12/20/2021 City of Everett Page 1 /3 <br /> 8:46:13AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E2102-139 Site Address 2902 RUCKER AVE <br /> Applied 2/19/2021 Applicant AUDIO VIDEO SECURITY SYS INC Lot <br /> Approved 2/22/2021 Owner DMT Rucker LLC Block <br /> Issued 3/5/2021 Contractor AUDIO VIDEO SECURITY SYS INC Tract <br /> Parent Permit No. FA2103-002 Description Fire Alarm LOW VOLT <br /> Notes NEED SEPARATE FIRE ALARM PERMIT <br /> Scheduled Completed Tvne Inspector Result Remarks Inspector's Comments <br /> 3/29/2021 3/29/2021 ELEC 08-OTHER TJJO CORRECTION eTRAKiT Inspection 3/26/2021 10:10 AM AUDIO VIDEO <br /> Request SECURITY SYS INC <br /> Requesting final onlst floor for Fast Signs <br /> Contact Name:Rodney j rieger <br /> Site Address:5112 77th Place NE <br /> Phone:4253198032 <br /> e-Mail:ayss.net@gmail.com <br /> (3/29/2021 3:08 PM TJJO) <br /> 760.130(b)(1)Wire must be protected up to <br /> 7'and splices must be made in listed <br /> fittings,boxes and enclosures <br /> WAC 296-46B 760 boxes must be <br /> substantially red in color inside and out. <br /> (paint boxes that are being worked on in <br /> work package) <br /> 4/14/2021 4/14/2021 ELEC 09-FINAL SKB PARTIAL APPR as noted Fast sign 4/13/2021 8:32 AM AUDIO VIDEO <br /> only SECURITY SYS INC <br /> Fast Signs hallway:Mornings preferred, <br /> Correction for splice not in electrical box in <br /> hallway by men's bathroom <br /> Contact Name:AUDIO VIDEO <br /> SECURITY SYS INC <br /> Site Address:2902 RUCKER AVE <br /> Phone:4253198032 <br /> e-Mail:ayss.net@gmail.com <br /> (4/14/2021 10:56 AM SKB) <br /> Fast Sign suite only. <br /> INSP12 CMS YSTEMS <br />