NOTES (APPLICABLE TO ALL, ELECTRICAL DRAWINGS) <br />1. ALL SYSTEMS, EQUIPMENT, DEVICES, RACEWAYS, CABLES, ETC. INDICATED ARE <br />NEW UNLESS SPECIFICALLY NOTED AS EXISTING. <br />2. THE ELECTRICAL WORK SHALL INCLUDE ALL WORK SHOWN ON THE DRAWINGS, <br />DETAILS, DIAGRAMS, SCHEDULES, ETC., AND AS DESCRIBED IN THE SPECIFICATIONS. <br />3. PLAN DRAWINGS ARE DIAGRAMMATIC IN FORM AND DO NOT ATTEMPT TO SHOW <br />COMPLETE (DETAILS OR LIST EVERY ITEM OF THE ELECTRICAL SYSTEM, EQUIPMENT, <br />OR BUILDING CONSTRUCTION; HOWEVER, THE ROUTING OF RACEWAYS AND CIRCUITS, <br />THE LOCATIONS OF EQUIPMENT, DEVICES AND FIXTURES REPRESENT THE DESIRED <br />FINISHED ARRANGEMENT. <br />4. OBTAIN APPROVAL FROM ARCHITECT & ENGINEER. PRIOR TO PROCEEDING WITH <br />ALTERNATE CONDUIT ROUTES. <br />5. DETAIL DRAWINGS SHALL BE CONSIDERED APPLICABLE TO ALL PLAN DRAWINGS <br />AND SIMILAR CONDITIONS EVEN IF THE DETAILS ARE NOT SPECIFICALLY REFERENCED <br />6, RACEWAYS AND CABLES THROUGHOUT THE FACILITY SHALL BE RUN CONCEALED IN <br />THE WALLS, ABOVE THE CEILING OR BELOW THE FLOOR, WHERE POSSIBLE, EXCEPT, <br />EXPOSED WITHIN UTILITY & OTHER NON-PUBLIC SPACES. WITHIN PUBLIC SPACES, <br />WHERE DUE TO THE BUILDINGS CONSTRUCTION, IT IS NOT POSSIBLE: TO ROUTE <br />RACEWAYS & CABLES CONCEALED; RACEWAYS MAY BE RUN EXPOSED. (EXPOSED <br />CABLES ARE NOT ALLOWED EXCEPT IN TELECOMMUNICATIONS ROOMS.) EXPOSED <br />RACEWAYS SHALL BE RUN AS NEATLY & UNOBTRUSIVELY AS POSSIBLE, SUPPORTED <br />AS REQUIRED, PARALLEL OR AT RIGHT ANGLES TO CEILINGS, WALLS & STRUCTURAL <br />MEMBERS. <br />T RACEWAYS SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE: <br />A. INTERIOR ACCESSIBLE CONCEALED SPACES- ELECTRICAL METALLIC TUBING <br />(EMT) WITH FLEXIBLE METAL CONDUIT (FLEX) FOR FINIAL CONNECTIONS TO <br />VIBRATING EQUIPMENT. <br />B. INTERIOR NON -ACCESSIBLE CONCEALED SPACES - FLEXIBLE METAL CONDUIT <br />(FLEX) MAY BE "FISHED" FROM ONE POINT OF CONNECTION TO ANOTHER. <br />FLEX SHALL NOT BE USED FOR HOME RUNS. <br />C. INTERIOR., EXPOSED IN TELECOM ROOMS, UTILITY ROOMS & 01-HER NON-PUBLIC <br />SPACES - ELECTRICAL METALLIC TUBING (EMT). <br />D. EXTERIOR ABOVE GRADE - GALVANIZED RIGID STEEL CONDUIT (GRS). <br />E. EXTERIOR BELOW GRADE - POLYVINYL CHLORIDE CONDUIT (PVC), EXCEPT <br />CONDUIT ELBOWS FOR SIZE 2 INCH AND LARGER SHALL BE TYPE <br />RTRC (FIBERGLASS). <br />8. RACEWAYS SHALL BE SITED SO THAT THE CABLE FILL DOES NOT EXCEED 40%, <br />EXCEPT, MINIMUM CONDUIT SIZES SHALL BE AS FOLLOWS, UNLESS NOTED <br />OTHERWISE: <br />A. 3/4" -BRANCH CIRCUITS AND SYSTEM RACEWAYS, EXCEPT AS NOTED BELOW- <br />B. V -TELECOMMUNICATIONS RACEWAYS TERMINATING IN A SINGLE DEVICE. <br />C_ 1 1/4 TELECOMMUNICATIONS RACEWAYS SERVING TWO DEVICE LOCATIONS <br />9. DEVICE. BOX SIZES SHALL BE SIZED IN ACCORDANCE WITH NEC FOR BOX FILL, EXCEPT <br />MINIMUM SHALL BE AS FOLLOWS, UNLESS SPECIFICALLY NOTED OTHERWISE: <br />A. POWER & LIGHTING - 4" x 4" x 1 1/2" <br />B. TELECOM MUNICATIONS - 4 11/16" x 4 11/16" x 2 1/8" <br />C. FIRE ALARM, ACCESS CONTROL, SECURITY, PAGING, ANCILLARY, ETC. <br />SYSTEMS SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS <br />REQUIREMENTS. <br />10. DEVICE MOUNTING HEIGHTS SHALL BE AS FOLLOWS, UNLESS SPECIFICALLY NOTED <br />OTHERWISE. MOUNTING HEIGHTS SHOWN ON THE DRAWINGS ARE TO THE CENTER <br />OF THE BACK BOX FROM THE INTERIOR FINISHED FLOOR. <br />A. POWER, TELECOMMUNICATIONS, AUDIO/VIDEO, ETC. RECEPTACLES - 18" <br />B. LIGHTING SWITCHES, CONTROL STATIONS, ETC. - 46" <br />C. DEVICES ABOVE COUNTERS - 4" ABOVE BACKSPLASH. <br />D. FIRE ALARM PULL STATIONS - 46" <br />E. FIRE ALARM NOTIFICATION APPLIANCES - 80" <br />F. EXIT & EMERGENCY LIGHTS - 150" <br />11. TELECOMMUNICATIONS CONDUITS SHALL BE PROVIDED WITH PULL ROPES BELOW <br />GRADE AND PULL STRINGS ABOVE GRADE. EXISTING CONDUITS TO BE USED SMALL <br />BE FISHED AND CLEANED PRIOR TO INSTALLATION OF CABLES. <br />12. BELOW GRADE SERVICE & FEEDER CABLE SMALL BE I/C COPPER (UNLESS <br />SPECIFICALLY NOTED OTHERWISE) WITH 600V TYPE USE/RI- H/RHW OR <br />XHHW INSULATION. <br />13, BRANCH CIRCUIT CABLES, EQUIPMENT GROUND CABLES AND ABOVE GRADE <br />FEEDER CABLES SHALL BE 1/C COPPER, #12 ,'AWG UNLESS NOTED OTHERWISE, <br />WITH 600V TYPE XHHW OR THHN/THWN INSULATION. <br />14. IN ADDITION TO THE CIRCUIT CONDUCTORS INDICATED, CONTRACTOR SHALL PROVIDE <br />AN EQUIPMENT GROUND CABLE (SIZED THE SAME AS THE LARGEST CIRCUIT <br />CONDUCTOR UNLESS SPECIFICALLY NOTED OTHERWISE) WITHIN EACH RACEWAY <br />WITH THE CIRCUIT CONDUCTORS. <br />15. SCE ELECTRICAL SPECIFICATION FOR SYSTEMS CABLE TYPES. <br />16. ALL WIRING SHALL BE ENCLOSED WITHIN THE RACEWAY SYSTEM. <br />17. VERIFY ALL EQUIPMENT, DEVICE, ETC. LOCATIONS WITH TIME ARCHITECT PRIOR TO <br />ROUGH -IN. SEE MECHANICAL DRAWINGS FOR LOCATION OF MECHANICAL <br />EQUIPMENT, ARCHITECTURAL DRAWINGS FOR SPECIALTY EQUIPMENT, CASEWORK, <br />ETC. THE OWNER RESERVES THE RIGHT TO RELOCATE OUTLETS, ETC. WITHIN IY OF <br />THE LOCATION INDICATED, PRIOR TO INSTALLATION, WITHOUT INCREASE IN COST. <br />18. CONTRACTOR SHALL VERIFY WITH THE ARCHITECT THE MOUNTING HEIGHT FOR <br />ALL WALL MOUNTED AND PENDANT MOUNTED LIGHTING FIXTURES PRIOR TO <br />ROUGH -IN. <br />19. SEE ARCHITECTURAL SPEC. SECTIONS (E.G. DOOR HARDWARE, APPLIANCES, DOORS, <br />ETC.), ENTIRE DIVISION 11 - EQUIPMENT, & ENTIRE DIVISION 22 - PLUMBING, <br />DIVISION 23 - HVAC FOR ADDITIONAL REQUIREMENTS, FURTHER CLARIFICATIONS, <br />ETC. OF EQUIPMENT ELECTRICAL REQUIREMENTS. <br />20. CONTRACTOR SHALL VERIFY WITH THE ARCHITECT THE FIRE RESISTIVE RATINGS <br />FOR WALLS, PARTITIONS AND OTHER BUILDING STRUCTURES. INSTALLATION OF <br />SYSTEM COMPONENTS AND RACEWAYS MUST MAINTAIN THE FIRE RESISTIVE <br />RATING OF THE BUILDING. <br />21 e SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3 FEET OF ANY AIR SUPPLY <br />VENT REGARDLESS OF THE LOCATION INDICATED ON THE DRAWINGS. <br />22. FIRE ALARM & SECURITY WIRING SHALL RUN FROM DEVICE TO DEVICE WITHOUT <br />SPLICES OR TAPS. AT EACH BOX., THE INCGMMING PAIR OF THE INTELLIGENT LOOP <br />CONDUCTORS SHALL BE IDENTIFIED WITH A SINGLE WRAP OF RED COLORED <br />ELECTRICAL TAPE. "T" TAPS SHALL NOT BE INSTALLED WITHOUT SPECIFIC APPROVAL <br />FROM THE ENGINEER. <br />23. LABELING & NAMEPLATES: <br />A. OUTLETS SHALL BE LABELED WITH THE PANEL AND CIRCUIT NUMBER FROM <br />WHICH ITS FED. LABELS SHALL BE HEAVY DUTY ADHESIVE TYPE, CLEAR <br />TAPE WITH BLACK LETTERING, MADE WITH A I-ABEL PRINTING DEVICE. <br />B. JUNCTION BOXES SHALL BE LABELED WITH THE PANEL AND CIRCUIT NUMBER. <br />CONTAINED WITHIN. MARKING SHALL BE LEGIBLY HAND-WRITTEN WITH BLACK <br />INDELIBLE MARKER. <br />C. REFER TO SPECIFICATIONS FOR PANELS, DISCONNECT SWITCHES, STARTERS, <br />ETC. NAMEPLATES AND LABELING. <br />DEMOLITION NOTES (APPLICABLE TO ALLELECTRICAL DRAWINGS): <br />1. CONTRACTOR SHALL REMOVE ALL EXISTING EQUIPMENT, DEVICES, ETC. WHERE <br />INDICATED. EXISTING DEVICES NOT SHOWN ON THE DRAWINGS SHALL REMAIN. ALL <br />ASSOCIATED CONDUIT, BOXES, CABLES, ETC. SHALL BE REMOVED TO THEIR POINT <br />OF ORIGIN &/OR DESTINATION; EXCEPT, CONCEALED CONDUITS MAY BE LABELED & <br />ABANDONED IN PLACE. <br />2. EXISTING EQUIPMENT, FIXTURES, DEVICES, ETC. TO BE RE -USED IN THE NEW WORD <br />SHALL BE REMOVED CAREFULLY, & PROTECTED FROM DAMAGE AS REQUIRED <br />DURING DEMOLITION & CONSTRUCTION. <br />3. EXISTING EQUIPMENT, FIXTURES, DEVICES, ETC. TO REMAIN SHALL BE PROTECTED <br />AS REQUIRED DURING DEMOLITION AND CONSTRUCTION. <br />4. ALL SURPLUS MATERIAL REMOVED DURING THE DEMOLITION( SMALL BE INSPECTED <br />BY THE OWNER, AND THOSE ITEMS SELECTED SHALL REMAIN _PdE PROPERTY OF <br />THE OWNER. ALL REMAINING SURPLUS MATERIALS SHALL BE REMOVED FROM THE <br />SITE & DISPOSED OF BY THE CONTRACTOR. <br />ELECTRICAL L <br />LIGHTING MILLNE <br />LED LUMINAIRE, SURFACE MTD, <br />(Aa - FIXTURE TYPE A CONTROLLED <br />BRANCH CIRCUIT, ABOVE GRADE, CONCEALED (OR SIMILAR, <br />5LA5HE5 -- NO. OF CIRCUIT CONDUCTORS WHERE APPLICABLE) <br />BY SWITCH $a, TYPICAL. NL e NIGHTLIGHT) <br />HOMERUN TO LOCATION INDICATED, CONCEALED (TYPICAL) <br />1=� <br />LED LUMINAIRE, SURFACE MTD. <br />HONERUN TO LOCATION INDICATED, EXPOSED (TYPICAL) <br />LED LUMINAIRE, WALL MTD <br />EMERGENCY LIGHTING UNIT, WALL MTD <br />o 0 0 — e -n e — <br />BELOW GRADE CONDUIT <br />LIGHTED EXIT SIGN <br />�`" m a <br />BELOW FLOOR CONDUIT <br />FLOODLIGHT, POLE MTD. <br />m ®� <br />GROUND CABLE <br />000e�°a= v <br />CABLE PUN 'OPEN' IN ACCE551BLE CEILING SPACE <br />® <br />(5LA5HE5 - No. 4 TYPE OF CABLES WHERE APPLICABLE) <br />EXISTING TO REMAIN <br />WITCHING- <br />---- <br />EX15TING TO DE REMOVED <br />wp <br />WEATHER PROOF <br />S <br />SINGLE -POLE SWITCH <br />EX <br />EXISTING TO REMAIN <br />53 <br />THREE-WAY SWITCH <br />REX <br />REPLACE EXISTING WITH NEW <br />Sad <br />TWO POLE SWITCH <br />63F <br />THREE -POLE SWITCH <br />REL <br />RELOCATE EXISTING <br />5M5 <br />MOTION 5EN60R SWITCH <br />C.®. <br />CONDUIT ONLY <br />(SEE SPECIFICATIONS FOR TYPE) <br />PANELDOARD, SURFACE MOUNTED <br />624T <br />TIMER SWITCH WITH 24 HOUR TIME CLOCK <br />PANELBOAPD, FLUSH MOUNTED <br />(SEE SPECIFICATIONS FOR TYPE) <br />5m <br />177:� <br />DISCONNECT SWITCH <br />MOTOR RATED SWITCH <br />sr) <br />LOW VOLTAGE, 0-10 VOLT DIMMER SWITCH <br />$m <br />LOW VOLTAGE, MANUAL -ON MASTER 5WITCH <br />© <br />DAYLIGHTING PHOTOCELL <br />ANCILLARIES <br />(a) <br />LIGHTING MOTION DETECTOR, CEILING MTD, <br />FIRE ALARM MANUAL PULL STATION <br />m <br />MOTION/DAYLIGHT SEN50R POWER SUPPLY <br />15cd <br />FIRE ALARM HORN WITH STRODE LIGHT <br />lbc:d UNLE55 OTHERW15E NOTED <br />QUILET5 <br />FIRE ALARM MANUAL PULL STATION <br />WITH 5PEAKER/6TRODE ABOVE <br />DUPLEX OUTLET <br />FIRE ALARM STROBE LIGHT <br />DUPLEX OUTLET, CEILING MTD. <br />EOL <br />END OF LINE RE515TOR <br />DUPLEX OUTLET, SPLIT WIRED <br />FIRE ALARM SMOKE DETECTOR <br />DOUBLE DUPLEX OUTLET, WITH ONE CONTROLLED OUTLET <br />FIRE ALARM PATE OF RISE DETECTOR <br />FLOOR BOX DOUBLE DUPLEX OUTLET, <br />FIRE ALARM HEAT DETECTOR <br />WITH ONE CONTROLLED OUTLET <br />SECURITY SYSTEM KEY PAD <br />2C <br />TELECOMMUNICATIONS OUTLET, FLUSH MOUNTED <br />W <br />(aC e 2 CATOA CABLES, TYPICAL) <br />SECURITY CAMERA (CEILING MTD) 2-WAY <br />(W - WALL PHONE TYPE OUTLET) <br />FLOOR E30X TELECOMMUNICATIONS OUTLET <br />- <br />SECURITY CAMERA (WALL MTD) <br />TELECOMMUNICATIONS WIRELE55 <br />SECURITY CAMERA (WALL MTD), WEATHERPROOF <br />wp <br />ACCE65 POINT OUTLET <br />SECURITY 5Y6TEM MOTION DETECTOR, CEILING MTD, <br />SECURITY SYSTEM DOOR CONTACT <br />LINE VOLTAGE THERMOSTAT <br />LOW VOLTAGE CABLE CODES <br />CODE <br />FUNCTION <br />DESCRIPTION <br />COLOR <br />NE'C TYPE <br />CABLE aOUTING <br />CNN <br />DATA SYSTEM HORL70NTAL CABLE <br />CAT6A FOILEDIUNSHIELDED TWISTED PAIRS (FIUTP) <br />BLUEJACKET <br />CMR <br />RACEWAY <br />H <br />F.A. SYSTEM NOTIFICATION (HORN/STROBE) CIRCUIT <br />1 - 2/C 914 AWG <br />RED JACKET <br />FPLR <br />RACEWAY <br />Z <br />F.A. SYSTEM ADDRESSABLE DEVICE LOOP <br />1 - 2/C #16 AWG <br />RED JACKET <br />FPLR <br />RACEWAY <br />L <br />LIGHTING PHOTO & MOTION CONTROL CIRCUIT <br />VARIES, PER MANUFACTURERS REQUIREMENTS <br />YELLOW JACKET <br />CL2R OR CMR <br />RACEWAY <br />LID <br />LIGHTING 6-10V DIMMING CONTROL CIRCUIT <br />VARIES, PER MANUFACTURERS REQUIREMENTS <br />YELLOW JACKET <br />CL2R OR CNIR <br />RACEWAY <br />SR <br />SECURITY SYSTEM KEYPAD & CARDREADER <br />1 - 6/C # 18 AWG SHIELDED <br />BLACK JACKET <br />CL2R OR CMR <br />RACEWAY <br />SM <br />SECURITY SYSTEM MOTION DETECTOR CIRCUIT <br />1 -6/C # 16 AWG SHIELDED <br />WHITE JACKET <br />Cl OR CMR <br />RACEWAY <br />SDC <br />SECURI I Y SYSTEM DOOR CONTACT MONITORING CIRCUfT <br />1 -21C # 22 AWG SHIELDED <br />WHITE JACKET <br />CL2R OR CMR <br />RACEWAY <br />SV <br />ISECURITY CAMERA VIDEO CIRCUIT <br />CAT6A FOILED/UNSHIELDED TWISTED PAIRS (F/UTP) <br />BLACK JACKET <br />CATVR <br />RACEWAY <br />NOTES: <br />1. ALL CABLING SHALL BE IN RACEWAYS. <br />2. CONFIRM CABLE TYPES WITH TELECOM, FIRE ALARM, SECURITY, AND LIGHTING CONTROLS SYSTEM PROVIDERS PRIOR TO INSTALLATION. <br />LO <br />00 <br />m <br />uj <br />v3 <br />yj� <br />E <br />® a <br />? <br />M <br />�1 <br />LL <br />-,E <br />5 <br />( co <br />- <br />C) <br />CC' 0- . <br />z <br />r, <br />V4 to <br />woo <br />go 0 <br />a) <br />cf) <br />IT - <br />a) <br />0 <br />Q) <br />> <br />(D <br />a <br />0. <br />Job No: 1705.30 Date: 2017-8-23 <br />File No: <br />Drawn By: KL <br />Checked By: STV <br />Issued for: BID <br />ELECTRICAL I - <br />NOTES, <br />