Laserfiche WebLink
• <br /> James Bronder <br /> From: James Bronder <br /> Sent: Monday, February 14, 2022 2:14 PM <br /> To: permits@preciseheatandcool.com <br /> Subject: Correction Notice M2202-002 <br /> Permits, <br /> The following comments have been issued after review of the permit application. Please respond to and address the <br /> following comments and revise drawings as required: <br /> 1. On Sheet M101.00, please verify that the total weight of the RTUs are provided as it appears that the proposed <br /> weight may not include the weight of the roof curb adapter and economizer installation. Currently as shown, <br /> the proposed weight appears to exceed the design roof loading for the proposed area mechanical unit <br /> area. Please verify via stamped design calculations such that the existing roof framing is adequate or if not <br /> adequate, please provide stamped roof strengthening drawings and calculations as required. IEBC 806.2. <br /> 2. Drawings are indicated as"For Reference Only—Not For Construction." Please submit a final construction <br /> drawing for the proposed work. Please revise drawings as required. <br /> Thank you, <br /> James Bronder, P.E.,S.E. <br /> Illm <br /> 1111 Associate Engineer—Plans Examiner I Permit Services <br /> 425.257.8810 13200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> EVERETT Phone Hours: M/W/Th: 8 a.m.—12 p.m & 1 p.m.—3 p.m. <br /> everettwa.gov/permits I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> 1 <br />