Laserfiche WebLink
• <br /> 2015 Washington State EtTer Code Compliance <br /> 9Y p ce Forms for Commercial,R2 and R3 over 3 stories and all R1-Page 5 of 7 <br /> Mechanical Permit Plans Checklist MECH-CHK <br /> 2015 Washington State Energy Code Compliance Forms for Commercial Buildings Including R2&R3 over 3 stories and all R1 Revised January 2017 <br /> Project Title: 2732 Grand Ave Date 4/27/2020 <br /> The following information Is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the <br /> Washington State Energy Code,Commercial Provisions. <br /> Applicable Code Section Code ProvisionLocation in Building Department <br /> (yes,no,na) Information Required-Must be in permit documents <br /> Documents Notes <br /> For buildings with food service,meat or deli departments that have 2 500,000 Btulh of remote <br /> refrigeration capacity for coolers/freezers,indicate condenser ER and use of captured energy <br /> (service water heating,space heating,or dehumidification reheating) <br /> C403.5.3 Energy recovery- <br /> cooler/freezer condensers For buildings with z 40,000 sf conditioned floor area and with z 1,000,000 Btulh of remote <br /> refrigeration capacity for coolers/freezers,indicate condenser ER and use of captured energy <br /> for service water heating and also for space heating,or dehumidification reheating <br /> For buildings with 24-hour operation and with>1,500,000 Btulh of heat rejection capacity and <br /> C403.5.4 Energy recovery- design service hot water load>250,000 Bluth,indicate condenser ER to pre-heat service <br /> condenser systems water;or exception taken.Provide calculations showing the amount of recovered heat that is <br /> utilized(60%of peak heat reiectlon load or pre-heat service water to 85°F). <br /> Hydronic System Controls <br /> For hydronic system pump motors z 7.5 hp,Indicate method of variable flow control(VSD or <br /> C403,2.13 Variable flow control- equivalent method that requires z 30%design wattage at 50%design fluid flow);note <br /> C403.4.2.7 hydronic system pumps exception taken <br /> Identify whether hydronic coils have DDC controls and associated manner of pump speed <br /> control(differential pressure,zone hydronic demand,etc) <br /> For boilers that provide building heating,Indicate controls that provide heating water <br /> temperature setback based on outdoor temperature <br /> For heating and chilled water systems 300,000 Btu/h,indicate systems are configured to <br /> C403.2.5 Hydronic system setback automatically reset supply water temperature based upon demand;or exception taken. <br /> C403.4.2.4 and part load controls If system pump motor hp 2 3 hp,also indicate controls automatically reduce flow by z 50%. <br /> For chilled water systems(a 300,000 Btu/h,pump motor hp a 3 hp)that serve water-cooled <br /> unitary air conditioners,indicate VSD or staged pumps in chilled water system and heat <br /> rejection loop that reduce pump flow so that one control valve is nearly wide open,or to <br /> maintain a minimum differential pressure;or exception taken <br /> C403.4.2 Boiler sequencing Indicate automatic controls that sequence operation of multiple boilers <br /> C403.4.6 Hot gas bypass limitation For cooling equipment with hot gas bypass,provide either multiple step unloading or <br /> continuous capacity modulation;Indicate bypass capacity per Table C403.4.6 <br /> C403.4.2.2 Two-pipe changeover Indicate changeover deadband(min 15°F),heating/cooling mode scheduling and <br /> systems changeover temperature range(limit 30°F) <br /> C403.4.2.6 Chiller/boiler plant pump Indicate controls are configured to automatically reduce overall plant flow and shut-off flow <br /> isolation through individual chillers and boilers when not in use <br /> For cooling towers with fan motors 2 7.5 hp,indicate VSD and method to adjust fan speed <br /> C403.2.13.1.1 Heat rejection equipment- (adjusted based on leaving fluid temperature or condenser temperature/pressure of heat <br /> C403.4.3.1.1 variable flow control rejection device) <br /> C403.4.3.1.2 For multiple-cell heat rejection equipment with VSD,indicate controls that ramp all fans in <br /> unison <br /> C403.4.3.3 Heat rejection equipment- Indicate open-circuit cooling towers with multiple pumps or VSD control are designed so all <br /> cooling tower flow turndown cells can be run in parallel <br /> C403.4.2.3.1 Water loop heat pump- Indicate capability of central equipment to provide minimum 20°F water supply temperature <br /> deadband deadband between heat rejection and heat addition modes;or exception taken <br /> Water loop heat pump Indicate type of cooling tower(open-or closed-circuit) equipment schedule;Indicate method <br /> C403.4.2.3.2.1 heat rejection equipment, In q ui P <br /> Zone 4 used to limit system heat loss when heat rejection Is not needed <br /> Water loop heat pump- For open-or closed-circuit cooling towers,provide a heat exchanger that separates the cooling <br /> C403.4.2.3.2.2 heat rejection equipment, tower and heat pump loop <br /> Zone 5 <br /> C403.4.2.3.3 Water loop heat pump- For hydronic heal pump systems with total system power>10 hp,indicate 2-way isolation <br /> Isolation valves valves on each heat pump and variable flow system control <br /> Dedicated Outdoor Air Systems(DOAS)-Optional through 6/30/16,Prescriptive 7/1/2016 <br /> For buildings with office,retail,education,library and fire station spaces,identify these spaces <br /> C403.6 Dedicated outdoor air on plans;indicate that ventilation air In each occupied space is provided via a DOAS system; <br /> C403.6.3 systems or document compliance with C403.6.3 Impracticality;or exception taken(buildings complying <br /> with C402.4.1.4 or C406.6 may not utilize exceptions) <br /> Energy recovery ventilation For all DOAS systems,indicate exhaust air ER method;or exception taken with supporting <br /> C403.6.1 with DOAS calculations.Indicate ER rated effectiveness that Increases OSA enthalpy by Z 50%based on <br /> delta between OSA and return air enthalpies at design conditions. <br /> Indicate equipment associated with the delivery of zone level heating and cooling(fans, <br /> Heating/cooling system hydronic pumps,primary air dampers,etc)are configured to shut off,and central equipment Is <br /> C403.6.2 controls with DOAS configured to turn down,when there is no call for heating or cooling in the zone they serve <br /> If applying Exception to heating/cooling fans used for air mixing in the space during deadband <br /> periods,Include fan watts per cfm in equipment schedule <br />