1 U 2 <br />118-206 - ACCESSIBLE ROUTES <br />1 A. At least one accessible route shall be provided within the site from accessible parking spaces and <br />accessible passenter loading zones; public streets and sidewalks; and public transportation stops to <br />the accessible building or facility entrance they serve. <br />DIVISION 3 - BUILDING BLOCKS <br />A. Carpet or carpet tiles provided on a floor surface shall be securely attached; be firm, have a level <br />loop, textured loop, level cut pile, or level cut/uncut pile texture. Maximum pile height shall be 1/2". Exposed <br />edges of carpet shall be fastened to floor surfaces and have trim along the exposed edges. <br />A. <br />Openings in floor or around surfaces shall now allow passage of a sphere more than 1/2" diameter. <br />B. Elongated opening shall be placed so that the long dimension is perpendicular ot the dominant direction of travel. <br />11 B-303.2 - VERTICAL (REFERENCE FIGURE I I B-303.2 as shown on 'this sheet) <br />AChanges in level Lip to 1/4" maximum may be vertical and without edge treatment <br />I 1 B-303.3 - BEVELED (REFERENCE FIGURE 1 1 B-303.3 as shown on this sheet) <br />B. Changes in level between, 1/4" high minimum and 1/2" maximum shall be beveled with a slope no greater than 1:2 (50%) <br />THIS LIST IS NOT ALL INCLUSlVE. FOR CONMTIONS NOT COVERED, CONTACT THE ARCH, ITECT. <br />�E <br />� <br />_F____1_1 rr_____�, <br />VERTICAL CHANGE |NLEVEL BEVELED CHANGE |NLEVEL <br />8B-3O4-TURNING SPACE <br />A. The space required tomake mwheelchair turn tomake a188°turn is 60"diameter tua"T-shapad"space. <br />118-305-CLEAR FLOOR GROUND SPACE <br />A. Minimum clear floor space for a wheelchair and occupant shall be 30" wide )(48" long. Clear floor space <br />may be positioned for forward or paralled approach. Clear floor space shall be centered on the element It serves. <br />B. One full unobstructed side of the clear floor space adjoins or overlaps an accessible route or adjoins <br />another wheelchair clear floor surface. <br />11B-30TPROTRUDING OBJECTS <br />_ <br />11B-3071'GENERAL <br />A. Objects projecting from walls (for example, telephones) with their leading edges between 27" - 80" above <br />the finished floor shall protrude no more than 4" maximum horizontally into the circulation path. <br />B. Free-standing objects mounted on posts or pylons may overhang 1 2" maximum when located 27" minimum <br />and 8Q" maximum above the ground nrfinished floor. <br />| | JL~-4'MAX. M}N� <br />_�N� �_ N1 - , <br />\ L !'l <br />- A. Vertical clearance shall be 80" high minimum roorn. <br />DIVISION 4 - ACCESSIBLE ROUTES <br />A. The minimum clear width for single wheelchair passage shall be 32" at a point and 36" continuously. <br />A. Walkways maintain a minimum 48" width. <br />B. Walkways less than 60" wide shall have a minimum 60" x 60" landing not to exceed every 200 ft. <br />A. The minimum clear width for two wheelchairs to pass is 60". <br />A. Cross slope shall not exceet 1:48. <br />A. Running slope shall not exceet 1:20 (5%). (If slope exceets 1:20 (5%), refer to section I I B-405 RAMPS). <br />118-404.2.2 DOUBLE -LEAF DOORS AND GATES <br />A. At least one of the active leaves of doorways with two leaves shall comply with sections I I B-404.2.3 and <br />A. Door openings shall provide a cleair width of 32" minimum, with the door open 90*. <br />1Clear openings shall be measured between the face of the door and opposite stop. <br />2Openings more than 24" in depth shall provide a clear opening of 36" minimum. <br />Exception: Doors �ot requiring full user passage, such as shallow closets, may have a clear opening of 20" <br />�� <br />� <br />Provide level (1:50 (5%) max. slope) and clear maneuvering area at doors as follows: <br />C� B. Front approach push side - 48" m inimum length & 0" beside strike edge (I 2" at strike if door has both a closer <br />(a C. Hinge side approach pull side - 60" minimum width; 36" minimum beside strike edge. <br />0) D. Hinge side approach push side - 44" minimum width & 22" minimum beside hinge edge (48" minimum width if <br />_J door has both a closer and a latch.) <br />n - - - 60" minimum width and 24" minimum beside strike edge (54" minimum width if <br />0 E. Latch side appraoch pull side <br />M door has a closer). <br />0- F. Latch side approach push side - 44" minimum width and 24" minimum beside strike edge (48" minimum width if <br />a) door has a closer). <br />C. <br />.5 AThe height of the threshold shall be at a maximum of 1/2" above the floor/landing. <br />L_ B. Change in level between 1/4" and 1/2" shall be beveled with a slope no greater than 1:2 (50%) slope. <br />0- Note: The threshold shall have vertical edges no greater than 1/4". <br />N A. Front approach pull side - 60" minimum length & 18" minimum beside strike edge 24" at exterior doors. <br />�_ <br />�� <br />' <br />Ir_ A. The maximum force for pushing or pulling open a door shall be as follows: <br />CD 1 . Fire doors shall have the minimum opening force allowable by the appropriate administrative authority, not <br />C) 2. Other doors: <br />a. Exterior hinged doors: 5 lbs maximum <br />I b. Interior hinged doors: 5 lbs maximum <br />T_ <br />C) c. Sliding or folding doors: 5 lbs maximum <br />n <br />T_ <br />"O A. if a door has a closer, then the sweep period of the closer shall be adjusted so that from an open position of <br />0 90', the time required to move the door to a position of 12' from the latch is 5 seconds, <br />�L A. Handles, pulls, latches, looks, and other operating devices shall have a shape that is easy to grasp with one <br />0 hand and does no' require tight grasping, tich pinching, or twisting of the wrist to operate. <br />C B. Hardware required for accessible door passage shall be centered between 34" minimum and 44" maximum <br />W above finish floor. <br />.5 C. Lever -operated mechanisms and push-pull activating -type mechanisms are acceptable designs. <br />�1 A. Swinging door and gate surfaces within 1 0" of the finish floor or ground measured vertically shall have a smooth <br />surface on the push side extending the full width of the door or gate. <br />DIVISION 6 - PLUMBING ELEMENTS AND FACiLITIES <br />co I <br />.15E I 11B-602A - SPOUT HEIGHT (REFERENCE FIGURE 118-36 as shown on this sheet) <br />A. Accessible spouts shall be no higher than 36", measured from the floor or ground surface to the spout outlet. <br />B. In addition to the accessible drinking unit, at least one drinking fountain shall be at a standard helght (38" <br />-low" fountain will accommodate both requirements, <br />minimum and 43" maximum above finish floor). A "hi <br />I I B-6022 - CLEARANCES + ALCOVES (REFERENCE FIGURE I 1 B-313 as shown on this sheet) <br />co A. Wall and post -mounted cantilever fountains shall have clear knee space as follows: <br />CL 1. Minimum 27" high (from apron bottom to floor) minimum 30" wide, and i 8"-1 9" deep. <br />CD 2. A clear floor space allowing a forward approach to the unit shall be provided. The minimum clear floor space <br />T_ A. Drinking fountains shall be located within alcoves, wing walls or otherwise positioned not to encroach into <br />0 pedestrian ways. The minimum alcove size shall be 32" wide minimum x 18" deep,minimum. <br />N I 113-211.2 - ACCESSIBLE DRINKING FOUNTAIN REQUIREMENTS <br />(.0 A. Where only one drinking fountain area is provided on a floor, 'there shall be a drinking fountain that is accessible to <br />individuals who use wheelchairs and one that is accessible to those who have difficulty bending or stooping. This can <br />be accommodated by use of "hidow" -fountains. <br />B. Where more than one drinking fountain is provided on a floor, 50% of those provided must be wheelchair <br />__ 1 � 2 <br />DRINKING� FOUNTAIN �'�N HEIGHTS <br />D C E R CE& �� �� <br />18"TO1 - EQu,nvEm/ ��K�N <br />I PERMITTED INO"K&�� ' ' <br />- I ,,--�-� - , - \ I " \ L-_,,,- <br />�-0 �0 i� <br />� <br />�� � <br />/ �� <br />| Q � �|� <br />L-__r\ <br />00 <br />- �~|/ �_ <br />`|.'�' - <br />b <br />� <br />� <br />� <br />| <br />o ._.�:D��& R. �E�� TOE��� <br />u�rTH/ co 0 <br />FREE STANDING HI -LOW <br />�� <br />SIDE ELEVATION (IN PLAN) (IN PLAN) (IN ELEVATION) <br />N) <br />11B-684-WATER CLOSETS AND TOILET CDMPARTME0TS <br />I 113-604.4 - HEIGHT OF WATER CLOSET (REFERENCE FIGURE 100 as shown on this sheet) <br />NOTE: <br />At alcoves deeper than 24" additional 6" maneuvering clearance is required. At "hi -low" type fountains, center the 30" x 48" clear floorspace <br />on the <br />"LOV"fountain fixture. <br />A. The height to the top of the toilet seat shall be 17" minimum - 19" maximum from the finished floor. <br />Note: The dimension is measured from the floor to the top of a 2" maximum high toilet seat. <br />B� Seats shall not hnsprung toreturn toalifted position. <br />1IB-G04.5-GRAB BARS (REFERENCE FGURE1Q8eashown onthis sheet) <br />A. For water closets not located in toilet stalls, the following grab bars shall be provided: <br />1. Side wall: minimum 43"long, 12"minimum from bmckwml|. <br />2. Rear wall: minimum36" long, measured from the center line of water closet to 12" minimum at one end of <br />grab bar and 24",minimum onthe other end ofthe grab bar. <br />Note: The grab bars are measured 33" minimum and 36" maximum above finish floor measured to the top of of the griping surface. <br />11B-GO4.4-FLUSH CONTROLS (REFERENCE FIGURE 1OOaashown onthis sheet) <br />A. Controls shall ba44"maximum above the finish floor. <br />B. Lever controls or flush valves shall be mounted on the wide side of toilet areas. <br />C. The force required toactivate controls shall benogreater than 5|bt <br />D. Controls shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. <br />Note: Controls shall behand operated orautomatic. <br />11B'6O47-TOILET TISSUE DISPENSERS (REFERENCE FIGURE 18Oas shown on this sheet) <br />&� Toilet paper dispensers shall be installed on the side wall, a minimum 19" above the floor to centerline of dispenser. <br />Nkate:Dispensers that control delivery ordonot permit continuous paper flow shall not baused. <br />B. Centerline of dispenser shall be 7" minimum and 9" maximum from the front of the toilet <br />11B-GO4.82.2-DOORS ATWATER CLD8ETCOMPARTME@T(S) <br />A. Toilet stall doors shall have an autornatic-closing device and shall have clear, unobstructed opening width of 32" when located <br />at the end and 34"when located at the side with the door located mtD8°from its closed position. <br />I I B-604�9A - SIZE AND ARRANGEMENT AT TOILET STALLS (REFERENCE FIGURE I 00 as shown on this sheet) <br />A. Toilet stalls may be arranged to provide either a left or a right handed approach. <br />SINGLE ACC8N0DAT0NTOILET FACILITY: <br />FLUSH <br />ACTIVATOR <br />�* 17TO1 ON WIDE 18"M<N <br />�/ _���_- <br />- C111| | / SIDE | <br />TOILET FACILITY MOUNTING AND INSTALLMENT HEIGHTS � <br />5��� <br />�� <br />1� <br />Z, <br />�� <br />RIM --� <br />q�__ <br />�ELONGATED CD <br />�� <br />�L_|+ <br />< 0 <br />�MIN. /9" MAX/ (I <br />ACCESSIBLE WATER CLOSET COMPARTMENT <br />WITHIN A IVIULTIPLE-ACCOMMODATION TOILET <br />FACILITY: <br />FLUSH <br />�7"TD1 <br />�� ACTIVATOR <br />ON <br />~- | | / VNDEG0E <br />m / <br />18"MIN. CUR. <br />3��N <br />TRANSFER SIDE -~�OOTOP OF SEAT 11 <br />2" IVIAX. HIGH SEAT <br />� <br />� <br />"MAX <br />� <br />:2i <br />� ` �� ` <br />� <br />2 � � | | <br />LU <br />� �� i� HOLD <br />� -_ � <br />� �� � <br />M �o - <br />�+ <br />_ <br />FIGURE 100 SHOWS MINIMUM REQUIREMENTS. SEE DETAIL I ON SHEET A307 FOR ENLARGED FLOOR <br />PLAN OF EXISTING PUBLIC RESTROOM CONDITIONS, <br />i1B-213.2-MULTIPLE-ACCOMMODATION TO|LETFAC0]lES <br />A. Ktoilet stalls are provided inatoilet room orbathroom, then atleast one stall shall bea"standard"accessible toilet stall <br />(for wheelchair users) complying with this Section 11B-6O8. <br />B. Provide atleast one ambulatory accessible compartment where six ormore compartments are provided within <br />a multiple -accommodation toilet room, (This is in addition to the accessible water closet.) The provided compartment <br />shall be 36" wide with an outward swinging self -closing door and parallel grab bars complying with Section I I B-604.5. <br />I I B-605.2 - HEIGHT OF ACCESSIBLE URINALS (REFERENCE FIGURE 101 as shown on this sheet.) <br />A. Urinals shall be stall -type or wall hung with a tapered, elongated rim at 17" maximum above the finished floor. The rim shall <br />extend o minimum of 13 1/2"from the wall. <br />1 1113-605.3 - CLEAR FLOOR SPACE + APPROACH (REFERENCE FIGURE 101 as shown on this sheet) <br />A. A clear floor space 30" wide x 48" deep minimum shall be provided in front of urinal to allow forward approach. <br />1. This space shall adjoin oroverlap anaccessible route. <br />2. Urinals installed in alcoves deeper than 24" require a maneuvering area of at least 36" minimum wide, centered onfixture. <br />11B'GD5.4FLUSH CONTROLS (REFERENCE FIGURE 1D1anshown onthis sheet) <br />A. Controls shall be44"maximum above the finished floor. <br />1. Controls shall hehand operated orautomatic. <br />2. Controls shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. <br />3. The force required toactivate controls shall benogreater than 5|bt <br />��11_ <br />m <br />� 4��N <br />UL 1 1 <br />�� | | <br />� <br />� <br />�_- __� �- <br />to | | <br />CLEAR <br />| ������� <br />KVIN, �\�, <br />L�� �� �� <br />PLAN VIEW / / <br />� <br />= <br />" '�� <br />�`����' <br />-`�!� <br />,- <br />.�,_ <br />'' <br />� <br />.:'. <br />..� <br />� �'I <br />`��, <br />/�� <br />',v` � <br />` <br />^ ~�II � <br />` <br />i <br />��`^t� `~-, '-``'/r�"'''} '� <br />'� _�� ��-, ���.���. . `��� �� . <br />'.�' _,�__ ,�_ <br />'�,���' � �'��/���� `�,'.� <br />���`^��.'�������'������.����I �����������ELEVATION <br />HOLD <br />Im <br />11B-6D6-LAVATORYHB8HT+CLEARANOE8(REFERENCEFIGURE118-68Oanohownonthisohaet) <br />A. Lavatories shall bemounted with the rim orcounter surface nohigher than 34" above the finished floor. <br />1. Lavatories shall extend i7"minimum from the wall. <br />1 Clearance of 29" minimum shall be provided from the finished floor to bottom of the apron. <br />3. Kne*c|amnsnoaof27"minimummhe||extendO"minimumundorthefrontofth*|evatory. <br />4. Toe clearance of 9" minimum shall be provided ior the full depth of the lavatory. <br />­��11 \ �K W `_ F - - <br />) I ;, ;2� = <br />-P,//" F = ��I \J :2�_ / / <br />/ 4/_/_ -1 \ / / I <br />I SIDE ELEVATION ���:_if 1�1 , C,-P--, I <br />PLAN VIEW <br />LAVATORY fWRROR MOUNTING HBGHTS AND CLEARANCES <br />11B-6OG.4-FAUCETS <br />A. Controls shall be operable with one hand and shall not require tight grasping, pinching, or twi���v� <br />B. The force required to activate controls shall bono greater than G{bf. <br />C. Acceptable faucet designs include: lever -operated, push -type, and electronically controlled mechanisms. <br />O. If self-cIosing valves are used, the faucet shall remain open for at least I 0 seconds. <br />1IB-8OG.5-EXPOSED PIPES + SURFACES BENEATH LAVATORIES <br />A. Hotwater and drain pipes under lavatories shall be insulated or otherwise configured to protect against contact. <br />B. There shall benosharp orabrasive mudfaces under lavatories. <br />i1B-GOl3'MIRRORS (REFERENCE FIGURE i1B-SUOaoshown onthis sheet) <br />A� Mirrors shall bemounted with the bottom edge ofthe reflecting surface 4O"maximum above the finished floor. <br />11B-6OQ.11-GRAB BARS /11B-68Q3'DIAMETER SIZE +SPACING <br />A� GnabbemwithoCincu|arcmeooectiontuhaweodiommtnrorwidthofQrippingaurfauoehe||be1-1/4"to2"moximum, <br />B. The space between grab bars and adjacent wails shall be1'1/2'`minimum, <br />11B-0OQ.8-GRAB BARS - STRUCTURAL STRENGTH <br />A. Grab bars and mounting devices shall meet the following requirements: <br />1. Allowable stresses shall not be exceeded for materials used when a vertical or horizontal force of 250 <br />pounds is applied at any point on the grab bar, faster, mounting device, or supposering structure. <br />I IB-GO0.G-GRAB BARS 'SURFACE <br />A. Grab bars and adjacent wall surfaces shall be free of sharp or abrasive surfaces and shall have rounded edges, <br />11B-GO3.5-ACCESSORIES <br />GENERAL: Where towel, sanitary napkins, waste receptacles, dispensers, other equipment and controis are provided <br />at least one of each type shall be located on an accessible route, with all operable parts, including coin slots, within 40" <br />from the finished floor. <br />11B-GOI5-SPOUT LOCATION <br />A. Spouts shall be located at the front of the unit (I 5" minimum from the vertical support and 5"maximum from the <br />front edge including bumpers and the water stream from the bubbler shall have a flow in a trajectory that is parallel <br />(or nearly parallel) hothafrnntedge nJthe unit. <br />1� The spout shall provide eflow ofwater etleast 4"high minimum . <br />2. If the fountain has a round or oval bowl, the spout must be positioned so the flow of water is within 3" of the <br />front edge ofthe fountain. <br />116'8O2.3-OPERABLE PARTS <br />A. The flow of water shall be activated by a manually operated system that is front mounted or side mounted and <br />located within 6" of the front edge of the fountain or an automatic electronically controlled device. Maximum <br />force tooperate ia5|bf. <br />DIVISION 7 - COMMUNICATION ELEMENTS AND FEATURES <br />1iB-7O3j'GENERAL <br />A. When new or additional signs and/or identification devices are provided or when existing signs are <br />nap|oued/alt*nad,the new/altered signs shall comply with 11B-7D3: types include: <br />1. Identification signs <br />l Directional & informational signs <br />3. Accessibility signs <br />11B-7D3I1/11S-7O3.S.2-FINISH AND CONTRAST <br />A. Characters, symbols and background ofsigns shall have onon-glare finish. <br />B. Characters and symbols shall contrast with their background (i.e.alight characters unadark background or <br />dark characters onolight bookgmund). <br />11B703.2.4'PROPORTIONS <br />A. Visual characters nnsigns shall beselected from fonts where the width nfthe uppercase letter "O"io6Q <br />percent minimum and iiOpercent maximum ufthe uppercase letter "|" Stroke thickness ofthe uppercase letter "I" <br />shall be 10 percent minimum and 20 percent maximum of the height of the character. <br />11B-7D3.53-CHARACTER HEIGHT <br />A� Characters on signs shall be appropriately sized according to the viewing distance from which they are to be <br />read, refer tothe "Visual Character Height" table insection 11B-703.5�5 <br />B. Pictorial symbol signs (pictograms) shall be accompanied by the verbal (i.e. text) description placed directly <br />below the pictogram. The outside dimension ufthis pidoQnamahaUboominimum o/Ginches inheight. <br />C. Chana�emand 8naiUmshall bminahorizontal <brmoi <br />D� Braille shall be placed at a minimum of 3/8" and a maximum of 1/2" directly below the tactile characters, flush <br />left nrcentered. <br />E. When tactile text iamm0|ined.all Braille shall baplaced together below all lines oftactile text. <br />118-7D33-BRAILLE (REFERENCE FIGURE %meshown onthis sheet) <br />A. Braille dots are 1/10" on center in each cell with 2/10" space between cells, measured from the second column <br />cfdots inthe first cell tothe first column ofdots inthe Second cell. <br />B. Braille dots are raised ominimum of1/4U"above the background. <br />C. Braille dots are domed orrounded. <br />1 113-7103.3.2 - MOUNTING LOCATION & HEIGHTS (REFERENCE FIGURE 2 as shown on this sheet for restroorns) <br />A. Where permanent identification signage are provided for rooms & spaces signs shall be located on the wall <br />adjacent tothe latch side ofthe door. <br />Note: Where there is no wall space on the latch side, including at double -leaf doors, signs shall be placed on the <br />nearest adjacent wall. It is preferred on the right side, clear of any door swing. <br />& Todi|eoignaforpermanontmomeonomounhadonthnwallataminimumo[48"abmmthefiniahflun/hntho <br />baseline of lowest tactile character and a maximum of 60" above the finish floor to the baseline of highest tactile <br />character. Provide clear floor space of 18" minimum x 18" minimum centered on the tactile characters beyond the <br />arc oYany door swing between the closed position and 4G"open position. <br />C. The braille baseline must bebobwen4G"and GU''above the finished floor. <br />SANITARY FACILITY SIGNAGE <br />NOTE: Sanitary -facilities are required to display signs in a minimum of two locations: <br />1. One type located mnthe doorway urentryway hothe facility. <br />2. One type mounted onthe wall adjacent tuthe latch side o[the door. <br />l 1 i B-703.4.2 Restroom identification signs shall be located on the approach side of the door as one enters <br />the room orspace. <br />11B-703 SANITARY FACILITY DOOR MOUNTED S|GNAGE <br />A. 11B-783.72�1 (Men's) - Men's sanitary facilities shall be identified by an equilateral triangle 1/4" thick with <br />edges 12" long and a vertex pointing upward. The triangle symbol shall contrastwith the door, either light nnadark <br />background ordark nnolight background. Fig. 1aashown onthis sheet. <br />B. 11B-703I2.62 (Women's) - Women's sanitary facilities shall be identified by a circle that is 114" thick and 12" <br />indiameter. The circle symbol shall contrast with the door, either light mnodark background mdark omalight <br />background. Fig. 1 aoshown, nnthis sheet. <br />C. 11B-7D3I2.8.3 (Unisex) - Unisex sanitary facilities shall be identified by a 12" diameter circle that is 1/4" thick <br />triangle superimposed within the circle. The triangle symbol shall contrast with the circle symbol, either light ona <br />dark background or dark on a light background. The circle symbol shall contrast with the door, either light ono <br />dark background ordark unolight background. Fig. 1oashown onthis sheet. <br />D� I 1 B-703.4.1 - The geometric symbols shall be centered horizontally on the door at a height of 60" above the <br />finish floor or ground surface measured to the center of the symbol. Fig. 2. as shown on this sheet. <br />E, I I 13-703.726A - The edges of the signs shall be rounded, chamfered or eased, and any corners have a <br />minimum radius of1/Q"Fig. 1mashown onthis sheet. <br />1 IB-7O3SANITARY FACILITY WALL MOUNTED 8|GNAGE <br />A. The matroomidentification eignage(i.e. MEN'8.VVDMEN'8'UNBEXjiolocated onthe wall adjacent tnthe <br />latch side ofthe door. Fig. 2.anshown onthis sheet. <br />NOTE: Where there is no wall space on the latch side, 'Including at double leaf door, signs shall be placed on the <br />nearest adjacent wall, preferably oothe right. Fig�2.oxshown nnthis oha*L <br />B� Pictorial symbol signs (pictograms), if utilized in conjunction with verbal (i.e. text) identification, are located <br />directly above the verbal (ia. text) description and the border dimension of this pictogram is a minimum of 6" in <br />height, IiB-7O3.G1 Fig. 1ooshown nnthis sheet. <br />C. Provide clear floor space of 18" minimum x 18" minimum centered on 'the tactile characters beyond the arc of <br />any door swing between the closed pnmiUonand 45"open pooi�on.Fig�3,FiQ�4aoehmmnunthinsheet. <br />11B-7O3I21-INTERNATIONAL SYMBOL OFACCESSIBILITY <br />A. The International Symbol nfAccessibility shall beposted toidentify facilities that are accessible toand <br />usable byphysically disabled persons. <br />B. The Symbol ofshall consist nfawhite figure unablue background. <br />C. The blue color shall beequal ioColor No. 158SUinFederal Standard 585B. <br />Excegion: The appropriate enforcement agency may approve other colors, special signs and Identification to <br />compliment decor or unique design when it is determined that such an identification provides adequate <br />dim�iontopersons with disabilities. <br />11B-703-ENTRANCE SIGNS <br />A. Entrances to buildings and facilities that are accessible to and usable by persons with disabilities shall <br />be identified with a minimum of one International Symbol of Accessibility and with addition directional signs, <br />utilizing the symbol, at junctions where the accessible route of travel diverges from the regular circulation <br />path, to be visible to persons along approaching circulation paths. Fig. 1 as shown on this sheet <br />� <br />= <br />U 7 � <br />101j-TACTILE EXIT SIGNS <br />A. ��Q�����re���V����d�m��w���i�1.�������a���nm�0m <br />word, "EXIT". Fig. 4&5moshown unthis sheet <br />B. Each exit door, that iorequired {ocomply with section i&i1.that leads directly ioagrade-level exterior exit bymeans ofo <br />stairway or ramp shall be identified by a tactile exit sign with following words as appropriate: Fig. 5 as shown on this sheet <br />1. "EXIT STAIR DOWN" <br />2. "EXIT RANYIPDOWN" <br />3� �0 STAIR UP" <br />4. "EXIT RAMP UP" <br />C� Each exit door, that is required to comply with seGdm1011.that leads directly toagrade-level exterioemit bymeans ofanexit <br />enclosure that does not utilize a stair or ramp, or an exit passageway shall be identified by a tactile exit sign with the words, <br />"EXIT ROUTE". <br />O. Each exit access door, that is required to comply with section I 0 1 1, from an interior room (or area) thatis <br />required to have a visual exit sign shall be identified by a tactile exit sign with the words, "EXIT ROUTE". <br />E. Each exit door, that is required to comply with section 101 1, through a horizontal exit shall be identified byatactile exit sign with <br />the words, "TO EXIT" <br />1Z°D <br />0 �07_1 ___ _-) /' �\ Fi I ]�, / �__ _� / \ <br />- a6 0 0 0 � /'_ /�%�-7 <br />�� <br />V tuv &�___ 111, /�,, , I I I 6,� I � / �0 <br />WOMEN J / / <br />WALL-SIGNAGE DOOR MOUNTED SIGNAGE <br />NOTE: PICTOGRAMS AN/OR LETTERING ARE NOT lREQUIRED DNDOOR MOUNTED8IGNAGE.'NJ"' <br />r it,=_'% . <br />INTERNATIONAL SYMBOL OF ACCESSIBILITY <br />PROVIDE CLEAR FLOOR SPACE OF18INCHES MINIMUM X18INCHES MINIMUM, <br />CENTERED ONTHE TACTILE CHARACTERS BEYOND THE ARC DFANY DOOR SWING <br />BETWEEN THE CLOSED POSITION AND 45"OPEN POSITION. <br />~_�' � <br />- MOUNTED 60"AFFMAX. <br />TDBASELINE OF <br />H|GHTESTTACT|LE <br />CHARACTER <br />0 p- <br />+ 0:2�o <br />�LU <br />� <br />=� � <br />�. <br />R�RAISED�� <br />_�Z = = <br />PERMANENT 6|GNASETQBEINSTALLED ONTHE WALL <br />ADJACENT TO THE LATCH SIDE OF THE DOOR. <br />MOUNTING LOCATION MUST ALLOW A PERSON TO <br />APPROACH WITHOUT ENCOUNTERING PROTRUDING <br />OBJECTS OR STANDING WITHIN THE SWING PATH OF <br />THE DOOR. <br />L'i ­ .... ... \1 . . co W <br />:� MIN. X 18" MIN. CENTERED ON THE <br />DOOR SWING PATH / TACTILE CHARACTERS BEYOND THE <br />ARC DFANY DOOR SWING BETWEEN <br />THE CLOSED POSITION AND 45"OPEN <br />I Ir- <br />i�� <br />PERMANENT ROOMS AND SPACES POSITION. <br />/-- LETTERING RAISED <br />ROOM <br />/ 234 <br />(braille grid) <br />oocmoo <br />000000 <br />00000u <br />ubc <br />LETTERS AND NUMBERALS SHALL BE RAISED <br />1/32'UPPER CASE, SANSERIF TYPE AND <br />SHALL BEACCOMPANIED WITH GRADE N <br />BRAILLE, RAISED CHARACTERS SHALL BEAT <br />LEAST 50"HIGH, BUT NOHIGHER THAN 2~ <br />STANDARD DIMENSIONS: <br />Dot diameter <br />0.059 inches <br />Inter -dot mpooeing <br />0.098inoheo <br />Horizontal separation <br />between cells <br />0.241 inches <br />Vertical separation <br />between cells <br />8.395inohea <br />L, <br />o <br />� <br />DOOR SWING PATH / `~`=/ PROVIDE --- - - --- - <br />K0N. X18"MIN. CENTERED DNTHE <br />TACTILE CHARACTERS BEYOND THE <br />ARC OFANY DOOR SWING BETWEEN <br />FIGURE 4 - TACTILE EXIT SIGN L 10- i_�� <br />THE CLOSED POSITION AND 45,OPEN <br />POSITION. <br />DISTANCE FROM <br />RAISED BORDER <br />ANDDECORT|VE Z� <br />2 <br />ELEMENTS ----=~ <br />� <br />co <br />FIGURE 5 - TYPICAL EXIT SIGNS <br />118-308.2-CLEAR FLOOR SPACE <br />A. Clear floor space complying with Section 11B-305 that allows a forward mparallel approach byaperson using awheelchair <br />shall beprovided atcontrols, dispensers, receptacles and other operable equipment. <br />11B-3O8,8.2-HEIGHT <br />A. The highest operable part of alI controls, dispensers, receptacles and other operable equipment shall be placed within at <br />least one ofthe reach ranges specified insections 11S3O8.3.2and 11B-308 <br />. Where a forward reach is required, accessible storage spaces shall be 48" maximum and 15" minimum above the floor. <br />If the forward reach is over an obstruction (with knee space equal to or greater than reach distance) 20" - 25" deep, the <br />maximum height shall be44'`; ifthe obstruction ialess than 2O".maximum height shall be48" <br />. Where aside reach isprovided, accessible st� ogespaces shall �� bemaxmumandi5"minimumobnvotheOoo. <br />Maximum height shall be 46" for side reach over an obstruction 34" maximum high and 24" maximum deep. The high side <br />side reach shall be 48" over an obstruction 10" maximum in depth and 34" maximum high. <br />EXCEPTION: These requirements do not applywhere the use of special equipment dictates othenuise or where electrical and <br />communication system receptacles are not normally intended for use by building occupants. <br />11B'30Q.4-OPERATION <br />A. Controls and operating mechanisms shall bnopmab|ew�one hand and shall not �quireUghtgmmp�g. <br />pinching, orbwi�ingufthe wrioL <br />B. The force required huactivate the controls shall benugreater than 5|bt <br />I I B-308.3.2 - INSTALLATION OF HEIGHTS OF ELECTRICAL SWITCHES AND RECEPTACLE OUTLETS <br />A. Controls and switches shall belocated nomore than 48"measured from t'he top ofthe ouUaibox nor less than 15~ <br />measured �omthe bo#omof�eoutlet box tothe level ofthe �nimh0oornrworking platform, <br />B. Electrical outlets on branch circuits of 30 amps or less and communication system receptacles shall be no more than 48" <br />mommuradfromthetopoftheouUetboxornooeptau|ehouoingnor|enmthen15"meeoumdhnmthebottomnyiho <br />outlet box or receptacle housing to the level of the finish floor or working platform. <br />Note: Controls located inanalcove greater than 24"deep must have a3G"wide area ofclear floor space to <br />mohiovae0nntappmsnh. <br />1. Wheneoheok-outeio|emampmvidad,ohoch-outeielnocump|yingwithSnction11B-Q04.3ohaUbepmvidedin <br />accordance with Table 11B-2272 Where check-out sales serve different functions, check-out aisles complying <br />with Section I 1 B-904.3 shall be provided in accordance with Table 1 1 B-227.2 for each function. <br />2. Each check-out aisle shall be identified per the governing agencies requirements and per the "International <br />symbol nfaccessibility" complying with Section I1B'7O372.1. The sign shall boaminimum of4"by4" <br />3. Accessible check -stands shall boidentified byesign clearly visible tnthose inwheelchairs which displays the <br />international symbol ofaccessibility inwhite nnanall blue background and shall state "This check stand shall ba <br />open atall times for Cushum*rswithDieohi/itiau" <br />1. Sales counters and service counters shall comply with Section 11B-9O4.4.1ur11B-9O4�.2.The <br />0000saib|epurtionofthouountertopahoUoxandthaoamed*pthamtehualennraem(oeonuntertop. <br />1iB-D1i-DEPTH (REFERENCE FIGURE i18-6Daoshown unthis sheet) <br />A. Where a forward reach is required, accessible storage spaces shall be 48" maximum and 15" minimum above <br />the floor. If the forward reach is over an obstruction (with knee space equal to or greater than reach distance) 20" - <br />25" deep, the maximum height shall be 44"; if the obstruction is less than 20", maximum height shall be 48". <br />B. Where a side reach is provided, accessible storage spaces shall be 48" maximum and 15" minimum above the <br />Moor. Maximum height shall be 46" for side reach over an obstruction 34" maximum high and 24" maximum deep. <br />The high side side reach shall be 48" over an obstruction 10" maximum in depth and 34" maximum high. <br />11B-8i1.3-HEIGHT (REFERENCE FIGURE 1iB'5Daushown unthis sheet) <br />A. Storage areas may be 25" in depth or less, If more than 36" in depth then area must allow 60" diameter of clear <br />floor space for turning, <br />118-D1i.4-HARDWARE <br />A. Hardware -for accessible storage facilities shall be operable with one hand and shall not require tight <br />grasping, pinching, ortwisting ufthe wrist. <br />B. The force required toactivate the hardware shall benugreater than 5|hf <br />C. Touch |acheoand U-shaped pulls are acceptable. <br />CLEAR FLOOR SPACE: (REFERENCE FIGURE 11B-50,aoshown onthis sheet) <br />. -1 -1 , 1, 1/1 <br />- _ '' 1_� 2: �_ �'N = ! <br />1O"MAX. <br />\`_10^MAX(UNOBGTI ,UCTEDREACH) <br />24"MAX. (UNOBSTRUCTED HIGH REACH) <br />(___ <br />I )L-11111 <br />(a) <br />CLEAR FLOOR SPACE <br />PARALLEL APPROACH SIDE REACH <br />1O"MAX. , <br />11 <br />(b) (c) <br />UNOBSTRUCTED HIGH SIDE REACH UNOBSTRUCTED HIGH SIDE REACH <br />REACH RANGES & CLEAR FLOOR SPACE <br />FIXED OR BUILT-IN SEATING, TABLES &COUNTERS <br />1. Where fixed mbuilt-in seating, tables, or counters are provided in accessible public use or common use areas, <br />never less than one must b*accessible, aorequired per Table 11B-221.2i1 (I113-2211). <br />2. Ifseating spaces for persons inwheelchairs are provided edfixed tables orcounters, clear floor space ommp|�ng <br />with Section I I B-305 shall be provided. Such clear floor space shall not overlap knee space by more than 19" (i 1 B-306). <br />3. If seating for persons in wheelchairs is provided at fixed tables or counters, knee spaces at least 27" high, <br />3U"wide, and 1B"deep shall heprovided. (1IB'S82.2/11B-30G) <br />4. The tops nftables and counters shall be28"minimum to34"maximum from the floor orground, (111B-982.3) <br />Where required, fire alarm systems shall have permanently installed audible and visible alarms complying with NFPA 72 <br />and Chapter 9 sections 907.5.2.1 and 907.5.2.3, except that the maximum allowable sound level of audible notification <br />appliances shall have esound level nomore than 11OdBat the minimum hearing distance from the audible appliance. <br />EXCEPTION: Fire alarm systems in medical care facilities shall be permitted to be provided in accordance with industry practice. <br />BO7.52.1-AUDIBLE ALARMS <br />GENERAL: <br />Audible alarm notification appliances shall be provided and emit a distinctive sound that is not to be used for ally purpose other <br />than that ofafire alarm. In Group 1-2 occupancies, audible appliances located in patient areas shall be only chimes or similar <br />sounding appliances furalerting staff. <br />EXCEPTION: Visible alarm notification appliances shall be allowed in lieu of audible alarm notification appliances in <br />patient areas ofGroup |'2occupancies. <br />A. AVERAGE SOUND PRESSURE - Audible alarm notification appliances shall provide a sound pressure <br />level of 15 decibels (dBA) above the average ambient sound level or 5 dBA above the maximum sound level <br />having a duration off at least 60 seconds, whichever is greater in every occupiable space within the building. <br />The minimum sound pressure levels shall be: 75 dBA in occupancies in Group R; 90 dBA in mechanical <br />equipment rooms and GOdBAinother occupancies. <br />B. MAX/MUM SOUND PRESSURE - The maximum sound pressure level for audible alarm notification <br />appliances shall be 1 10 dBA at the minimum hearing distance from the audible appliance. Where the <br />average ambient noise is greater than 95 dBA, visible alarm notification appliances shall be provided in <br />accordance with NFPA 72 and audible alram notification appliances shall not be required. <br />C. AUDIBLE ALARM SIGNALE - The audible signal shall be the standard fire alarm evacuation signal, ANSI <br />S3.41 Audible Emergency Evacuation Signal, "three pulse temporal pattern,"as described in NFPA 72. <br />EXCEPTION: The use of existing evacuation signaling scheme shall be permitted where approved by the enforcing agency. <br />QOT.523-VISUAL ALARMS <br />A. Where required visual alarm signal appliances shall be integrated into the building or facility alarm system. If <br />single station audible alarms are provided then single station visual alarm signals shall be provided, Visual alarm <br />notification appliances shall be provided In public use areas and common use ares, including but not limited to: <br />sanitary facilities including restrooms, bathrooms and shower rooms, corridors, music practice rooms, <br />gymnasiums, lobbies, meeting rooms, classrooms, occupied rooms where ambient noise impairs hearing of the <br />fire alarm, occupational shops, band rooms, and multipurpose rooms. <br />Visual Alarm appliances shall have the following features: <br />1. The lamp shall booxenon strobe type orequivalent. <br />2. The color shall be clear or nominal white (i.e. unfiltered or clear filtered white light). <br />3. The maximum pulse duration shall belbivo-tenths of one second with a maximum duty cycle of4U%.(The pulse <br />duration is defined as the time interval between initial and final points of 10% of max signal) <br />4. The intensity shall be a minimum of 15 candela (effective) in non -sleeping rooms and a minimum of I 10 <br />oande|o(effectiva)ifthe strobe inmore than 24inches from the ceiling and 177candela (eOectiva)ifthe strobe ia <br />less than 24'from the ceiling. <br />5� The flash rate shall beaminimum uf1Hzand amaximum nf2Hz <br />G� Thaapp|ienueuha||bep|emad80"minimumendBS"maximumabovethefiniuhOoor, <br />7. Ingeneral, strobe placement shall toachieve illuminance ofmt|oaa�O.O375|m/ft'inall areas inthe room. <br />8. No place in common corridors or hallways shall be more than 50 feet from the signal and a maximum of 15 feet from each end. <br />� <br />� <br />� <br />� <br />��U7�Y� ���� �����������. <br />��" v « ��: ���u-o��~x : <br />���U����� ���� �E����U�� <br />;& <br />� "el, e 11,� <br />� ��� �- ������� ��� ����� <br />B��H�) ����U� ������� <br />�0� �������� <br />������� ��x0 � �� <br />��� ��� � ==� ���== � �� <br />������ � �� � � �� <br />REGISTERED <br />���4 REGISTERED <br />F ARCHITECT <br />I CH C. SMIT <br />ARCHITECT <br />CH6 <br />06/03/2021 <br />@we2,mn.Al/ rights reserved. No partofthisuocumant maybe reproduced <br />in any form or by any means without permission in writing from MG2, Inc. <br />MEMNEMNIMERIMME <br />/\ DATE DES CRiPTUON <br />