK SIZE
<br />MAX CFM &P�
<br />NC MATERIAL
<br />FINISH FRAME REMARKS
<br />CODE
<br />(L BS)
<br />CODE
<br />_ CENTRIFUGAL
<br />S-1
<br />TUTTLE AND BAILEY SOD
<br />21x21 16x16
<br />855 0.08
<br />26 STEEL
<br />WHITE SURFACE
<br />EF-1 CAPTIVE AIRE CASRE18DD ROTISSERIE DIRECT 3290 1475 1.64 3.0
<br />296
<br />20813
<br />1,2,3,4,E
<br />UPBLAST
<br />S-2
<br />TUTTLE AND BAILEY SDT54
<br />21x14 1 8x 12
<br />860 0.02
<br />10 STEEL
<br />WHITE SURFACE 1
<br />EF-2 CAPTIVE AIRE CASRE18DD ROTISSERIE. CENTRIFUGAL DIRECT 3290 1475 1.64 3.0
<br />296
<br />208 / 3
<br />1,2,3,4,E
<br />UPBLAST
<br />ROTISSERIE
<br />E-1
<br />TUTTLE AND BAILEY CRE500
<br />10x10 Sx8
<br />125 0.08
<br />26 STEEL
<br />WHITE SURFACE
<br />EF-3 CAPTIVE AIRE DRIOHFA DOWNBLAST DIRECT 125 800 0.125 0.16E
<br />60
<br />115 / 1
<br />1,i,6,7
<br />PREP
<br />NOTES:
<br />ACCESSORIES:
<br />1 - PROVIDE WITH DAMPER EXTRACTOR.
<br />1 - DISCONNECT SWITCH.
<br />-
<br />2 - GREASE TRAP WITH DRAIN CONNECTION.
<br />3 - RAIN CAP ASSEMBLY WITH HARDWARE. AND GASKET.
<br />4 - 24" NON -VENTED ROOF CURB WITHOUT WOOD NAILER BY FAN MANUFACTURER.
<br />5 - 20" NON -VENTED ROOF CURB WITH WOOD NAILER BY FAN MANUFACTURER.
<br />6- OWNER PROVIDED EQUIPMENT. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION, START UP, AND WARRANTY.
<br />7 - CONTROLLED BY '12 HOUR TIMER SWITCH PROVIDED BY E.C.
<br />KITCHEN HOOD SCHEDULE(FURNISHED OWNER / CONTRACTOR INSTALLED)
<br />CUTLET S.P..
<br />T1iJ4 a
<br />PLAN CODE MFGR MODEL TYPE MATERIAL LENGTH WIDTH HEIGHT CFM OUTLET SIZE
<br />MAX
<br />HEHEIGHT�v10UNT (G
<br />ACCESSORIES
<br />KH-1 CAPTIVEAIRE 7830 1 430 STAINLESS 13'-2" U-6" 2'-6" 3290 18"0
<br />1.13"
<br />92
<br />1,2,3,4,5,6,7,8
<br />ND-2 STEEL
<br />KH-2 CAPTIVEAIRE 7830 1 430 STAINLESS 1T-2" U-6" 2-6" 3290 18°0
<br />1.13"
<br />92
<br />1,2,3,4,5,6,7,8
<br />ND-2 STEEL
<br />ACCESSORIES.
<br />1 - STAINLESS STEEL BAFFLE GREASE FILTERS.
<br />2 - U.L. LISTED WITHOUT FIRE DAMPER.
<br />3 - INCANDESCENT LIGHT FIXTURES (50) FOOT CANDLES WITH Obi/OFF SWITCH MOUNTED ON HOOD.
<br />4 - COMPLETE WET CHEMICAL FIRE SUPPRESSION SYSTEM WITH REMOTE MOUNTED UTILITY CABINET.
<br />5 - 3" INTEGRAL AIR SPACE ON BACK OF HOOD.
<br />6 - STAINLESS STEEL SIDE -SPLASH PANEL, 72" HIGH.
<br />7 - 3" STAINLESS STEEL END STANDOFF.
<br />8 - EMS CONTROL CABINET WITH VFD'S AND TEMPERATURE INTERLOCK.
<br />NOTE:
<br />KITCHEN HOODS, EXHAUST FANS, AND FIRE SUPPRESSION INFORMATION PROVIDED BY CAPTIVEAIRE. SEE SHEETS M102, M103, M104.
<br />MAKE-UP AIR UNIT SCHEDULE
<br />FAN OUTSIDE AIR HEATING COIL
<br />COOLING COIL
<br />FAN
<br />PLAN MFGR MODEL
<br />CODE
<br />ESP (IN MIN MAX GAS PRSS.
<br />INPUT
<br />OUTPUT
<br />EAT/LAT ENTERING ERING
<br />LEAVING
<br />LEAVING
<br />SENSIBLE
<br />LATENT
<br />TOTAL POWER
<br />SERVES
<br />CFM
<br />WG) (CFM) (CFM) (IN WC)
<br />BTUH
<br />BTUH
<br />ff) DB ff) ff)
<br />LWB
<br />DB (°F)
<br />WB ff)
<br />CAPACITY (MBH)
<br />CAPACITY
<br />([xABH) CAPACITY
<br />(MBH) P (V/Ph/Hz)
<br />I CAPTVE
<br />MAU-1 A3-D.500-G18-MPU 6000
<br />0,50 3500 6000 7-14
<br />477240
<br />439065
<br />10/80 95 78
<br />84.2
<br />73.0
<br />67.4
<br />52.5
<br />120 5.0 208/3160 ROTISSERIE HOOD KH-1, KH-2
<br />APT
<br />NOTES: ACCESSORIES:
<br />A - PROVIDE WITH INSULATED ROOF CURB AND MOUNTING RAIL.
<br />ADDITIONALA. PLANS ARE BASED ON EXISTING DRAWINGS AND LIMITED
<br />SITE INVESTIGATION, CONTRACTOR SHALL REVIEW
<br />EXISTING CONDITIONS AND PROVIDE ANY
<br />NOTED,INCIDENTALS REQUIRED FOR DEMOLITION AND/OR _4
<br />CONSTRUCTION, WHETHER OR NOT SPECIFICALLY
<br />PLANS.AND SHALL PERFORM ALL REMOVALS OR WORK NEEDED
<br />TO MEET NEW PROJECT SCOPE REQUIREMENTS AS PER
<br />CONSTRUCTION
<br />SHALLPIPING, CEILINGS, DUCTS, ETC. ARE TO BE REMOVED, SUCH==�..
<br />REMOVAL ALL ANCHORS, HANGERS,
<br />INSTALLATIONFRAMING, FOUNDATIONS, ETC.
<br />B. VERIFY LOCATION OF EXISTING STRUCTURAL
<br />COMPONENTS, NO CORE DRILL SHALL INTERFERE WITH
<br />THE INTEGRITY OF THE BUILDINGS STRUCTURAL
<br />C. ALL TRADES MUST COORDINATE ALL WORK BEFORE ANY
<br />1KES PLAON THIS
<br />CE. CEILING SPACE
<br />FLOOR IS l ANY WORK
<br />PROPER COORDINATION IS SUBJECT TO REMOVAL l
<br />RE -INSTALLATION AT THE INSTALLING CONTRACTOR'S
<br />D. SHALL
<br />PRIORINFORM THE ARCHITECT IMMEDIATELY
<br />COMMENCEMENT OF WORK.