Laserfiche WebLink
s. <br /> b. The"I-4"occupancy should indude all spaces that are directly provided as part of or to serve this occupancy. For <br /> example,the Reception,Gentle Care, Multi-Purpose,Activity,and Exam rooms appear to constitute this occupancy. <br /> Other spaces should be included unless shown to not be part of this occupancy. <br /> RESPONSE: See our response to question #7 <br /> REFERENCE: A101-P <br /> 9. Opening protectives(e.g.,doors,etc.)should be identified on the plans. The minimum required fire ratings should be <br /> specified per IBC Table 716.1(2). Note that the plans do not appear to include a door schedule as stated in the Floor Plan <br /> Legend on Sheet A102-P. See IBC Section 107.2.1. <br /> RESPONSE: Since there are no rated doors now, this doesn't apply. <br /> REFERENCE: N/A <br /> 10. Multiple doors in the Floor Plan on Sheet A102-P should specify minimum 18-inch clearances for accessibility,including <br /> but not limited to Doors 214,218A,and 200. See IBC Section 1101.2 and ICC A117.1-09 Figure 404.2.3.2. <br /> RESPONSE: See update plan highlighting doors to be accessibly as per our ADA sheet G101-P. <br /> REFERENCE: A152-P, A102-P <br /> Should you require any additional information regarding this matter, please contact me at 206.962.6459 <br /> Thank you. <br /> Sincerely, <br /> John R. Leuck <br /> Project Manager, Associate <br /> jrl <br /> c: MG2 Corporation <br /> 6—,age 3 of 3 ) <br />