Laserfiche WebLink
A I B I C I D I E I F I G I H <br /> LOAD CALCS-TOTAL AMPS AVAILABLE MAX AC OPERATING CURRENT CALCS FOR MI-1200 MAX AC OPERATING TOTAL <br /> BUS RATING 120% TOTAL MAIN BREAKER MAX BREAKER SIZE #OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT CURRENT FOR MI-1200,MI-600&MI-300 <br /> 200A X 1.2 = 240 - 200A = 40A 2 X 5.0A = 10.00A MI-1200 MI-600 MI-300 <br /> COMBINER BOX PANEL SIZE CALCS MAX AC OPERATING CURRENT CALCS FOR MI-600 <br /> NUMBER OF NUMBER OF NORMINAL OUTPUT COMBINED <br /> #OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT 10.00A + 5.00A + 1.25A = 16.25A <br /> CIRCpUITT# MODULES MICROINVERTERS CURRENT TOTAL 125% TOTAL TOTAL BREAKER SIZE 2 X 2.5A = 5.00A <br /> CIRCUIT 1(1 of 2) 2 1 X 2.5A 2,5A x 1,25 =,3.125A MAX AC OPERATING CURRENT CALCS FOR MI-300 <br /> 9.375A = 15A #OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT BREAKER SIZE CALCS <br /> CIRCUIT 1(2 of 2) 4 1 X S.OA = 5.0A x 1.25 = 6.25A 1 X 125A = 1,25A MAX AC OPERATING CURRENT 125% TOTAL BREAKER SIZE <br /> . <br /> CIRCUIT 2(1 of 3) 1 1 X 1.25A = 1.25A r 1 25 = 1 56A 16.25A X 1.25 = 20.31A = 25A <br /> CIRCUIT 2(2 of 3) 2 1 X 2.5A = 2.5A x 1.25 = 3.125A = 10.935A = 15A <br /> CIRCUIT 2(3 of 3) 4 1 X 5.OA = 5,OA x 1.25 = 6.25A <br /> NOTES: <br /> 1. 200A UTILITY METER AND 200 AMP MAIN SERVICE PANEL <br /> (EXISTING) <br /> 2. 60A RATED FUSED AC DISCONNECT WITH(2)----A FUSES. — <br /> (NEW) <br /> 3. PRODUCTION METER.(NEW) <br /> 4. 125A RATED COMBINER PANEL.(NEW) <br /> (V N <br /> 0 <br /> - 0 - <br /> CIRCUIT#1 (1 of 2)-2 ZSHINE CIRCUIT#1 (2 of 2)-4 ZSHINE MAIN SERVICE PANEL(E) <br /> ZXM6-60-320W MODULES ZXM6-60-320W MODULES (2)8 AWG <br /> WITH HOYMILES MI-600 MICRO WITH HOYMILES MI-1200 MICRO (1)8AWG EGC UTILITY METER(E) <br /> INVERTERS INVERTERS <br /> C 0( <br /> (2)8 AWG <br /> M (21 1 1, (41 f 31 (21 0x � © (1)8 AWG EGC4:0 • MAIN SERVICE <br /> DISCONNECT(E) <br /> (2)12 AWG • <br /> (1)8 AWG EGC • <br /> e Q <br /> T T <br /> eil • <br /> • • <br /> ---) 1-7 <br /> HxH ti <br /> CIRCUIT#2(1 of 3)-1 ZSHINE CIRCUIT#2(2 of 3)-2 ZSHINE CIRCUIT#2(3 of 3)-4 ZSHINE —I <br /> ZXM6-60-320W MODULES ZXM6-60-320W MODULES ZXM6-60-320W MODULES <br /> WITH HOYMILES MI-300 MICRO WITH HOYMILES MI-600 MICRO WITH HOYMILES MI-1200MICRO <br /> INVERTERS INVERTERS INVERTERS <br /> 1 <br /> (2)8 AWG <br /> (1)8 AWG EGC <br /> 11 (2 (1 (4. 31 (21 (11 25A LOAD-SIDE -I, <br /> ✓ ✓ ✓ —� ✓ SOLAR OCPD <br /> (Opposite end of the main disconnect <br /> (2)12 AWG on the busbar-NEC 705.12(B)(2)(3)(b) <br /> (1)8 AWG EGC <br /> —� _� / '� <br /> Lo Cn <br /> DRAWN BY: DRAWING SCALE: <br /> CONFIDENTIAL-THE INFORMATION CONTAINED KAM NOT TO SCALE <br /> IN THIS PACKET AND SUBSEQUENT CUTSHEETS Linda Adams DATE DESIGN <br /> SSHALL NOT BE USED FOR THE BENEFIT OF SOLGEN POWER <br /> OLGcANYONE OUTSIDE SOLGEN POWER, NEITHER 5100 ELM RD, 9I1/2020 <br /> SHALL IT BE DISCLOSED TO OTHERS OUTSIDE PASCO,WA 99301 <br /> THE RECIPIENTS ORGANIZATION, EXCEPT IN 1 <br /> POWER CONNECTION WITH THE SALE AND USE OF THE P: 509-931-1663 1306 10th St . Everett WA 98201 <br /> , , PAGE# 3 <br /> RESPECTIVE EQUIPMENT,WITHOUT WRITTEN PV3s <br /> CONSENT FROM SOLGEN POWER. <br />