-- GENERAL NOTES-- <br />1 DESIGN BASIS: Designed in accordance with the 2015 International Building Code <br />(IBC). <br />2 OCCUPANCY CATEGORY: II (per IBC Table 1604.5) <br />3 DESIGN DEAD / LIVE LOADS <br />- Floor Live Load: 100 PSF Typical Slab on grade <br />Roof Dead Load: 15 PSF Typical (Incl. Framing) <br />Roof Live Load: 20 PSF Typical <br />4 DESIGN SNOW LOADS (ASCE 7-10) <br />- Ground Snow Load: Pg = 20 PSF <br />Flat Roof Snow Load: Pf = 14 PSF <br />- Minimum Uniform Roof Snow Load = 25 PSF (unreducible) <br />- Snow Load Importance Factor: Is = 1.0 <br />5 DESIGN WIND LOADS (ASCE 7-10) <br />V (3-sec gust) = 110 MPH / Exposure: B / Importance Iw = 1.0 <br />Components & Cladding: Component and cladding -wind pressures to be used for <br />the design of exterior components and cladding (by others) shall be determined in <br />accordance with ASCE 7 and the IBC. <br />6 DESIGN SEISMIC LOADS (ASCE 7-10) <br />- Site Class = D <br />- Seismic Design Category = D / Importance le = 1.0 <br />Ss = 124% / S1 = 43% <br />Sds = 0.332 / Sd 1 = 0.463 <br />Building System: Bearing Wall System <br />SFRS: Light Frame Wood Walls with Structural Wood Shear Panels <br />Response Modification Factor Used: (R) m 6.5 <br />7 QUALITY: Contractor shall ensure high standards of worksmanship throughout, <br />with strict adherence to the contract documents and all governing codes and <br />standards, <br />6 DESIGN Kingworks <br />RESPONSIBILITY: g orks is responsible only for the design of the <br />primary structural system as shown in the contract documents. Design of all <br />secondary structure or non-structural elements are by others. <br />9 DISCREPANCIES: Notify the Architect immediately of any discrepancies between <br />those notes, the contract drawings, the specification, or the governing code, The <br />Architect shall reply in writing. Any related work performed by the Contractor prior to <br />receiving a reply from the Architect is at the Contractor's sole risk. For purposes of <br />bidding, the most stringent of the conflicting documents shall apply. <br />10 VERIFICATIONS: Verify all existing conditions; verify all dimensions in the field; <br />verify architectural, mechanical and electrical openings for size, location and <br />number; notify the Architect of any discrepancies, substandard existing conditions, <br />or conditions not included in or contrary to the Contract Documents prior to shop <br />drawing submittal or construction. <br />11 DRAWING COORDINATION: Coordinate the structural drawings with drawings <br />from all other disciplines (including but not limited to Architectural, Civil, Mechanical, <br />and Electrical). <br />12 COMPLETED FORM: The structure shown in these drawings is designed to be <br />stable and to resist the loads above only in a fully completed form. Contractor shall <br />ensure that the structure is adequately braced and shored during construction for <br />all temporary loads until all elements are in place, and shall ensure that temporary <br />loadings do not exceed the allowable capacity of any structural elements both <br />before and after these elements are in place. <br />13 MEANS AND METHODS: Contractor is solely responsible for site safety, <br />coordination, procedures, construction methodology, shoring, bracing, sequencing, <br />and all other "means and methods" of construction except where specifically shown <br />in the Contract Documents. <br />14 PROTECTION AND BRACING: Contractor is solely responsible for the protection <br />of existing buildings, utilities, streets, equipment, etc. during construction. Provide <br />temporary bracing and protection as required, <br />15 SCALING: Do not scale drawings. Sep: architectural drawings for dimensions, and <br />notify the Architect of any discrepancies. <br />16 ALTERATIONS: Any holes or other alterations to the structure which are not <br />specifically detailed on the Contract Drawings shall be submitted to the engineer for <br />approval <br />17 LOAD COORDINATION: The design of all pre-engineered components shall <br />include provisions for precise locations and weights of all mechanical units and <br />other concentrated loads. Concentrated loads are not necessarily indicated on the <br />Structural Drawings, and must be coordinated by the General Contractor, who shall <br />also inform the Architect of any significant loads not shown in the contract <br />documents, The Contractor shall assume full responsibility for coordination of <br />weights, locations, hanger spacings, methods of attachment and seismic bracing of <br />all mechanical units, sprinklers, pipes, ductwork, and other miscellaneous MEP <br />assemblies. <br />16 MEP CONNECTIONS TO STRUCTURE: Unless specifically shown otherwise in the <br />Contract Documents, all anchorage, support, and seismic bracing of mechanical <br />and electrical equipment, piping, ceilings, fixtures and other non-structural <br />components shall be designed by a Washington State Licensed Professional <br />Engineer and installed by the Contractor. The engineer shall be retained by the <br />Contractor, and the Contractor is responsible for all associated engineering, <br />component, and installation costs. Design shall be per ASCE. 7 Chapter 13. <br />19 DELIVERY, STORAGE AND HANDLING: All products shall be delivered, stored, <br />and handled according to the Manufacturer's recommendations and installation <br />instructions. Protect all items from damage, moisture, corrosion, or other <br />deterioration before, during and after installation. <br />20 COPYRIGHT: These drawings, and all designs shown within these drawings, are <br />copyrighted by Kingworks Consulting Engineers. Duplication is not permitted <br />without written permission. The designs shown herein are intended for this project <br />only and may not be used on any other project or for any other purpose. <br />-- SUBMITTALS -- <br />I GENERAL: Provide PDF of all submittals to the Architect. Allow two weeks for <br />review. Submittals will be reviewed for general conformance to the contract <br />documents. Responsibility for adherence to the contract documents lies solely with <br />the Contractor, including but not limited to dimensions, sizes, connections, and <br />quantities. <br />2 CONTRACTOR REVIEW: Contractor shall review, mark, and stamp all submittals <br />before submittal to the Architect. Unreviewed or unstamped submittals will be <br />returned to the Contractor without review. <br />3 RESUBMITTALS: Resubmittals shall have all revisions clearly identified with <br />"drawing clouds" and revision dates. KW shall not be responsible for review of .any <br />unmarked revisions. <br />4 SHOP DRAWINGS: To include typical and unique conditions and all connections, <br />shall be submitted to the Engineer of Record for the following products prior to <br />fabrication. Shop drawings shall clearly demonstrate the Contractor's understanding <br />of the contract documents. The following shall be considered minimum structural <br />submittals for this project: <br />- Concrete Mix Designs (confirm f'c prior to construction) <br />Slab -on -Grade Jointing Plan <br />5 DEFERRED SUBMITTALS: Shall be designed by a Washington State Licensed <br />Professional Engineer (Structural Engineer where required by jurisdiction). <br />Submittals shall clearly indicate all loads and reactions to be imposed on the <br />primary structure. Submittals shall include all components and connections required <br />to perform the work. Where the Contract Documents indicate member or <br />connection qualities and/or quantities, these shall be considered a minimum and <br />remain the design responsibility of the component engineer to increase as required <br />to satisfy load and deflection requirements. Deferred submittals shall include <br />calculation set. Both the calculation set and all relate shop drawings f i d op d aw ngs o the <br />deferred submittal shall be sealed prior to submission. The Architect shall p t t s a forward <br />deferred submittals to the Building Official where required. The following shall be <br />considered Deferred Submittals on this project: <br />- Metal Plate Connected Wood Trusses (MPCWT) <br />-- SUBMITTALS -- <br />6 SUBMITTAL REVIEW COMMENTS: Engineer marks and comments on shop <br />drawings and other submittals are a normal and expected part of the submittal <br />process, and are not to be used as a basis for change orders except in cases <br />where these marks result in or derive from substantial changes to the Contract <br />Drawings. Time required to revise and resubmit any submittal shall be considered <br />inherent to the submittal review process and shall not be deemed a change order. If <br />discrepancies are discovered between the submittals and the Contact Documents <br />(either before, during, or after submittal review), the Contract Documents shall <br />govern and be implemented unless specifically directed otherwise. <br />-- SPECIAL INSPECTIONS, TESTING, AND STRUCTURAL OBSERVATION <br />®� <br />1 GENERAL: A special inspection agency shall be retained by the owner to perform <br />inspections according to IBC Chapter 17. The following scheduled structural special <br />inspection and testing regimen shall be cross-referenced with the IBC and its <br />referenced standards for more specific requirements and exceptions. Special <br />inspection and test reports shall be submitted to the Building Official, Architect and <br />Structural Engineer in accordance with IBC 1704.2.4. <br />-- STRUCTURAL SPECIAL INSPECTION SCHEDULE -- <br />REFERENCE (2015 IBC Section, <br />STRUCTURAL ITEM FREQUENCY (C=coefinuous, Rtperiodic) uon) <br />1 POST -INSTALLED Table 1705.3 <br />ANCHORS <br />- Conform to Spec C (type, size, embed depth, <br />Reqmts location, finish) <br />Conform to M1fr C (hole depth, diameter, Per Product iCC®ES <br />Reqmts cleaning, install, torque) Reports <br />2 IWOOD 1705.5 <br />- Shearwalls (nailing, P (not req'd when fasteners are 1705.11.1, 1705.12.2 <br />thickness, grade, in single row and spaced greater <br />blocking, top and than 4" o/c) <br />bottom fastening, sill <br />bolts, holdowns) <br />3 <br />SOILS & <br />FOUNDATIONS <br />1705.6, Table 1705.6, <br />Geotech Report <br />- Subgrade Adequacy <br />P (beneath fill and/or <br />foundations) <br />Table 1705.6 <br />- Excavation Depth <br />P <br />Table 1705.6 <br />- Fill Materials <br />P <br />Table 1705.6 <br />- Fill Placement & <br />Compaction <br />C <br />Table 1705.6 <br />-- SPECIAL INSPECTIONS, TESTING, AND STRUCTURAL OBSERVATION <br />2 NONSTRUCTURALCOMPONENTS: Nonstructural components are also subject to <br />special inspection for conformance to the Seismic Design Requirements of ASCE <br />7-10 Chapter 13. The support and seismic bracing of nonstructural components <br />shall be designed by a Washington State Licensed Engineer, who shall be retained <br />by the Contractor. Nonstructural components subject to seismic design and periodic <br />special inspection requirements of ASCE 7-10 and IBC Chapter 17 include (but are <br />not limited to) the following: <br />- Suspended Ceilings (ASCE 7-10 Sec 13.5.6.2.2) <br />- Mechanical and Electrical Components (IBC 1705.12.6) <br />Reference the architectural, electrical, and mechanical drawings and/or <br />specifications for additional special inspection and testing requirements. <br />3 STRUCTURAL OBSERVATION: Kingworks will perform Structural Observations in <br />accordance with IBC Section 1704.6 if/as required. These observations provide <br />intermittent checks of general conformance to the design intent and are in addition <br />to (not replacing) the third -party special inspection regimen.It shall be the <br />Contractor's responsibility to keep the Structural Engineer apprised of the general <br />schedule of construction, such that observations may be made at appropriate <br />stages before significant structural components (such as reinforcing bars, framing <br />members, or wall holdowns) are obscured. <br />- FOUNDATIONS E -- <br />1 SOIL ALLOWABLE BEARING PRESSURE: 1500 PSF (per IBC presumptive <br />values) <br />2 VERIFICATIONS: Verify sizes, slopes and locations of tunnels, electrical cells, pits, <br />pipes, floor drains, trenches and floor recesses with architectural, mechanical and <br />electrical contractors. <br />3 UTILITIES: Utilities are not to pass through or beneath footings, stemwalls, and <br />other concrete work on grade except as shown in specific details. <br />4 ALIGNMENT: All footings shall be centered below columns and walls, unless <br />dimensioned otherwise. <br />6 FROST PROTECTION: Maintain minimum 1'-6" soil cover, measured from finished <br />grade to the bottom of the footing, for perimeter wall foundations and isolated <br />exterior foundations. <br />7 EXCAVATION SLOPE: Excavation slope shall not exceed that permitted by local <br />regulation, except as specifically approved by the geotechnical engineer. <br />-- ANCHORAGE TO CONCRETE -- <br />1 MATERIALS (unless noted otherwise in the drawings) <br />Concrete or grout must cure for a minimum of 21 days prior to drilling any holes or <br />placing post -installed anchors. <br />Anchor type shall be according to the drawings. All post -installed anchors installed <br />in concrete shall have ICC-ES reports demonstrating IBC compliance for use in <br />cracked concrete and for seismic loading. Substitutions not permitted without written <br />permission by KW. <br />Pre -approved Epoxy for post -installed threaded rod or reinforcing in concrete base <br />material: HILTI HIT -RE 500 V3 or Simpson SET-XP or DEWALT/Powers Pure110+. <br />- Fire -approved "Expansion Anchors" in concrete base material: HILTI Kwik®Bolt TZ <br />or Simpson Strong -Bolt 2, or DEWALT/Powers Power -Stud+ SD2. <br />Pre -approved "Screw Anchors" in concrete base material: HILTI HUS-EZ or <br />Simpson Titen HD or DEWALT/Powers Screw -Bolt+ <br />Pre -approved "Powder Actuated Fasteners" in concrete: HILTI or approved equal, <br />with diameter/type per the Structural Drawings (0. 145"0 DON). <br />- Post -installed or Cast -in -Place Threaded Rod (Anchor): ASTM A36 <br />- Post -installed Reinforcing: ASTM A615 Grade 60 <br />2 EMBEDMENT: Anchor embedment in base material shall be per the drawings, <br />which shall govern over the typical values shown below. Where not otherwise <br />indicated, provide embedment as follows: <br />- Epoxy to Concrete: Min Embed = 12 x (Rod/Bar O) for 5/3" O (5) or smaller, 14 x <br />(Rod/Bar O) for 3/4" (6) or larger <br />Expansion Anchor to Concrete: Min Embed = 3 x (Anchor O) <br />- Screw Anchor to Concrete: Min Embed = 9 x (Anchor O) <br />- PAF to Concrete: Min Embed = 1 1/4", Min Edge Distance = 3" <br />- Cast -In -Place Anchor: Min Embed = 7" to top of embedded washer or hook <br />3 INSTALLATION: Post -installed anchor hole diameter, drilling depth, cleaning and <br />installation procedure shall be in accordance with the current Manufacturer's Printed <br />Installation Instructions (MPII) provided in the ICC/ES report. Holes shall be drilled <br />with rotohammer equipment. Core -drilled holes are not permitted unless specifically <br />noted otherwise. <br />4 COLD -WEATHER INSTALLATION: Do not use epoxy or adhesive anchors outside <br />of their rated temperature range. Contact the Structural Engin <br />eer for alternate if the <br />base material temperature may b less n 4 e e e e s the 0 degrees during installation or <br />p Y g g <br />curing. <br />5 CAST -IN -PLACE ANCHORS: Cast -in -place anchors shall have nut and washer at <br />embedded end, UON. Anchors shall be affixed to the form to prevent movement <br />during pouring, vibration, or set-up and shall not be "stabbed" into wet concrete or <br />grout. Verify adequate length of exposed thread to fully engage all attached work. <br />anchorsexterior, or subject to moisture, or where �* <br />- <br />contact with pressure treated wood, shall begalvanized per ASTM Al 53, <br />post-installedincluding matching washers and nuts. <br />7 REINFORCEMENT LOCATIONS: All • • to <br />avoid• into reinforcement,• •. by -= <br />Reinforcement e• with considerationo post -installed <br />anchors. Do not damage reinforcing during drilling operations. <br />1 MATERIALS <br />- Required concrete strength 'Tc" shall be evaluated at 26 days (56 days OK for fly <br />ash or slag concrete). <br />- Conform to following concrete material schedule requirements. <br />-- CONCRETE MATERIAL SCHEDULE -- <br />f'c <br />(PSI) <br />W/CM <br />(MAX) <br />COARSE <br />AGG (MAX) <br />FLY ASH <br />SLAG <br />TOT <br />F.A.+SLAG <br />FOOTINGS <br />3000* <br />0.60 <br />11/2" <br />0-25% <br />30-50% <br />30%-50% <br />SLAB <br />4000* <br />0.50 <br />1" <br />0-25% <br />20-40% <br />20%-40% <br />COLUMNS <br />4000* <br />0.50 <br />3/4" <br />0-25% <br />20-40% <br />20%-40% <br />-- WOOD FRAMING -- <br />12 BEAMS: Bear beams full length and width on supporting wall plates and/or posts, <br />unless shown otherwise per typical details. Provide glulam bears camber equal to <br />3500-foot radius for all simple span beams, except where special camber is <br />indicated on the plans; install with upward curvature (highest at midspan). Do not <br />camber cantilever beams unless specifically noted. Beams exposed to view shall <br />be Architectural Appearance grade in accordance with AITC 110, with finish per <br />the Architect. <br />13 POSTS: Unless noted otherwise, provide Simpson BC or AC caps at all post to <br />beam and post to beam (below) connections. At post to concrete provide Simpson <br />ABU or CB post bases, uon. Posts in walls may bear on the sill with connection <br />hardware per typical details. At wood or steel posts/columns continuous through <br />floor framing, block tight all-around at floor to prevent lateral movement or <br />buckling. <br />14 CONNECTORS: Connectors and/or fasteners called out by letters & numbers in <br />the drawings shall be manufactured by Simpson Strong -Tie, or approved equal All <br />connecting hardware shall be installed per the Manufacturer's recommendations <br />and requirements, as per current catalog and related publications. Fill all fastener <br />holes with the fastener type (diameter and length) indicated by the Manufacturer, <br />uon. Where light -gage connector occurs at steel column, weld 1/6" all-around, uon, <br />17 PRESSURE TREATMENT: Except where specifically noted otherwise, the <br />following member types shall be pressure treated in accordance with the following <br />guidelines, in addition to any such members noted in the plans or details. <br />Minimum treatment retention shall be as recommended by AWPA for the "Use <br />Category„ appropriate to each application. Treatment shall be non -ammonia <br />formulation in all cases. <br />Lumber exposed to exterior, humidity, or within 3" of soil: AWPA C2 <br />Lumber directly against concrete: AWPA C31 <br />- Plywood sheathing (where indicated): AWPA C9 <br />- Glulam beams (where indicated): AWPA C26 <br />Borate -treated lumber is acceptable in locations where protected from rainfall or <br />other potential repeated moisture, such as sill plates in an enclosed wall cavity and <br />interior ledgers. <br />- Engineered Lumber (where indicated): Per Manufacturer <br />16 FIELD TREATMENT: Field treat all cuts, ends, and holes in pressure treated <br />lumber with copper naphthenate applied per manufacturer's recommendations. <br />19 EXTERIOR WOOD PROTECTION: Provide fleshings, sealants and finishes per <br />the Architect in order to protect all exterior wood surfaces and post/beam ends <br />from moisture. <br />20 GALVANIZING: All steel components, hardware, or fasteners for wood framing <br />members exposed to moisture, high humidity, or in contact with pressure treated <br />lumber shall be hot -dip galvanized per ASTM A153. Light gage connectors shall <br />be galvanized per ASTM A653, G165 minimum (Simpson "Z-max" or approved <br />equal). The above described galvanizing requirements specifically include, but are <br />not limited to: nails, screws, bolts, washers, nuts, anchor bolts, threaded rods, <br />cast -in -place and post -installed anchors, Simpson hardware, and weldments. <br />(Exception: not required for S X/DOT borate -treated wood protected from <br />weather.) <br />21 MEMBRANE PROTECTION: Where specified steel hardware in contact with <br />pressure treated wood is unavailable in HDG or G165 finish, Grace Vycor (or <br />approved eq) membrane shall be placed per manufacturer's recommendations to <br />isolate the hardware from the treated wood. HDG fasteners shall be used in such <br />instances. <br />22 SHEATHING: Place roof and floor sheathing with face grain oriented in the <br />direction of span. Offset adjacent rows of sheathing panels by 24" minimum, with <br />all panel ends bearing on joists, beams, trusses or walls. Place cants or crickets <br />over continuous basic roof sheathing with drilled vent holes per the Architect. <br />Install wall sheathing in either the horizontal or up -right orientation. Adjust all <br />sheathing layouts so that no panel is less than 16" long. Where edges are not <br />required to be blocked per schedule, provide Simpson PSCA clips at spacing per <br />catalog recommendation. All sheathing shall be APA rated, with <br />type/blocking/fastening per the following schedule. <br />23 SHEATHING FASTENING: Minimum nailing per the following schedule shall apply <br />at all locations, except where larger nails and/or smaller spacing are required by <br />plans or details. Shearwall nailing is shown by schedule on the plans. Where <br />"boundary nailing„ (BN) and/or "edge nailing" (EN) are referenced in these <br />drawings, panel edge values per the schedule shall apply. Blocking for edges shall <br />be 2x4 flat, minimum, unless a greater size is required to avoid splitting. See plans <br />for zones of special nailing requirements. <br />-- WOOD SHEATHINGSCHEDULE ®a <br />USE <br />TYPE <br />BLOCK EDGES <br />MIN EDGE NAILING <br />MIN FIELD NAILING <br />Shearwalls <br />15/32" PLY or <br />OSB (Struct 1) <br />"Yes <br />Per SW Sched <br />(EN) <br />1 Od @ 12" <br />Other Sheathed Walls <br />15/32" PLY or <br />OSB <br />No <br />3d @ 6" <br />3d @ 12" <br />Roof <br />15/32" PLY <br />No <br />6d @ 4" (BN) <br />3d @ 12" <br />-- METAL PLATE CONNECTED WOOD T ( PC ®s) -- <br />1 DESIGN STANDARDS: The design, manufacture, and quality assurance of <br />MPCWT shall be in accordance with the ANSI/TPI 1. In addition, all requirements <br />of IBC Section 2303.4 shall be satisfied. <br />2 SUBMITTAL PACKAGE: The truss submittal package provided by the <br />manufacturer shall consist of individual truss design drawings (including cricket <br />overtraming), a truss placement diagram, truss member permanent bracing plan <br />and details, any other structural details germane to the truses, and sealed cover <br />sheet/truss index sheet. <br />3 DESIGN / PLACEMENT DRAWINGS: The truss design drawings for each <br />individual truss shall include all information required by IBC Section 2303.4.1.1. <br />The truss placement diagram shall be in accordance with IBC Section 2303.4.2. <br />4 LOADS: Trusses shall be designed by the manufacturer for the following minimum <br />non -superimposed loads, in addition to roof live, snow, seismic and/or wind loads <br />indicated elsewhere in these drawings or notes: Top Chord Dead Load= 5 psf, <br />Bottom Chord Dead Load = 10 psf, Bottom Chord Live Load = 20 psf. See plan <br />and details for additional special loads. Contractor shall coordinate locations and <br />amplitudes of special loads prior to shop drawing submittal <br />5 COMPONENT / CONNECTION DESIGN: The truss designer is responsible for all <br />the design of all truss components and connections as required to form a fully <br />functional roof system, except where specifically detailed in these drawings. <br />6 TOP CHORD: Top chord shall be 5 1/2" minimum depth in all instances, <br />7 DEFLECTION: Deflection of roof trusses shall not exceed L/360 or 1 inch for live or <br />snow load, nor L/240 for total load. <br />6 PERMANENT BRACING: Truss manufacturer shall design and provide all <br />components required for permanent bracing of the truss system. Permanent <br />bracing shall conform to IBC Section 2303.4.1.2 and the WTCA/TPi "Building <br />Component Safety Information" (BCSI) guide, current edition. The bracing design <br />shall include, but not be limited to: plan layout, bracing sizes, "scabs" or other <br />reinforcement, connections of braces to chords, web members, and supporting <br />structure. The bracing design shall be clearly indicated in the truss submittal <br />package. <br />9 SPACING: MPCWT spacing indicated on plans shall be considered to be a <br />maximum allowable and shall be decreased as required to meet zones of higher <br />loading (including but not limited to snow drift or mechanical unit loads). <br />10 MULTI -PLY TRUSSES: Multiple ply (girder) trusses, where required by plan and/or <br />by the manufacturer's engineer, shall be sistered per the manufacturer to ensure <br />equal load distribution between members. <br />11 MEP COORDINATION: See Specifications and Mechanical Drawings for critical <br />duct locations/sizes that may affect truss profiles and design parameters. General <br />Contractor shall coordinate all such requirements and all special circumstances <br />shall be clearly indicated in the truss submittal package. See General Notes for <br />additional coordination responsibilities. <br />CONC STEMWALL <br />WOOD BRG WALL (WHERE OCCURS) <br />EDGE OF STEMWALL / SLAB ON GRADE <br />CONTINUOUS CONC FTG <br />APPROX LOCATION OF STEP IN FTG. <br />COORDINATE WITH ARCH DWGS. <br />F CONC FTG <br />SEE FTG SCHEDULE <br />WOOD BRG WALL ABOVE <br />E v STRUCTURAL BRG WALL BELOW <br />WOOD NON-BRG WALL ABOVE <br />EXISTING (E) BRG WALL BELOW <br />WOOD SHEARWALL <br />SHEARWALL END POST (SWEP) <br />SHEARWALL TYPE, <br />SEE SHEARWALL SCHEDULE <br />EXISTING (E) SHEARWALL FRAMING. AT <br />DEMO. AREAS, OR FILLED iN AREAS IN (E) <br />SHEARWALL, PROVIDE SHEARWALL <br />FRAMING, SHEATHING, & FASTENING PER <br />PLANS & SCHEDULE. <br />SHEARWALL TYPE, <br />SEE SHEARWALL SCHEDULE <br />JOIST / TRUSS <br />BEAM <br />EXISTING (E) BEAM/JOIST <br />- - ROOF OVERFRAMING <br />1 <br />LEGEND (REMODEL) <br />U 1 /4 = 1 -01 <br />I <br />Verify;_ <br />Enclosing box measures 1/2 inch tall x 2112 inch wide <br />when drawings are printed at full scale. <br />`8/22 1 <br />® pG� 37388 t y <br />�/I2AL E�aCs <br />1�AL <br />Digita_ Seal <br />Applied to PDF <br />!17 1• 1.f �. � J <br />File No: <br />Drawn By: BAndersen <br />Checked By: JKing <br />Issued for: BID <br />�.t <br />© copyright KW. 2017 <br />