PART1 GENERAL <br />1.1 SUMMARY <br />A. SECTION INCLUDES: <br />1. GAS PIPING MATERIALS <br />2. GAS PIPING LAYOUT INCLUDING SERVICE, METER AND DISTRIBUTION PIPING, WITH GAS BOOSTER, IF APPLICABLE. <br />3. GAS SAFETY SHUT-OFF VALVES <br />4. MASTER GAS CONTROL VALVES <br />5, GAS LUBRICATED PLUG VALVES AND GAS COCKS <br />6, GAS PRESSURE BOOSTER SYSTEM INCLUDING: <br />a, GAS BOOSTER PUMP <br />b. GAS PRESSURE SWITCH <br />c. LUBRICATED PLUG VALVES <br />d, CHECK VALVES <br />e. FLEXIBLE PIPE COUPLING <br />f. PRESSURE GAUGES <br />g. HEAT EXCHANGER <br />h. CONTROL SYSTEM - PANEL AND WIRING DIAGRAM. <br />I. PRESSURE AND GAS FLOW COMPENSATION MODULE <br />T STRAINERS <br />8. PIPE JOINT SEALING MATERIALS <br />9. FLANGES AND GASKETS <br />10. PULSATING GAS METER <br />11. RELAY & CONTROL PANEL <br />1.2 REFERENCES <br />A. INTERNATIONAL FUEL GAS CODE WITH WASHINGTON STATE AMENDMENTS <br />B. AMERICAN NATIONAL STANDARDS INSTITUTE: <br />1. ANSI Z21.15 -MANUALLY OPERATED GAS VALVES FOR APPLIANCES, APPLIANCE CONNECTOR VALVES AND HOSE END VALVES. <br />C. AMERICAN SOCIETY OF MECHANICAL ENGINEERS: <br />1. ASME B16.3 - MALLEABLE IRON THREADED FITTINGS. <br />2. ASME B16.26 - CAST COPPER ALLOY FITTINGS FOR FLARED COPPER TUBES, <br />3. ASME B16.33 - MANUALLY OPERATED METALLIC GAS VALVES FOR USE IN GAS PIPING SYSTEMS UP TO 125 PSIG (SIZES 1/2 - 2). <br />4, ASME B31.9 - BUILDING SERVICES PIPING. <br />5. ASME SECTION IX - BOILER AND PRESSURE VESSEL CODE - WELDING AND BRAZING QUALIFICATIONS, <br />D. ASTM INTERNATIONAL: <br />1. ASTM A53/A53M - STANDARD SPECIFICATION FOR PIPE, STEEL, BLACK AND HOT -DIPPED, ZINC -COATED, WELDED AND SEAMLESS. <br />Z ASTM A234/A234M - STANDARD SPECIFICATION FOR PIPING FITTINGS OF WROUGHT CARBON STEEL AND ALLOY STEEL FOR MODERATE AND HIGH TEMPERATURE <br />SERVICE, <br />3. ASTM B88 - STANDARD SPECIFICATION FOR SEAMLESS COPPER WATER TUBE, <br />4. ASTM B280 - STANDARD SPECIFICATION FOR SEAMLESS COPPER TUBE FOR AIR CONDITIONING AND REFRIGERATION FIELD SERVICE. <br />5. ASTM B749 - STANDARD SPECIFICATION FOR LEAD AND LEAD ALLOY STRIP, SHEET, AND PLATE PRODUCTS. <br />6. ASTM E708 - STANDARD PRACTICE FOR DESIGN AND INSTALLATION OF RIGID PIPE HANGERS, <br />E. AMERICAN WELDING SOCIETY: <br />1, AWS D1.1 -STRUCTURAL WELDING CODE- STEEL. <br />F. AMERICAN WATERWORKS ASSOCIATION: <br />1. AWWA C105 -AMERICAN NATIONAL STANDARD FOR POLYETHYLENE ENCASEMENT FOR DUCTILE -IRON PIPE SYSTEMS. <br />G. MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY: <br />1, MSS SP 58 - PIPE HANGERS AND SUPPORTS - MATERIALS, DESIGN AND MANUFACTURER. <br />2, MSS SP 67 - BUTTERFLY VALVES. <br />3. MSS SP 69 - PIPE HANGERS AND SUPPORTS - SELECTION AND APPLICATION. <br />4. MSS SP 78 - CAST IRON PLUG VALVES, FLANGED AND THREADED ENDS. <br />5. MSS SP 89 - PIPE HANGERS AND SUPPORTS - FABRICATION AND INSTALLATION PRACTICES. <br />6. MSS SP 110 - BALL VALVES THREADED, SOCKET -WELDING, SOLDER JOINT, GROOVED AND FLARED ENDS, <br />H. NATIONAL FIRE PROTECTION ASSOCIATION: <br />1. NFPA 54 - NATIONAL FUEL GAS CODE. <br />L UNDERWRITERS LABORATORIES INC.: <br />1. UL 842 -VALVES FOR FLAMMABLE FLUIDS. <br />1.3 SYSTEM DESCRIPTION <br />A. WHERE MORE THAN ONE PIPING SYSTEM MATERIAL IS SPECIFIED, PROVIDE COMPATIBLE SYSTEM COMPONENTS AND JOINTS. USE NON -CONDUCTING DIELECTRIC <br />CONNECTIONS WHEN JOINING DISSIMILAR METALS IN SYSTEMS. <br />B. PROVIDE FLANGES, UNIONS, OR COUPLINGS AT LOCATIONS REQUIRING SERVICING. USE UNIONS, FLANGES, OR COUPLINGS DOWNSTREAM OF VALVES AND AT <br />EQUIPMENT CONNECTIONS. DO NOT USE DIRECT WELDED OR THREADED CONNECTIONS TO VALVES, EQUIPMENT, <br />C. PROVIDE PIPE HANGERS AND SUPPORTS IN ACCORDANCE WITH ASME B31.9, ASTM F708, MSS SP 58, MSS SP 69, AND MSS SP 89. <br />D. USE PLUG, BALL, OR BUTTERFLY VALVES FOR SHUT-OFF AND TO ISOLATE EQUIPMENT, PART OF SYSTEMS, OR VERTICAL RISERS. <br />1.4 SUBMITTALS <br />A. PRODUCT DATA: <br />1. PIPING: SUBMIT DATA ON PIPE MATERIALS, FITTINGS, AND ACCESSORIES: SUBMIT MANUFACTURERS CATALOG INFORMATION. <br />2. VALVES: SUBMIT MANUFACTURERS CATALOG INFORMATION WITH VALVE DATA AND RATINGS FOR EACH SERVICE. <br />3. HANGERS AND SUPPORTS: SUBMIT MANUFACTURERS CATALOG INFORMATION INCLUDING LOAD CAPACITY. <br />4. PIPING SPECIALTIES: SUBMIT MANUFACTURERS CATALOG INFORMATION INCLUDING CAPACITY, ROUGH -IN REQUIREMENTS, AND SERVICE SIZES FOR THE <br />FOLLOWING: <br />a. STRAINERS. <br />b. NATURAL GAS PRESSURE REGULATORS. <br />c. NATURAL GAS PRESSURE RELIEF VALVES. <br />d. METERS <br />B. DESIGN DATA: INDICATE PIPE SIZE. INDICATE LOAD CARRYING CAPACITY OF TRAPEZE, MULTIPLE PIPE, AND RISER SUPPORT HANGERS. <br />C. TEST REPORTS: INDICATE RESULTS OF PIPING SYSTEM PRESSURE TEST. <br />D. MANUFACTURER'S CERTIFICATE: CERTIFY PRODUCTS MEET OR EXCEED SPECIFIED REQUIREMENTS. <br />E. WELDERS CERTIFICATES: CERTIFY WELDERS EMPLOYED ON THE WORK, VERIFYING AWS QUALIFICATION WITHIN PREVIOUS 12 MONTHS. <br />1.5 CLOSEOUT SUBMITTALS <br />A. PROJECT RECORD DOCUMENTS: RECORD ACTUAL LOCATIONS OF VALVES, PIPING SYSTEM, AND SYSTEM COMPONENTS. <br />B. OPERATION AND MAINTENANCE DATA: SUBMIT FOR VALVES AND GAS PRESSURE REGULATORS INSTALLATION INSTRUCTIONS, SPARE PARTS LISTS, AND EXPLODED <br />ASSEMBLY VIEWS, <br />1.6 QUALITY ASSURANCE <br />A. PERFORM NATURAL GAS WORK IN ACCORDANCE WITH NFPA 54, <br />B. PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES AND LOCAL GAS COMPANY REQUIREMENTS. <br />C. PERFORM WORK IN ACCORDANCE WITH ASME B31.9 CODE FOR INSTALLATION OF PIPING SYSTEMS AND ASME SECTION IX FOR WELDING MATERIALS AND PROCEDURES. <br />D. PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES FOR WELDING HANGER AND SUPPORT ATTACHMENTS TO BUILDING STRUCTURE. <br />E. FURNISH SHUTOFF VALVES COMPLYING WITH ASME B16.33 OR ANSI Z21.15. <br />F. PERFORM WORK IN ACCORDANCE WITH LOCAL AND STATE CODES. <br />G. MAINTAIN ONE COPY COPIES OF EACH DOCUMENT ON SITE. <br />1.7 QUALIFICATIONS <br />A. MANUFACTURER: COMPANY SPECIALIZING IN MANUFACTURING PRODUCTS SPECIFIED IN THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE. <br />B. INSTALLER: COMPANY SPECIALIZING IN PERFORMING WORK OF THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE APPROVED BY MANUFACTURER, <br />C. DESIGN PIPING SYSTEM HANGERS AND SUPPORTS UNDER DIRECT SUPERVISION OF PROFESSIONAL ENGINEER EXPERIENCED IN DESIGN OF THIS WORK AND LICENSED <br />AT PROJECT LOCATION IN STATE OF NEW YORK. <br />1.8 DELIVERY, STORAGE, AND HANDLING <br />A. ACCEPT VALVES ON SITE IN SHIPPING CONTAINERS WITH LABELING IN PLACE. INSPECT FOR DAMAGE. <br />B. PROTECT PIPING AND FITTINGS FROM SOIL AND DEBRIS WITH TEMPORARY END CAPS AND CLOSURES, MAINTAIN IN PLACE UNTIL INSTALLATION. FURNISH TEMPORARY <br />PROTECTIVE COATING ON CAST IRON AND STEEL VALVES, <br />1.9 ENVIRONMENTAL REQUIREMENTS <br />A. DO NOT INSTALL UNDERGROUND PIPING WHEN BEDDING IS WET OR FROZEN. <br />1.10 FIELD MEASUREMENTS <br />A. VERIFY FIELD MEASUREMENTS PRIOR TO FABRICATION. <br />1,11 COORDINATION <br />A. COORDINATE TRENCHING EXCAVATING BEDDING BACKFILLING OF BURIED PIPING SYSTEMS, <br />1.12 WARRANTY <br />A. FURNISH FIVE YEAR MANUFACTURER WARRANTY FOR VALVES EXCLUDING PACKING. <br />1,13 EXTRA MATERIALS <br />A. FURNISH TWO PACKING KITS FOR EACH TYPE AND SIZE VALVE. <br />PART PRODUCTS <br />2.1 MATERIALS <br />A. GAS PIPING SHALL BE STANDARD WEIGHT (SCHEDULE 40) BLACK STEEL PIPE. GAS CONTROL, VENT AND RELIEF PIPING SHALL ALSO BE STANDARD WEIGHT, SCHEDULE 40 <br />BLACK STEEL PIPE. STEEL PIPE SHALL BE SEAMLESS OR WELDED MADE IN ACCORDANCE WITH THE CURRENT EDITION OF THE ASTM A53 SPECIFICATION. <br />1. IN NO CASE SHALL ANY GAS PIPE BE LESS THAN 3/4", THE SIZES OF PIPE INDICATE NOMINAL PIPE SIZE. <br />2. GAS DISTRIBUTION PIPING FOR SYSTEMS OPERATING AT 1/2 PSIG OR LESS SHALL BE IN ACCORDANCE WITH ANSI Z223.1-1974 (NFPA-54) AND NATIONAL FUEL CODE <br />3. GAS DISTRIBUTION PIPING SYSTEMS HAVING A GAS PRESSURE ABOVE 1/2 PSIG SHALL CONFORM TO ANSI B31.2-1968, FUEL GAS PIPING AND REQUIREMENTS OF THE <br />INTERNATION FUEL GAS CODE <br />4. PIPING JOINTS FOR GAS DISTRIBUTION PIPING: <br />a. PIPING AT 1/2 PSIG (14" WC) AND LESS: <br />1) 4" AND SMALLER... SCREWED <br />2) -OVER 4"......,WELDED <br />b. PIPING OVER 1/2 PSIG (14" WC) TO AND INCLUDING 3 PSIG: <br />1) UNDER 4".....SCREWED <br />2) 4" AND LARGER... WELDED <br />c. PIPING OVER 3 PSIG: <br />1) ALL PIPING..,. WELDED <br />B. FITTINGS <br />1. FITTINGS FOR SCREWED GAS PIPING SHALL BE 150 LBS. BLACK MALLEABLE IRON FITTINGS, CONFORMING TO ASTM A197, LATEST EDITION, <br />2. COMPRESSION TYPE FITTINGS AND STEEL WELDING FITTINGS SHALL BE AS SPECIFIED AND APPROVED BY THE GAS COMPANY. <br />3. STEEL BUTT WELDING FITTINGS SHALL CONFORM TO ANSI B16.9 REQUIREMENTS. <br />4. FITTING FOR CONTROL, VENT AND RELIEF PIPING SHALL BE 300 LB. BLACK MALLEABLE IRON SCREWED FITTINGS CONFORMING TO ASTM A197, LATEST <br />EDITION. <br />C. FLANGES <br />1. ALL FLANGES SHALL BE STEEL AND COMPATIBLE IN TYPE AND PRESSURE RATINGS WITH MATING FLANGE AND SHALL COMPLY WITH ANSI B16.5. <br />2. FLANGES SHALL BE WELDING NECK OR THREADED END, SLIP ON FLANGES ARE NOT PERMITTED. <br />3. WHERE 150 POUND STEEL FLANGES ARE BOLTED TO CLASS 125 CAST IRON FLANGES, THE RAISED FACE ON THE STEEL FLANGE SHALL BE REMOVED, <br />D. GASKETS <br />1. GASKETS SHALL BE COMPATIBLE WITH THE GAS SERVICE ON WHICH THEY ARE USED, WITHOUT CHANGE TO THEIR CHEMICAL OR PHYSICAL PROPERTIES, <br />2. GASKET SHALL BE BLUE-GARD COMPRESSED ASBESTOS FREE GASKETS, STYLE 3000 OR GYLON GASKETING STYLE 3500, COLOR: FAWN WITH BLUE BRAND <br />BOTH AS MANUFACTURED BY GARLOCK INC. <br />1 GASKETS OF METAL OR METAL -JACKETS, ALUMINUM O-RINGS AND SPIRAL WOUND METAL GASKETS, OR OTHER MATERIALS, IF APPROVED BY THE UTILITY <br />COMPANY MAY BE USED. <br />4. FULL FACE GASKETS SHALL BE USED WITH ALL BRONZE AND CAST IRON FLANGES, <br />E. BOLTS AND NUTS <br />1 BOLTS AND NUTS SHALL BE OF BEST QUALITY BOLT STEEL WITH SQUARE HEAD BOLTS AND HEXAGON NUTS WITH MACHINE CUT V-THREADS. <br />F, THREAD JOINT SEALANT MATERIALS <br />1, THREAD SEALANT TO BE USED ON NATURAL GAS PIPING SHALL BE RECTORSEAL CORP NO. 5, OATEY GREAT BLUE PIPE JOINT COMPOUND HERCULES <br />MEGALOC MULTI -PURPOSE THREAD SEALANT OR APPROVED EQUAL. THREAD SEALANT SHALL BE A NON -TOXIC, SOFT SETTING, SLOW DRYING SEALANT MADE <br />FROM INERT FILLERS. THE JOINT SEALANT MATERIAL MAY CONTAIN TEFLON, IF THAT SUBSTANCE IS THE APPROVED TYPE FOR NATURAL GAS APPLICATION. <br />APPROVED TEFLON TAPES MAY BE USED ON NATURAL GAS LINES. NON -APPROVED TEFLON TAPES FOR USE ON PIPING FOR A NATURAL GAS SYSTEM ARE <br />PRONE TO TEARING WHEN PIPES ARE BEING ASSEMBLED AND TIGHTENED AND BITS OF TORN TAPE CAN MIGRATE INTO THE FLUID SYSTEM, CLOGGING <br />VALVES, SCREENS, AND FILTERS. <br />2.2 VENTING OF GAS PRESSURE REGULATORS <br />A, REGULATOR THAT MAINTAINS A GAS LINE PRESSURE OR CONTROLS THE SUPPLIED GAS PRESSURE TO APPLIANCES OR EQUIPMENTS SHALL HAVE AN <br />INDEPENDENT VENT PIPE ROUTED TO THE OUTSIDE OF THE BUILDING. THE VENT PIPE SHALL BE SO ARRANGED AS TO PREVENT THE ENTRY OF WATER OR <br />FOREIGN OBJECTS <br />2.3 FLEXIBLE GAS PIPE PASSING THROUGH A BUILDING SEISMIC JOINT <br />A. A BRAIDED FLEXIBLE STAINLESS STEEL MULTIPLE LEGS PIPE ASSEMBLY SHALL BE INSTALLED IN GAS PIPING SYSTEM PASSING THROUGH A BUILDING SEISMIC <br />JOINT OR BUILDING EXPANSION JOINT, WHEN REQUIRED, THE FLECIBLE PIPE CONNECTOR SHALL ALSO BE PROVIDED BETWEEN FLOORS TO RESTRAIN VERTICAL <br />DISPLACEMENT IN GAS PIPING ARRANGEMENT THAT IS CAUSED BY A SEISMIC EVENT <br />B. FLEXIBLE STAINLESS PIPE CONNECTOR SHALL INCORPORATE MULTIPLE LEG SECTIONS THAT ARE FORMED ON ANNULAR CORRUGATED STAINLESS STEEL HOSE. <br />THE CONNECTOR SHALL COMPENSATE FOR PIPE MOVEMENTS IN 6 DEGREEES OF FREEDOM: 3 COORDINATE AXES, PLUS SIMULATENOUS ROTATION AROUND <br />THOSE AXES, CONNECTOR SHALL BE CAPABLE TO RETRAIN DISPLACEMENT WITHOUT FAILURE FOR SEISMIC REQUIREMENTS LISTED IN SECTION BC 1621.1 <br />C. PROVIDE ACCEPTANCE BY OFFICE OF TECHNICAL CERTIFICATION AND RESEARCH (OTCR) TO UTILIZE THIS FLEXIBLE CONNECTOR FOR SEISMIC RESISTANCE IN <br />GAS PIPING, IN ADDITION, CONNECTOR SHALL BE TESTED, LISTED AND LABELLED TO UL 536-2003 BY AN APPROVED AGENCY AND AS REQUIRED PER AC 28-113.4, <br />ACCEPTABLE BRAIDED FLEXIBLE STAINLESS STEEL PIPE CONNECTOR SHALL BE SIMILAR TO TRI-FLEX LOOP AS MANUFACTURED BY FLEX HOSE. <br />PART 3 - EXECUTION <br />3.1 INSTALLATION <br />A. GAS SERVICE AND GAS DISTRIBUTION PIPING, NUMBER AND DISTRIBUTION OF APPLIANCES, SHALL BE INSTALLED AS INDICATED ON THE DRAWINGS AND SHALL BE <br />IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THE GAS COMPANY AND ACCORDING TO THE LATEST REGULATIONS OF THE ADMINISTRATIVE CODE OF <br />THE CITY OF NEW YORK AND SHALL MEET THE REQUIREMENT OF THE DEPARTMENT OF BUILDINGS. <br />1. CONTRACTOR SHALL ARRANGE FOR INSPECTION AND ADJUSTMENT OF ALL GAS APPLIANCES OF THE CONTRACT, SO THAT THEY WILL PROPERLY AND SAFELY <br />OPERATE WITH NATURAL GAS. <br />B. THE CONTRACTOR SHALL NOTIFY THE AUTHORITY WHEN ALL IS READY FOR THE GAS COMPANY TO EXTEND THEIR SERVICE PIPE TO THE STREET LINE; AND AGAIN <br />AFTER TESTS, WHEN ALL IS IN READINESS FOR THE INSTALLATION OF THE METERS, THE METERS, OF THE PULSATING KIND IF A LONWORKS NETWORK IS <br />PROVIDED, SHALL THEN BE CONNECTED WITH THE SERVICE PIPES, AND WITH THE SEVERAL LINES OF DISTRIBUTING PIPES. THE SETTING, PIPING AND <br />CONNECTING UP OF THE METERS SHALL BE DONE IN ACCORDANCE WITH THE RULES OF THE GAS COMPANY, <br />C. JOINT SEALING MATERIALS (PIPE DOPE) USED WITH SCREWED FITTING SHALL BE APPLIED SPARINGLY AND ONLY TO THE MALE THREADS OF PIPE JOINTS. THE <br />BURRS MADE IN CUTTING THE PIPE SHALL BE REMOVED. PLUGGED TEES IN PLACE OF ELBOWS SHALL BE USED WHEREVER DIRECTED. WHERE PIPES OF <br />DIFFERENT SIZES COME TOGETHER, REDUCING FITTINGS SHALL BE USED. NO BUSHING WILL BE PERMITTED. <br />D. PIPING INSTALLED BELOW GRADE SHALL BE CONNECTED BY WELDING BY APPROVED CERTIFIED WELDERS, OR WITH COMPRESSION TYPE FITTINGS AS SPECIFIED <br />AND APPROVED BY THE GAS COMPANY. <br />a. SERVICE PIPING BELOW GRADE SHALL BE MILL WRAPPED IN ACCORDANCE WITH THE GAS COMPANY REGULATIONS. <br />b. BACKFILL OPERATIONS SHALL BE STARTED ONLY AFTER WELDING INSPECTION, COATING INSPECTION AND TESTING HAVE BEEN COMPLETED AS PER <br />REGULATIONS OF THE GAS COMPANY, <br />E. INTER -CONNECTIONS BETWEEN PIPING AT DIFFERENT PRESSURE LEVELS IS NOT PERMITTED. <br />F. GAS METER PIPING SUPPLYING GAS TO A BUILDING AT A PRESSURE IN EXCESS OF 1/2 PSIG SHALL BE PROVIDED WITH A PRESSURE REGULATOR TO REDUCE THE <br />GAS PRESSURE TO 112 PSIG OR LESS UNLESS NOTED OTHERWISE. <br />G. PROVIDE GAS LUBRICATED PLUG VALVES WHERE SPECIFIED, SHOWN ON DRAWINGS OR OTHERWISE REQUIRED FOR CONTROL OF GAS IN THE DISTRIBUTION <br />PIPING; MAINS, BRANCHES AND AT THE BASE OF EACH RISER. INSTALL SLEEVES IN FLOORS FOR RISERS TO PASS THROUGH. AN ACCESSIBLE MANUAL GAS COCK <br />OR LUBRICATED PLUG VALVE OF THE SAME SIZE AS THE PIPE SHALL BE INSTALLED AT EACH PIECE OF GAS BURNING EQUIPMENT, TO ALLOW FOR ISOLATION OF <br />THE EQUIPMENT AND WHERE INDICATED ON DRAWINGS, ALL VALVES AND COCKS FOR GAS THROUGHOUT THE BUILDING SHALL BE TAGGED WITH NUMBERED <br />METAL TAGS, INSTALL DRIP, CONSISTING OF NIPPLE AND CAP, AT THE BASE OF ALL RISERS AND CHANGES IN ELEVATION, <br />H. GAS VALVES SHALL NOT BE INSTALLED IN CONCEALED LOCATIONS AND FURNACE PLENUMS. WALL ENCLOSURES, PIPE SPACES OR OTHER RECESS IN WHICH GAS <br />VALVES ARE INSTALLED MUST BE VENTED TO AN ADJOINING VENTILATED AREA. <br />1. IN NO CASE SHALL A GAS PIPE RUN THROUGH A HEAT DUCT OR STAIRWELL. THE CONTRACTOR SHALL DO ALL CUTTING AND BORING OF HOLES NECESSARY FOR <br />EXTENDING PIPES AND BRANCHES, MAKING ALL NECESSARY OPENINGS IN WALLS, AND SHALL MAKE ALL REPAIRS TO SAME. <br />J. ONLY GAS RANGES AND DRYER UNITS MAY BE CONNECTED WITH "FLEXIBLE CONNECTORS". ALL OTHER GAS BURNING EQUIPMENT MUST BE CONNECTED WITH A <br />RIGID CONNECTION. <br />K. FINAL CONNECTIONS TO BURNER PILOT LIGHTS AND BOILER GAS TRAINS SHALL BE MADE BY THE PLUMBING CONTRACTOR. <br />L. ALL GAS PIPING TO EQUIPMENT ON ROOF SHALL BE RUN ON ROOF AND BE SUPPORTED SECURELY AS SPECIFIED IN HANGERS AND SUPPORTS, <br />3.9 FLEXIBLE CONNECTORS <br />A. FLEXIBLE RANGE CONNECTORS SHALL BE OF THE MINIMUM PRACTICAL LENGTH AND SHALL NOT EXTEND FROM ONE ROOM TO ANOTHER NOR PASS THROUGH <br />ANY WALLS, PARTITIONS, CEILINGS OR FLOORS, <br />B. FLEXIBLE CONNECTORS SHALL NOT BE USED 1N ANY CONCEALED LOCATIONS, <br />C. FLEXIBLE CONNECTORS SHALL BE PROTECTED AGAINST PHYSICAL AND THERMAL DAMAGE AND SHALL BE PROVIDED WITH GAS SHUT OFF VALVES (COCKS) IN <br />READILY ACCESSIBLE LOCATIONS IN RIGID PIPING UPSTREAM FROM THE FLEXIBLE CONNECTORS. <br />3.10 PAINTING <br />A. PAINTS AND COATINGS USED IN THE INTERIOR OF BUILDING TO MARK PIPING FOR IDENTIFICATION PURPOSES SHALL NOT: <br />1. EXCEED THE VOC CONTENT LIMITS ESTABLISHED IN THE GREEN SEAL STANDARD GS-11 PINTS, FIRST EDITION, MAY 20, 1993. <br />2. EXCEED THE VOC CONTENT LIMIT OF 250 G/L ESTABLISHED IN THE GREEN SEAL STANDARD GC-03, ANTI -CORROSIVE PAINTS, SECOND EDITION, JANUARY 7, <br />1997. <br />B. ALL EXPOSED GAS PIPE SHALL RECEIVE ONE (1) COAT OF TNEMEC 10-99 OR BENJAMIN MOORE IRON CLAD RETARDO RUST INHIBITIVE PRIMER PAINT AND ONE(1) <br />FINISHED COAT OF SAFETY YELLOW. GAS VENT PIPING EXPOSED TO PUBLIC VIEW OUTSIDE THE BUILDING SHALL RECEIVE ONE (1) COAT OF TNEMEC 10-99 OR <br />BENJAMIN MOORE IRON CLAD RETARDO RUST INHIBITIVE PRIMER PAINT AND ONE COAT OF FINISHED PAINT SELECTED BY THE FILING ARCHITECT, <br />C. MILL -WRAPPED PIPING SHALL NOT BE PAINTED. <br />D. PIPING AT DIFFERENT PRESSURE LEVELS IN THE SAME SPACE SHALL BE COLOR CODED AND LABELED, <br />3.11 LABELING <br />A. GENERAL REQUIREMENTS: GAS PIPING OPERATING AT DIFFERENT PRESSURES SHALL HAVE LABELING MARKERS INDICATING OPERATING PRESSURE WITHIN THAT <br />PIPING. <br />B. ALL VALVES SHALL BE SUITABLY TAGGED TO INDICATE THE OPERATING PRESSURE LEVEL WITHIN THE DISTRIBUTION PIPING. <br />3.13 DEMONSTRATION <br />A. THE SERVICES OF A FACTORY TRAINED REPRESENTATIVE SHALL BE AVAILABLE ON THE JOB SITE FOR START-UP AND FOR INSTRUCTING THE BUILDING MANAGER <br />IN THE OPERATION AND MAINTENANCE OF THE GAS SAFETY SHUT-OFF VALVES AND THE CENTRIFUGAL GAS BOOSTER SYSTEM, <br />3.14 FIELD QUALITY CONTROL <br />A. TESTING <br />1. GENERAL <br />a. GAS PIPE WELDING IS SUBJECT TO ALL TESTS REQUIRED BY THE AUTHORITY AND SPECIAL INSPECTION REQUIREMENTS OF THE MEMPHIS BUILDING <br />CODE. <br />b. COOPERATE WITH THE TESTING LABORATORY IN MAKING ALL REQUIRED TESTS. <br />1. TESTING LABORATORY <br />a. THE AUTHORITY WILL ENGAGE A TESTING LABORATORY OR SPECIAL INSPECTION AGENCY TO PROVIDE THE INSPECTION AND SPECIALTY TESTING. <br />b. THE TESTING LABORATORY WILL BE RESPONSIBLE TO AND UNDER THE SUPERVISION OF A SPECIAL INSPECTOR. <br />c. THE LABORATORY WILL PERFORM THE FOLLOWING TESTING. <br />1) ALL WELDED GAS DISTRIBUTION PIPING, LESS THAN OR EQUAL TO 3 PSIG: IN ADDITION TO INDEPENDENT PRESSURE TESTING OF THE ENTIRE <br />SYSTEM, AT LEAST TEN (10) PERCENT OF ALL WELDS OTHERWISE NOT REQUIRED TO BE NON-DESTRUCTIVELY TESTED WILL BE SUBJECT TO NOW <br />DESTRUCTIVE TESTING (RADIOGRAPHED AND/OR SUBJECTED TO ULTRASONIC TESTING). THE MINIMUM SAMPLING SHALL BE FIVE (5) WELDS.. ALL <br />WELDS SHALL BE RADIOGRAPHED AT THE CONTRACTOR'S EXPENSE IF ANY FAILURE OF ANY OF THE SAMPLES IS FOUND. CONTRACTOR SHALL MAKE <br />ALL NECESSARY REPAIRS AT NO COST TO THE OWNER. <br />2) ALL GAS DISTRIBUTION AND METER PIPING OVER 3 PSIG: ALL WELDS WILL BE RADIOGRAPHED. <br />2 SPECIAL INSPECTOR <br />THE AUTHORITY WILL ASSIGN A SPECIAL INSPECTOR TO SUPERVISE THE TESTING. THE SPECIAL INSPECTOR WILL VERIFY THE QUALIFICATIONS OF THE <br />WELDER <br />3. NOTIFICATION: BEFORE ANY WORK IS COMMENCED ON AN ITEM OF CONSTRUCTION REQUIRING SPECIAL INSPECTION, ALL PERSONS RESPONSIBLE FOR SUCH <br />SPECIAL INSPECTIONS SHALL BE NOTIFIED IN WRITING AT LEAST SEVENTY TWO (72) HOURS PRIOR TO SUCH COMMENCEMENT. <br />3.16 FLEXIBLE GAS PIPE PASSING THROUGH A BUILDING SEISMIC JOINT <br />A. INSTALL BRAIDED STAINLESS STEEL FLEXIBLE PIPE CONNECTOR AT BUILDING EXPANSION JOINTS AND /OR WHERE REQUIRED TO MANAGE PIPE MOVEMENT THAT <br />IS DUE TO A SEISMIC EVENT. PIPE CONNECTOR SHOULD NOT BE SUBJECTED TO TORSIONAL, TENSILE OR EXCESSIVE BENDING STRESSES. <br />1. INSTALLATION GUIDELINES SHALL BE AS PER THE MANUFACTURER'S INSTRUCTIONS. <br />2. PROTECT FLEXIBLE PIPE CONNECTOR AGAINST MECHANICAL INJURY. <br />3. INSTALLATION OF THE FLEXIBLE PIPE CONNECTOR IS SUBJECT TO THE SPECIAL INSPECTION REQUIREMENTS OF THE MEMPHIS FUEL GAS CODE. <br />4. ALL SHIPMENTS AND DELIVERIES OF THIS FLEXIBLE PIPE SHALL BE ACCOMPANIED BY A CERTIFICATE OR LABEL DECLARING THAT THE MATERIALS SHIPPED <br />OR DELIVERED ARE EQUIVALENT TO THOSE TESTED AND APPROVED. <br />0 <br />0 <br />U <br />ID <br />a <br />a <br />a <br />a <br />a <br />Q <br />c <br />m <br />Permit/Seal <br />2021-03-05 <br />Project No.: <br />File Name: N/A <br />Author Designer Checker 03/05/21 <br />Dwn. Dsgn. Chkd. YYYY.MM.DD <br />Title <br />GAS SPECIFICATIONS <br />Revision:» <br />{ Y 7 IT <br /><Pick location in Project Information> <br />3/5/2021 7:10:31 PM <br />