Laserfiche WebLink
GENERAL NOTE SPECIAL CONDITIONS <br />REMODEL CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND SHALL PROVIDE ADEQUATE <br />SHORING AND BRACING OF ALL STRUCTURAL MEMBERS DURING CONSTRUCTION. CONTRACTOR <br />THE FOLLOWING NOTES APPLY UNLESS NOTED OTHERWISE - ASTM'S NOTED ARE TO BE LATEST SHALL NOTIFY ENGINEER OF ALL FIELD CHANGES PRIOR TO INSTALLATION. <br />EDITION. DEFERRED SUBMITTALS <br />1. DESCRIPTION THE STRUCTURAL DESIGN FOR DEFERRED SUBMITTALS BELOW SHALL FOLLOW THE DESIGN <br />Building Name & Site Location - Costco Wholesale - Everett, WA LOADS INDICATED IN THIS GENERAL NOTE. <br />2. DESIGN CODE AND STANDARDS 1. METAL INSULATED PANEL COMPRESSOR HOUSE. f <br />Applicable Code (Edition/Name) - 2015 International Building Code (IBC) 2. METAL GUARD RAIL AT CATWALK. �1 <br />Other documents referenced by these notes shall be the specific edition referenced by the <br />building code specified above, or if not specified, shall be the latest edition. ABBREVIATIONS <br />ARCM. ARCHITECT 2" <br />ESIGN LO S BAL. BALANCE <br />B. OR BOT. BOTTOM <br />a. Roof Snow Load 25 psf (snowy drift is not required). ! � BTWN. BETWEEN <br />BLDG. BUILDING <br />b. Slab Live oa 250 psf BRG. BEARING <br />c. Seismic Risk Category 11 C.I.P. CAST IN PLACE <br />S,i = 1.416, S, = 0.544, le = 1.0, Site Class "D" and C.J. CONSTRUCTION JOINT 0,_01, <br />SQs = 0.944, SD, = 0.544. CL CENTERLINE -- -- -- -- -- <br />Seismic Design Category = "D" CLR. CLEAR <br />d. Wind Load Risk Category 11 CMU CONCRETE MASONRY UNIT <br />Basic wind speed (3 sec. gust) VULT= 110 mph, VASD= 85 mph COL. COLUMN <br />Exposure B CONC. CONCRETE <br />Kzt=1.0 C.S.J. CLOSURE STRIP JOINT <br />IBC Load Cases per sec. 1605.2.1 or 1605.3.1 only K, = 0.85 EA. EACH 2- #4 CONT. -- <br />Importance factor 1.0. E.E. EACH END <br />e. Load Combinations All Code required load combinations are to be used in the building design. E.F. EACH FACE <br />E.J. EXPANSION JOINT 18"oc <br />STANDARDSOSHA EL. OR ELEV. ELEVATION \\\\ <br />THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PROVISIONS OF THE CURRENT E.N.W. OR ENW ENGINEERS NORTHWEST 2'-6" <br />OSHA STANDARDS. THE GENERAL CONTRACTOR SHALL REVIEW THESE STRUCTURAL EQ. EQUAL -- -- - -- <br />DRAWINGS FOR ANY NONCOMPLIANCE WITH OSHA STANDARDS, TAKING INTO ACCOUNT THE E.S. EACH SIDE <br />GENERAL CONTRACTOR'S MEANS AND METHODS. THE GENERAL CONTRACTOR SHALL INFORM E.W. EACH WAY - - <br />ENW OF ANY NONCOMPLIANCE SO THE DRAWINGS MAY BE MODIFIED FOR COMPLIANCE PRIOR F.O.C. FACE OF CONCRETE 4- #4 TOP 4 <br />TO CONSTRUCTION. THE GENERAL CONTRACTOR IS TOTALLY RESPONSIBLE FOR MEANS AND F.O.S. FACE OF STUD BOTT. ���111111 d _a a <br />6 r. d 9 <br />d <br />METHODS AS WELL AS JOBSITE SAFETY ON THIS PROJECT. F.O.W. FACE OF WALL VARIES _ _ <br />FTG. FOOTING <br />CONCRETEGA. GAGE <br />--- ---- ---- � <br />F'c=4000 PSI. 23 DAYS 5-1/2 SACKS MINIMUM CEMENT PER CUBIC YARD FOR ALL CONCRETE GALV. HOT DIP GALVANIZED <br />SLABS. G..B. GYPSUM WALL BOARD .. <br />F'c=3000 PSI. 28 DAYS 5-1/2 SACKS MINIMUM CEMENT PER CUBIC YARD FOR ALL OTHER. H. Off: HORIZ. HORIZONTAL y ' r2-1 <br />USE TYPE 1/11 CEMENT. FOR SPECIAL CONDITIONS ANOTHER TYRE CEMENT MAY BE REQUIRED. I.B.C. INTERNATIONAL BUILDING CODE (E) 6" CONC. SLAB <br />SUBMIT FOR APPROVAL. ULTIMATE STRENGTH DESIGN METHOD USED. MIXING AND PLACING OF I.C.C. INTERNATIONAL CODE COUNCIL ON GRADE <br />ALL CONCRETE AND SELECTION OF MATERIALS SHALL BE IN ACCORDANCE WITH THE ACI CODE LF INSIDE FACE <br />318, PROPORTIONING OF AGGREGATE TO CEMENT SHALL BE SUCH AS TO PRODUCE A DENSE INC. INCLUDING <br />WORKABLE MIX WITH 4" MAXIMUM SLUMP (UNLESS SUPERPLASTICIZERS ARE USED) WHICH CAN K KIP (1000 POUNDS) <br />BE PLACED WITHOUT SEGREGATION OR EXCESS FREE SURFACE WATER. FOR ADMIXTURES, L.W. LONG WAY SECT101 <br />SEE SPECIFICATIONS. MAXIMUM WATER/CEMENT RATIO - 0.49. 3/4" CHAMFER. ALL EXPOSED M.B.S. METAL BLDG SUPPLIER <br />EDGES, UNLESS INDICATED OTHERWISE ON ARCHITECTURAL DRAWINGS. WATER CURING SHALL N.F. NEAR FACE <br />BE USED. AIR ENTRAIN ALL HORIZONTAL CONCRETE EXPOSED TO WEATHER WITH 3% TO 6% AIR N.T.S. NOT TO SCALE <br />BY VOLUME. LIMIT WATER CEMENT RATIO TO 0.45 AND USE TYPE V CEMENT WHERE SOILS oc ON CENTER <br />"WATER SOLUBLE SULFATE EXCEEDS 0 20 PERCENT BY WT ADD NO WATER TO CONCRETE AT O.F. OUTSIDE FACE <br />I[m <br />NEW MECHANICAL HOUSE <br />BY OTHERS. ATTACHMENT <br />TO CONC. BY OTHERS. -` <br />6" CONC. SLAB <br />REINF. PER PLAN <br />2- 4 mi 18"oc <br />o r�� Q o <br />0® <br />® � 0 0n <br />0 O0a,:, o0 <br />4 ROWS #4 18"oc <br />EPDXY w/ HILTI 20OR <br />EMBED 4" w/ SPCL INSP., TYP. <br />SITE. IF INCREASED WORKABILITY IS REQUIRED, CONTRACTOR IS TO SUBMIT A MIX DESIGO <br />N <br />THAT WILL ALLOW THE ADDITION OF A FIXED AMOUNT WATER REDUCING AGENT OR A FIXED <br />.5. <br />O.T.O. <br />OUTSIDE <br />OUT TO OUT <br />2'-0" CONTACTED <br />AREA VFY. <br />5°-0" PER ARCH, FIELD VFY. <br />In <br />AMOUNT OF SUPER -PLASTICIZER AT THE CONCRETE PLANT. DO NOT USE FLY ASH OR OTHER, <br />PL <br />PLATE <br />NON-PORTLAND CEMENT, CEMENTUOUS MATERIALS IN CONCRETE FOR THIS PROJECT. THE <br />REINF. <br />REINFORCING <br />TESTING LAB MUST APPROVE THE CONTRACTORS METHOD OF COMPLIANCE AND CERTIFY THEIR <br />REM. <br />REMAINDER <br />(N) 6" MECHANICAL SLAB PER PLAN <br />1 <br />APPROVAL WITH EACH CONCRETE TEST CYLINDER THEY CAST. TESTING LAB TO NOTIFY THE <br />R.O. <br />ROUGH OPENING <br />N <br />ARCHITECT IMMEDIATELY BY FAX AND PHONE OF ANY NONCOMPLIANCE.. <br />SECT. <br />SECTIONS <br />(E) DOCK SLAB <br />SIM. <br />SIMILAR <br />C14 <br />REINFORCING L <br />S.J <br />SHRINKAGE JOINT <br />- 44 <br />STL. <br />STEEL <br />4 <br />v <br />d <br />ALL CONCRETE REINFORCING STEEL SHALL BE DEFORMED PER ASTM A615, GRADE 60 (fy=60,000 <br />SW <br />SHEARWALL <br />� ® <br />4 <br />psi) LAP CONTINUOUS REINFORCING BARS 44 BAR DIAMETERS, V-10" MINIMUM UNLESS NOTED <br />SYMM. <br />, <br />SYMMETRICAL- <br />OTHERWISE. CORNER BARS V-10" BEND TO BE PROVIDED FOR ALL HORIZONTAL <br />T. <br />e4,r <br />TOP <br />REINFORCEMENT. DETAIL STEEL IN ACCORDANCE WITH ACI MANUAL OF STANDARD PRACTICE <br />T_B. <br />TOP OF BEAM <br />OF DETAILING REINFORCED CONCRETE STRUCTURES". WELDED WIRE FABRIC (WWI TO <br />T..F. <br />TOP OF FOOTING <br />CONFORM WITH ASTM A185. REINFORCING HOOKS TO COMPLY WITH STANDARD ACI HOOKS. <br />T..S. <br />TOP OF STEEL <br />j <br />#4 I 13"oc EPDXY w/ <br />COVER TO MAIN REINFORCEMENT TO BE: <br />TOP OF SLAB <br />HILTI 20OR EMBED 4" wl <br />BOTTOM OF FOOTINGS 3 INCHES <br />T..W. <br />TOP OF WALL <br />SPCL. INSP. TYP. <br />FORMED SURFACES WEATHER & EARTH FACE 1-1/2 INCHES <br />TYP. <br />TYPICAL AT ALL SIMILAR PLACES <br />FORMED SURFACES INTERIOR FACE 3/4 INCHES <br />U.N.O. <br />UNLESS NOTED OTHERWISE <br />V.E.F. <br />VERTICAL EACH FACE <br />SEC `10N <br />SHOULD THE REINFORCING SUPPLIER AND/OR DETAILER CHOOSE TO USE SOFT METRIC, EACH <br />weERT <br />VERTICAL <br />1/2" ISOLATION JOINT <br />3/4" <br />4'-0" PER ARCH, FIELD VFY. <br />SAW CUT FULL DEPTH <br />DOCK SLA <br />=--/(N) CONC. RAMP w/ <br />-#4 18"oc EACH WAY <br />Q. d d <br />® - .4 d <br />v d ,. <br />- SEE SECTION 4 FOR <br />SLAB REPAIR DETAIL <br />AND EVERY REBAR CALLOUT MUST BE INDICATED WITH BOTH SIZES WITH THE IMPERIAL SIZE V.F.F. VERTICAL FAR FACE <br />FIRST THUS: "#4/#13" NO EXCEPTIONS. A CONVERSION TABLE ALONE IS UNACCEPTABLE. WE VFY VERIFY <br />WILL CHECK THE SHOP DRAWINGS TO THE IMPERIAL SIZES ONLY. IT WILL BE THE V.I.F. VERTICAL INSIDE FACE <br />RESPONSIBILITY OF THE REINFORCING SUPPLIER AND THE GENERAL CONTRACTOR TO VERIFY V.N.F. VERTICAL NEAR FACE <br />THAT ALL CONVERSIONS TO METRIC SUPPLY AT LEAST THE SAME AREA OF STEEL AS THE V.N.F. VERTICAL OUTSIDE FACE <br />IMPERIAL. W.A.B.O. WASHINGTON ASSOC. OF BUILDING OFFICIALS <br />STRUCTURAL L MISCELLANEOUS L w/ WITH <br />w/o WITH OUT <br />ALL WORK IN ACCORDANCE WITH "AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND W.H.S. WELD HEAD STUD <br />ERECTION OF STRUCTURAL STEEL FOR BUILDINGS", AND THE "CODE OF STANDARD PRACTICE". @AT <br />STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING STANDARDS: <br />WIDE FLANGE SHAPES ASTM A-992 (Fy=50,000 PSI) I <br />OTHER SHAPES AND PLATES ASTM A-36 (Fy=36,000 PSI} I _ (N) 4'-0" EXTEND Lt .L.V <br />TUBE COLUMNS ASTM A-500, GRACE B (Fy=46,000 PSI) <br />WELDHEAD STUDS ASTM A-108 (Fy=55,000 PSI) 20'a0°' I ; OPENING 1'° PAST H.S.S. <br />ALL -THREAD ASTM F1554, GRADE 36 (Fy=36,000 PSI) -- -- - - -- - - - _ I COPE HORIZ. I. <br />MACHINE BOLTS ASTM A-307 _ _ 3a AS REQUIRED <br />NIGH STRENGTH BOLTS ASTM A-325N (U.N.O.) <br />o <br />ALL STRUCTURAL STEEL BOLTED CONNECTIONS AT MECHANICAL PLATFORMS ARE ASTM A-325 <br />TYPE N CONNECTIONS - BEARING TYPE WITH THREADS INCLUDED IN SHEAR PLANE. - - s 3d - PER ELEV. <br />CONNECTIONS ARE NON -SLIP CRITICAL AND BOLTS NEED TO BE TIGHTENED "SNUG TIGHT" ONLY <br />EXCEPT AT FRAMES. PROVIDE WASHERS AT OUTER PLYS WITH SLOTTED HOLES. INSTALL A-325 154" <br />BOLTS IN ACCORDANCE WITH "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR --- -- -- `, ` <br />A490 BOLTS" (11/13/85). PROVIDE MINIMUM EMBEDMENT FOR ANCHOR BOLTS AS NOTED ON <br />DRAWINGS. ALL WELDING TO CONFORM WITH AWS D1.1 "CODE FOR WELDING IN BUILDING ;, EXIST. 10" f- <br />C.M.U. WALL �v � I <br />CONSTRUCTION". WELDS NOT SPECIFIED SHALL BE 1/4", CONTINUOUS FILLET MINIMUM. ALL � � z <br />WELDS BY CERTIFIED WELDERS. USE FRESH 70XX ELECTRODES FOR MANUAL SHIELDED I <br />) a. 0- R.O. PER ELEV <br />METAL -ARC WELDING OR EQUAL ELECTRODES. WELDHEAD STUDS (WHS) ARE TO BE MACHINE I I <br />WELDED WITH PROPER EQUIPMENT. SEE SPECIFICATIONS FOR ITEMS TO BE GALVANIZED. <br />3b DETAIL 3a <br />CONCRETE AND MASONRY ANCHORS THREADED RODS AND <br />RE AR OWELPI- - - - w LL TYP. 1 /2"x4"xV-0" PLATE <br />I 0 I 2- 5/8" 0 ANCHORS <br />DRILLED IN EXPANSION ANCHORS: _ - O 0t <br />CONCRETE HILTI KWK BOLT TZ PER ESR-1917 {EMBED 5 5/8" MIN.' <br />CMU HILT] KWIK BOLT 3 PER ESR-1385 b - ' : a) ) ; SEE "NOTE" BELOV <br />0o ADHESIVE ANCHORS: I �._- m €�7 U3 I ELEV. 1/S1.2, TYP. <br />CONCRETE HILTI HIT -RE 500 V3 PER ESR-3814 AND HILTI HIT-HY 200-R PER ESR-3187 <br />can CMU HILTI HIT-HY 270 PER ESR-4143 i, <br />� UNREINFORCEDIU <br />I - <br />MASONRY HILTI HIT-HY 270 PER ESR-4144CL <br />t <br />CAST IN PLACE ANCHORS: <br />CONCRETE EMBED PER PLANS AND SECTIONS04 <br />- <br />CMU EMBED PER PLANS AND SECTIONS a 3c <br />SCREW ANCHORS: TYP. R.O. PER ELEV. 3/S1.1 7" MIN. <br />CONCRETE HILTI KWIK HUS-EZ (KH-EZ) AND HUS-EZ I (KH-EZ 1) PER ESR-3027 c0 <br />CMU HILTI KWIK HUS-E <br />(KH-EZ) PER ESR-3056 0 0 + IL 3b <br />-- -- -- r #DE <br />ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF <br />INSTALLATION PER ACI 318 - 14 SECTION 17.1.2 INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR <br />UPWARDLY INCLINED TO SUPPORT SUSTAINED TENSION LOADS SHALL BE PERFORMED BY CERTIFIED <br />C) PERSONNEL IN CONFORMANCE TO ACI 318 -14 SECTION 17.8.2.2. <br />� <br />' <br />FOLLOW INSTALLATION PROCEDURES OF ESR REPO RE 500 V3 PER ESR-3814RT AND MANUFACTURER'S S'l-RONGBACK ELEVATION <br />�� <br />INSTRUCTIONS. PROVIDE SPECIAL INSPECTION AS NOTED AND/OR REQUIRED BY ESR REPORT. _ I Ilf <br />SUBSTITUTIONS ARE. NOT ALLOWED UNLESS WRITTEN APPROVAL BY ENW IS RECEIVED. SUBSTITUTIONS 1/4" 1`-0" 1 1/2"MUST BE SUBMITTED TO ENW FOR REVIEW PRIOR TO CONSTRUCTION. PROVIDE STAINLESS STEEL OR NOS. 3/16 I j <br />GALVANIZED ANCHORS FOR EXTERIOR APPLICATIONS AS REQUIRED. ANCHORS RATED FOR DRY 1.) CONCRETE ANCHORS: USE 5/8" 0 ALL THREAD ROD w/ HILTI HIT-HY 200-R ADHESIVE IN CONCRETE, <br />INTERIOR CONDITIONS MAY NOT BE USED FOR EXTERIOR APPLICATIONS PER ESR REPORT. INSPECT PER I.C.C. ESR-3187. <br />2.) <br />I.C.C. ESR 4143. SOLID GROUT ALLASONRY ANCHORS: USE 5/8"0 �CELLS�AD OD w/ HIT-HY 270 ADHESIVE IMASONRY, INSPECT R <br />THAT TO RECEIVE ANCHORS INSTALLATION i <br />SPECIAL II I` <br />� INSPECTIONS ARE TO BE PER THE CODE INDICATED ABOVE AND ARE TO BE BY AN INDEPENDENT <br />OF ANCHORS. GROUT TO BE Fie = 2,000 PSI MIN. <br />a TESTING LAB APPROVED PRIOR TO STARTING CONSTRUCTION BY THE BUILDING DEPT. AND THE 3.) DO NOT SUBSTITUTE OTHER ADHESIVES FOR THE HILTI HIT-HY 270 AND THE HILTI HIT-HY 200-R <br />_ ARCHITECT. INSPECT ALL SHOP WELDING UNLESS THE. SHOP IS CERTIFIED BY THE LOCAL WITHOUT PRIOR WRITTEN AUTHORIZATION FROM E.N.W. <br />BUILDING DEPARTMENT. 4.) DO NOT OVER CUT OPENINGS AT CORNERS, TYPICAL. <br />FOUNDATION: SOILS ENGINEER TO INSPECT FOOTING EXCAVATIONS AND PROVIDE 5.) CONTRACTOR TO VERIFY THAT NO VERTICAL WALL JOINTS OCCUR WITHIN THE NEW OPENING AND LAT <br />1!"xH.5.5. Vl,IDTH1°PE <br />0 STRONGBACK SPACE. <br />w/ 2- 5/8" O ALL THREAD <br />COMPACTION TESTS AS NOTED ABOVE. ,m <br />_ CONCRETE: TAKE CONCRETE CYLINDERS AS REQUIRED, VERIFY SLUMP AND <br />STRENGTH. SPECIAL INSPECTION IS REQUIRED DURING THE TAKING OF TEST NEW SLAB EXIST. SLAB <br />DETAIL 3c <br />SPECIMEN, AND PLACING OF ALL REINFORCED CONCRETE. <br />REINFORCING: VERIFY ALL REINFORCING IS PLACED IN ACCORDANCE WITH THESE <br />0 DRAWINGS. CHECK FOR REQUIRED COVED, SIZE, SPACING, LAP AND GRADE. <br />SPECIAL INSPECTION IS REQUIRED DURING THE PLACING OF REINFORCING <br />� LIGHTLY GREASE DOWEL <br />STEEL.THIS SIDE PRIOR TO <br />CONC. EXPANSION POUR & AFTER EPDXY <br />(E) 6" CONC. SLAB <br />(E) 10" CMU WALL <br />SUB -GRADE <br />BY OTHERS <br />6 <br />8" C.I.P. w/ #4 <br />12"oc HORIZ., TYP. <br />EXIST. CURB <br />TO REMOVE PER PLAN <br />#4 12"oc <br />EPDXY & EMBED <br />4" TYP. <br />(E) FOOTING 0'_0„ <br />NEW MECHANICAL HOUSE <br />BY OTHERS. ATTACHMENT <br />TO CONC. BY OTHERS. <br />6" CONC. SLAB <br />REINF. PER PLAN --ti <br />#4 CONT. -� \ <br />2' --- -- <br />#4 E.F. T.B. - - <br />& 16"oc BTWN. <br />4 v. <br />- - -;- 4 <br />a. <br />VARIES ± _ <br />SEE <br />DETAI! <br />EXIST. <br />IVIASOi <br />WALL <br />/2" O ANCHORS <br />R 24"oc SEE <br />ROTES BELOW <br />VS1.1 TYP. <br />If <br />ANGLE PER <br />DETAIL 3a <br />I EXIST. WALL TO <br />I BE REMOVED <br />I ONLY AFTER <br />I LINTEL ANGLE <br />IS IN PLACE <br />DETAIL <br />1. CK MASONRY ANCHORS TO EXIST. SLAB MAXIMUM SPACING & <br />& DRILLED -IN DOWELS: COPY OF ICC REPORT FOE ANCHORS OR ADHESIVE SYSTEM USED USE P.N.A. PD3 BASKET ASSEMBLY OR <br />u� EXIST. SLAB LOCATION PER FD�3. PLAN J� <br />MUST BE AVAILABLE AT JOB SITE. VERIFY ANCHORS OR ADHESIVE J APPROVED EQUAL, W/DOWELS @ 24"tic. <br />SYSTEM INSTALLATION IN ACCORDANCE WITH REPORT. NEW 6" CONCRETE t/4 x 1I8'" SOFT -CUT JOINT ( SPACING MAY BE INCREASED TO 26" IF <br />� a STEEL: IN ACCORDANCE WITH TABLE 1704.3 OF IBC AND REFERENCED STANDARDS. SLAB ON GRADE w/ SUPPORTING DATA CAN PROVE THAT A <br />6 CONTINUOUS INSPECTION: #4 REINF. WHERE <br />18"oc EACH GREATER SPACING CAN BE USED WITH <br />SLIP -CRITICAL (SC) HIGH STRENGTH BOLTED CONNECTIONS. WAY CENTERLINE APPLICABLE PER PLAN -1 COSTCO FORKLIFTS. BASKET SHOULD BE <br />0 COMPLETE AND PARTIAL PENETRATION GROOVE WELDS. NON-DESTRUCTIVE O SLAB PER PLAN MANUFACTURED TO HOLD PLATES AT i 1/4" <br />M TESTING IS REQUIRED FOR ALL COMPLETE PENETRATION LDS - SHOP AND VFY. OF SLAB CTR. <br />MULTIPASS FILLET WELDS. TO MATCH EXIST. ffi�. s _ d ® d, a �. <br />t d <br />SINGLE -PASS FILLET WELDS GREATER THAN 5/16-INCH. v _ > °' d <br />WELDING OF REINFORCING IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, <5 : �; - o ®c,. <br />a_ BOUNDARY ELEMENTS OF SPECIAL REINFORCED CONCRETE SHEAR WALLS op��0 �d0 ®0 0 QQoLU <br />`� �o HOLD 7" �} �' <br />G3 c,4 o O o0 ® 0 0 U 0® 04 (} <br />AND SHEAR REINFORCEMENT. p o®��c7 0 po o®® C5 0 0 000 0 ca 00 0 <br />PERIODIC INSPECTION: COMPACTED i I i-I I i l I; i �+ 0 od�®o 00 CLR. MAX. 0 o0aoo n0 <br />®I I -III f- <br />0) SUMO DE BY i - _ <br />VERIFY HIGH -STRENGTH BOLT IDENTIFICATION MARKINGS CONFORM TO -1 1-� ! 1-! =I I 1=1 i 1=I 11 5/8 O x 9 SMOOTH ROUND =1 11=1 11=1 I NOTE: =1 I 1=1 I 1=1 <br />SPECIFIED ASTM STANDARDS. REVIEW OF MANUFACTURER'S CERTIFICATE OF OTHERS (T!=� I 1=I 1= 1. SEE ARCH. DTLS, FOR SPECIAL JOINT FINISH. <br />� DOWELS 18° oc. EPDXY TO 2 }SOIL SUBG DE PER SOILS REPORT. <br />COMPLIANCE. EXIST. SLAB wl HILTI HET-HY ) <br />INSTALLATION OF BEARING -TYPE BOLTED CONNECTIONS. 200-R ADHESIVE. EMBED 4 1/2" 3.) USE OF OTHER JOINT SYSTEMS NOT ALLOWED. <br />SINGLE -PASS FILLET WELDS 5/16-INCH OR LESS. w/ SPECIAL INSPECTION, ORIENT <br />FLOOR AND ROOF DECK WELDS. PERPENDICULAR TO EXIST. <br />COLD -FORMED STEEL FRAME WELDING. SLAB SAW CUT EDGE AND <br />In <br />WELDING OF STAIRS AND RAILINGS. LEVEL w/ HORIZONTAL PLANE <br />WELDING OF STUDS. <br />VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN ASTMSECTION SHRINKAGE JOINT (S.J.) <br />A-706. <br />En <br />WELDING OF REINFORCING STEEL OTHER THAN THAT REQUIRING CONTINUOUS (TYPICAL SMALL SLAB REPLACEMENT DETAIL) 3/4" = V-0" 3/4" = 1'-01' <br />O INSPECTION. <br />�� �I�1L+i7���1�i�Z���l�+��[�►f'�E :��I+illtl�tLl�[+�%�rt�f�l�.IF <br />r <br />MAXIMUM SPACING <br />0 �J <br />� ®po q- <br />0 C70o -, <br />2 <br />ROWS #4 f-@ 16i'oc <br />EPDXY `rv/ HILTI 20OR <br />EMBED 4" wl SPCL INSP., TYP. <br />3/4" = 1'-0" <br />COLUMN PER PLAN <br />SLAB PER PLAN <br />vfell 101 <br />a <br />1/2" ISOLATION JOINT <br />p d <br />(E) 6" CONC. SLAB <br />6" t� <br />} <br />GAP Pa <br />a <br />(E) 10" CMU WALL <br />3 <br />SUB -GRADE <br />BY OTHERS <br />1 <br />w C.I.P. w/ #4 <br />12"oc HORN., TYP. <br />EXIST. CURBCD <br />` I <br />r <br />TO REMOVE <br />r 1 <br />" <br />41 <br />#4 @ 1 2 oc <br />,a <br />EPDXY & EMBED <br />I <br />4" TYP. <br />LA <br />(E) FOOTING <br />V-3" VFY. <br />I ( <br />41 <br />{ , <br />PRE-FAB METAL w u <br />r STAIRS PER ARCH <br />MOMENT FRAME , <br />COL. BY OTHERS <br />LL 1 I <br />i <br />> <br />{ <br />1 A <br />> I " <br />J <br />I , <br />S.J. s <br />I Y <br />a Y <br />{ <br />i <br />I � <br />i S.J. 8 <br />_.. -... _.... _ S 1.3 <br />LL <br />l I t <br />I I ) - <br />A <br />I 1 <br />MOMENT FRAME <br />I COL. BY OTHERS �I / C� <br />S.J. <br />1 I <br />S1.1LL <br />I <br />> a <br />C3 i <br />> a ! <br />NEW 6" CONCRETE SLAB ON GRADE. SLAB ! i <br />Ji <br />REINFORCING #4 @ 18"o/c EACH WAY. ! I <br />(CHAIR T-Wo/c MAX.) @ SLAB MID -DEPTH. ! <br />OVER SUB -GRADE BY OTHERS, TYP. TOP I <br />OF MECH. PAD c@ 2'-6" VFY. <br />S 1.1 <br />I � <br />A <br />s? 5y <br />� a S 1.1 <br />c' I <br />if <br />! <br />I !I <br />z I <br />I <br />I I) <br />a 7 <br />= S.J. r i <br />z <br />I� 6" GAP <br />LL <br />'. <br />x <br />I �I <br />cy�J\`' <br />%• <br />LL <br />t... <br />> t 2 I.. <br />I I I <br />C) <br />y <br />5 <br />I t <br />t®�®� � I <br />I 3 j <br />. 4 <br />I ; <br />PARIIAL FOUNDATION PLAN <br />I „ 5 <br />-- <br />NOTES: 1/4" = 1'-0" <br />1.) ALL ITEMS ARE EXISTING (E) UNLESS NOTED AS NEW (N). <br />L I <br />IF EXISTING DIMENSIONS AND EXISTING CONDITIONS ARE NOT AS SHOWN ON PLANS AND SECTIONS. <br />3.) VERIFY ALL DIMENSIONS wl ARCH. <br />4.) ( ) INDICATES TOP OF FOOTING RELATIVE TO FINISH FLOOR. <br />5.) VERIFY SLAB JOINT LOCATIONS WITH ARCH. <br />0 <br />1�1 C� <br />Cl? cv <br />z <br />0 <br />W <br />ry- <br />W C) <br />5 s-- <br />O <br />LiJ <br />U � <br />L <br />`'�J <br />i <br />F" <br />� T <br />00 <br />`s ti <br />1 <br />z <br />0 <br />1® <br />0 <br />z <br />D <br />I� <br />I� <br />0 <br />CD <br />z <br />W <br />z <br />W F <br />0 <br />(j) 0 <br />SHEET NO: <br />71 <br />