PART1 GENERAL
<br />1.1 SUMMARY
<br />A. SECTION INCLUDES:
<br />1. GAS PIPING MATERIALS
<br />2. GAS PIPING LAYOUT INCLUDING SERVICE, METER AND DISTRIBUTION PIPING, WITH GAS BOOSTER, IF APPLICABLE.
<br />3. GAS SAFETY SHUT-OFF VALVES
<br />4. MASTER GAS CONTROL VALVES
<br />5, GAS LUBRICATED PLUG VALVES AND GAS COCKS
<br />6, GAS PRESSURE BOOSTER SYSTEM INCLUDING:
<br />a, GAS BOOSTER PUMP
<br />b. GAS PRESSURE SWITCH
<br />c. LUBRICATED PLUG VALVES
<br />d, CHECK VALVES
<br />e. FLEXIBLE PIPE COUPLING
<br />f. PRESSURE GAUGES
<br />g. HEAT EXCHANGER
<br />h. CONTROL SYSTEM - PANEL AND WIRING DIAGRAM.
<br />I. PRESSURE AND GAS FLOW COMPENSATION MODULE
<br />T STRAINERS
<br />8. PIPE JOINT SEALING MATERIALS
<br />9. FLANGES AND GASKETS
<br />10. PULSATING GAS METER
<br />11. RELAY & CONTROL PANEL
<br />1.2 REFERENCES
<br />A. INTERNATIONAL FUEL GAS CODE WITH WASHINGTON STATE AMENDMENTS
<br />B. AMERICAN NATIONAL STANDARDS INSTITUTE:
<br />1. ANSI Z21.15 -MANUALLY OPERATED GAS VALVES FOR APPLIANCES, APPLIANCE CONNECTOR VALVES AND HOSE END VALVES.
<br />C. AMERICAN SOCIETY OF MECHANICAL ENGINEERS:
<br />1. ASME B16.3 - MALLEABLE IRON THREADED FITTINGS.
<br />2. ASME B16.26 - CAST COPPER ALLOY FITTINGS FOR FLARED COPPER TUBES,
<br />3. ASME B16.33 - MANUALLY OPERATED METALLIC GAS VALVES FOR USE IN GAS PIPING SYSTEMS UP TO 125 PSIG (SIZES 1/2 - 2).
<br />4, ASME B31.9 - BUILDING SERVICES PIPING.
<br />5. ASME SECTION IX - BOILER AND PRESSURE VESSEL CODE - WELDING AND BRAZING QUALIFICATIONS,
<br />D. ASTM INTERNATIONAL:
<br />1. ASTM A53/A53M - STANDARD SPECIFICATION FOR PIPE, STEEL, BLACK AND HOT -DIPPED, ZINC -COATED, WELDED AND SEAMLESS.
<br />Z ASTM A234/A234M - STANDARD SPECIFICATION FOR PIPING FITTINGS OF WROUGHT CARBON STEEL AND ALLOY STEEL FOR MODERATE AND HIGH TEMPERATURE
<br />SERVICE,
<br />3. ASTM B88 - STANDARD SPECIFICATION FOR SEAMLESS COPPER WATER TUBE,
<br />4. ASTM B280 - STANDARD SPECIFICATION FOR SEAMLESS COPPER TUBE FOR AIR CONDITIONING AND REFRIGERATION FIELD SERVICE.
<br />5. ASTM B749 - STANDARD SPECIFICATION FOR LEAD AND LEAD ALLOY STRIP, SHEET, AND PLATE PRODUCTS.
<br />6. ASTM E708 - STANDARD PRACTICE FOR DESIGN AND INSTALLATION OF RIGID PIPE HANGERS,
<br />E. AMERICAN WELDING SOCIETY:
<br />1, AWS D1.1 -STRUCTURAL WELDING CODE- STEEL.
<br />F. AMERICAN WATERWORKS ASSOCIATION:
<br />1. AWWA C105 -AMERICAN NATIONAL STANDARD FOR POLYETHYLENE ENCASEMENT FOR DUCTILE -IRON PIPE SYSTEMS.
<br />G. MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY:
<br />1, MSS SP 58 - PIPE HANGERS AND SUPPORTS - MATERIALS, DESIGN AND MANUFACTURER.
<br />2, MSS SP 67 - BUTTERFLY VALVES.
<br />3. MSS SP 69 - PIPE HANGERS AND SUPPORTS - SELECTION AND APPLICATION.
<br />4. MSS SP 78 - CAST IRON PLUG VALVES, FLANGED AND THREADED ENDS.
<br />5. MSS SP 89 - PIPE HANGERS AND SUPPORTS - FABRICATION AND INSTALLATION PRACTICES.
<br />6. MSS SP 110 - BALL VALVES THREADED, SOCKET -WELDING, SOLDER JOINT, GROOVED AND FLARED ENDS,
<br />H. NATIONAL FIRE PROTECTION ASSOCIATION:
<br />1. NFPA 54 - NATIONAL FUEL GAS CODE.
<br />L UNDERWRITERS LABORATORIES INC.:
<br />1. UL 842 -VALVES FOR FLAMMABLE FLUIDS.
<br />1.3 SYSTEM DESCRIPTION
<br />A. WHERE MORE THAN ONE PIPING SYSTEM MATERIAL IS SPECIFIED, PROVIDE COMPATIBLE SYSTEM COMPONENTS AND JOINTS. USE NON -CONDUCTING DIELECTRIC
<br />CONNECTIONS WHEN JOINING DISSIMILAR METALS IN SYSTEMS.
<br />B. PROVIDE FLANGES, UNIONS, OR COUPLINGS AT LOCATIONS REQUIRING SERVICING. USE UNIONS, FLANGES, OR COUPLINGS DOWNSTREAM OF VALVES AND AT
<br />EQUIPMENT CONNECTIONS. DO NOT USE DIRECT WELDED OR THREADED CONNECTIONS TO VALVES, EQUIPMENT,
<br />C. PROVIDE PIPE HANGERS AND SUPPORTS IN ACCORDANCE WITH ASME B31.9, ASTM F708, MSS SP 58, MSS SP 69, AND MSS SP 89.
<br />D. USE PLUG, BALL, OR BUTTERFLY VALVES FOR SHUT-OFF AND TO ISOLATE EQUIPMENT, PART OF SYSTEMS, OR VERTICAL RISERS.
<br />1.4 SUBMITTALS
<br />A. PRODUCT DATA:
<br />1. PIPING: SUBMIT DATA ON PIPE MATERIALS, FITTINGS, AND ACCESSORIES: SUBMIT MANUFACTURERS CATALOG INFORMATION.
<br />2. VALVES: SUBMIT MANUFACTURERS CATALOG INFORMATION WITH VALVE DATA AND RATINGS FOR EACH SERVICE.
<br />3. HANGERS AND SUPPORTS: SUBMIT MANUFACTURERS CATALOG INFORMATION INCLUDING LOAD CAPACITY.
<br />4. PIPING SPECIALTIES: SUBMIT MANUFACTURERS CATALOG INFORMATION INCLUDING CAPACITY, ROUGH -IN REQUIREMENTS, AND SERVICE SIZES FOR THE
<br />FOLLOWING:
<br />a. STRAINERS.
<br />b. NATURAL GAS PRESSURE REGULATORS.
<br />c. NATURAL GAS PRESSURE RELIEF VALVES.
<br />d. METERS
<br />B. DESIGN DATA: INDICATE PIPE SIZE. INDICATE LOAD CARRYING CAPACITY OF TRAPEZE, MULTIPLE PIPE, AND RISER SUPPORT HANGERS.
<br />C. TEST REPORTS: INDICATE RESULTS OF PIPING SYSTEM PRESSURE TEST.
<br />D. MANUFACTURER'S CERTIFICATE: CERTIFY PRODUCTS MEET OR EXCEED SPECIFIED REQUIREMENTS.
<br />E. WELDERS CERTIFICATES: CERTIFY WELDERS EMPLOYED ON THE WORK, VERIFYING AWS QUALIFICATION WITHIN PREVIOUS 12 MONTHS.
<br />1.5 CLOSEOUT SUBMITTALS
<br />A. PROJECT RECORD DOCUMENTS: RECORD ACTUAL LOCATIONS OF VALVES, PIPING SYSTEM, AND SYSTEM COMPONENTS.
<br />B. OPERATION AND MAINTENANCE DATA: SUBMIT FOR VALVES AND GAS PRESSURE REGULATORS INSTALLATION INSTRUCTIONS, SPARE PARTS LISTS, AND EXPLODED
<br />ASSEMBLY VIEWS,
<br />1.6 QUALITY ASSURANCE
<br />A. PERFORM NATURAL GAS WORK IN ACCORDANCE WITH NFPA 54,
<br />B. PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES AND LOCAL GAS COMPANY REQUIREMENTS.
<br />C. PERFORM WORK IN ACCORDANCE WITH ASME B31.9 CODE FOR INSTALLATION OF PIPING SYSTEMS AND ASME SECTION IX FOR WELDING MATERIALS AND PROCEDURES.
<br />D. PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES FOR WELDING HANGER AND SUPPORT ATTACHMENTS TO BUILDING STRUCTURE.
<br />E. FURNISH SHUTOFF VALVES COMPLYING WITH ASME B16.33 OR ANSI Z21.15.
<br />F. PERFORM WORK IN ACCORDANCE WITH LOCAL AND STATE CODES.
<br />G. MAINTAIN ONE COPY COPIES OF EACH DOCUMENT ON SITE.
<br />1.7 QUALIFICATIONS
<br />A. MANUFACTURER: COMPANY SPECIALIZING IN MANUFACTURING PRODUCTS SPECIFIED IN THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE.
<br />B. INSTALLER: COMPANY SPECIALIZING IN PERFORMING WORK OF THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE APPROVED BY MANUFACTURER,
<br />C. DESIGN PIPING SYSTEM HANGERS AND SUPPORTS UNDER DIRECT SUPERVISION OF PROFESSIONAL ENGINEER EXPERIENCED IN DESIGN OF THIS WORK AND LICENSED
<br />AT PROJECT LOCATION IN STATE OF NEW YORK.
<br />1.8 DELIVERY, STORAGE, AND HANDLING
<br />A. ACCEPT VALVES ON SITE IN SHIPPING CONTAINERS WITH LABELING IN PLACE. INSPECT FOR DAMAGE.
<br />B. PROTECT PIPING AND FITTINGS FROM SOIL AND DEBRIS WITH TEMPORARY END CAPS AND CLOSURES, MAINTAIN IN PLACE UNTIL INSTALLATION. FURNISH TEMPORARY
<br />PROTECTIVE COATING ON CAST IRON AND STEEL VALVES,
<br />1.9 ENVIRONMENTAL REQUIREMENTS
<br />A. DO NOT INSTALL UNDERGROUND PIPING WHEN BEDDING IS WET OR FROZEN.
<br />1.10 FIELD MEASUREMENTS
<br />A. VERIFY FIELD MEASUREMENTS PRIOR TO FABRICATION.
<br />1,11 COORDINATION
<br />A. COORDINATE TRENCHING EXCAVATING BEDDING BACKFILLING OF BURIED PIPING SYSTEMS,
<br />1.12 WARRANTY
<br />A. FURNISH FIVE YEAR MANUFACTURER WARRANTY FOR VALVES EXCLUDING PACKING.
<br />1,13 EXTRA MATERIALS
<br />A. FURNISH TWO PACKING KITS FOR EACH TYPE AND SIZE VALVE.
<br />PART PRODUCTS
<br />2.1 MATERIALS
<br />A. GAS PIPING SHALL BE STANDARD WEIGHT (SCHEDULE 40) BLACK STEEL PIPE. GAS CONTROL, VENT AND RELIEF PIPING SHALL ALSO BE STANDARD WEIGHT, SCHEDULE 40
<br />BLACK STEEL PIPE. STEEL PIPE SHALL BE SEAMLESS OR WELDED MADE IN ACCORDANCE WITH THE CURRENT EDITION OF THE ASTM A53 SPECIFICATION.
<br />1. IN NO CASE SHALL ANY GAS PIPE BE LESS THAN 3/4", THE SIZES OF PIPE INDICATE NOMINAL PIPE SIZE.
<br />2. GAS DISTRIBUTION PIPING FOR SYSTEMS OPERATING AT 1/2 PSIG OR LESS SHALL BE IN ACCORDANCE WITH ANSI Z223.1-1974 (NFPA-54) AND NATIONAL FUEL CODE
<br />3. GAS DISTRIBUTION PIPING SYSTEMS HAVING A GAS PRESSURE ABOVE 1/2 PSIG SHALL CONFORM TO ANSI B31.2-1968, FUEL GAS PIPING AND REQUIREMENTS OF THE
<br />INTERNATION FUEL GAS CODE
<br />4. PIPING JOINTS FOR GAS DISTRIBUTION PIPING:
<br />a. PIPING AT 1/2 PSIG (14" WC) AND LESS:
<br />1) 4" AND SMALLER... SCREWED
<br />2) -OVER 4"......,WELDED
<br />b. PIPING OVER 1/2 PSIG (14" WC) TO AND INCLUDING 3 PSIG:
<br />1) UNDER 4".....SCREWED
<br />2) 4" AND LARGER... WELDED
<br />c. PIPING OVER 3 PSIG:
<br />1) ALL PIPING..,. WELDED
<br />B. FITTINGS
<br />1. FITTINGS FOR SCREWED GAS PIPING SHALL BE 150 LBS. BLACK MALLEABLE IRON FITTINGS, CONFORMING TO ASTM A197, LATEST EDITION,
<br />2. COMPRESSION TYPE FITTINGS AND STEEL WELDING FITTINGS SHALL BE AS SPECIFIED AND APPROVED BY THE GAS COMPANY.
<br />3. STEEL BUTT WELDING FITTINGS SHALL CONFORM TO ANSI B16.9 REQUIREMENTS.
<br />4. FITTING FOR CONTROL, VENT AND RELIEF PIPING SHALL BE 300 LB. BLACK MALLEABLE IRON SCREWED FITTINGS CONFORMING TO ASTM A197, LATEST
<br />EDITION.
<br />C. FLANGES
<br />1. ALL FLANGES SHALL BE STEEL AND COMPATIBLE IN TYPE AND PRESSURE RATINGS WITH MATING FLANGE AND SHALL COMPLY WITH ANSI B16.5.
<br />2. FLANGES SHALL BE WELDING NECK OR THREADED END, SLIP ON FLANGES ARE NOT PERMITTED.
<br />3. WHERE 150 POUND STEEL FLANGES ARE BOLTED TO CLASS 125 CAST IRON FLANGES, THE RAISED FACE ON THE STEEL FLANGE SHALL BE REMOVED,
<br />D. GASKETS
<br />1. GASKETS SHALL BE COMPATIBLE WITH THE GAS SERVICE ON WHICH THEY ARE USED, WITHOUT CHANGE TO THEIR CHEMICAL OR PHYSICAL PROPERTIES,
<br />2. GASKET SHALL BE BLUE-GARD COMPRESSED ASBESTOS FREE GASKETS, STYLE 3000 OR GYLON GASKETING STYLE 3500, COLOR: FAWN WITH BLUE BRAND
<br />BOTH AS MANUFACTURED BY GARLOCK INC.
<br />1 GASKETS OF METAL OR METAL -JACKETS, ALUMINUM O-RINGS AND SPIRAL WOUND METAL GASKETS, OR OTHER MATERIALS, IF APPROVED BY THE UTILITY
<br />COMPANY MAY BE USED.
<br />4. FULL FACE GASKETS SHALL BE USED WITH ALL BRONZE AND CAST IRON FLANGES,
<br />E. BOLTS AND NUTS
<br />1 BOLTS AND NUTS SHALL BE OF BEST QUALITY BOLT STEEL WITH SQUARE HEAD BOLTS AND HEXAGON NUTS WITH MACHINE CUT V-THREADS.
<br />F, THREAD JOINT SEALANT MATERIALS
<br />1, THREAD SEALANT TO BE USED ON NATURAL GAS PIPING SHALL BE RECTORSEAL CORP NO. 5, OATEY GREAT BLUE PIPE JOINT COMPOUND HERCULES
<br />MEGALOC MULTI -PURPOSE THREAD SEALANT OR APPROVED EQUAL. THREAD SEALANT SHALL BE A NON -TOXIC, SOFT SETTING, SLOW DRYING SEALANT MADE
<br />FROM INERT FILLERS. THE JOINT SEALANT MATERIAL MAY CONTAIN TEFLON, IF THAT SUBSTANCE IS THE APPROVED TYPE FOR NATURAL GAS APPLICATION.
<br />APPROVED TEFLON TAPES MAY BE USED ON NATURAL GAS LINES. NON -APPROVED TEFLON TAPES FOR USE ON PIPING FOR A NATURAL GAS SYSTEM ARE
<br />PRONE TO TEARING WHEN PIPES ARE BEING ASSEMBLED AND TIGHTENED AND BITS OF TORN TAPE CAN MIGRATE INTO THE FLUID SYSTEM, CLOGGING
<br />VALVES, SCREENS, AND FILTERS.
<br />2.2 VENTING OF GAS PRESSURE REGULATORS
<br />A, REGULATOR THAT MAINTAINS A GAS LINE PRESSURE OR CONTROLS THE SUPPLIED GAS PRESSURE TO APPLIANCES OR EQUIPMENTS SHALL HAVE AN
<br />INDEPENDENT VENT PIPE ROUTED TO THE OUTSIDE OF THE BUILDING. THE VENT PIPE SHALL BE SO ARRANGED AS TO PREVENT THE ENTRY OF WATER OR
<br />FOREIGN OBJECTS
<br />2.3 FLEXIBLE GAS PIPE PASSING THROUGH A BUILDING SEISMIC JOINT
<br />A. A BRAIDED FLEXIBLE STAINLESS STEEL MULTIPLE LEGS PIPE ASSEMBLY SHALL BE INSTALLED IN GAS PIPING SYSTEM PASSING THROUGH A BUILDING SEISMIC
<br />JOINT OR BUILDING EXPANSION JOINT, WHEN REQUIRED, THE FLECIBLE PIPE CONNECTOR SHALL ALSO BE PROVIDED BETWEEN FLOORS TO RESTRAIN VERTICAL
<br />DISPLACEMENT IN GAS PIPING ARRANGEMENT THAT IS CAUSED BY A SEISMIC EVENT
<br />B. FLEXIBLE STAINLESS PIPE CONNECTOR SHALL INCORPORATE MULTIPLE LEG SECTIONS THAT ARE FORMED ON ANNULAR CORRUGATED STAINLESS STEEL HOSE.
<br />THE CONNECTOR SHALL COMPENSATE FOR PIPE MOVEMENTS IN 6 DEGREEES OF FREEDOM: 3 COORDINATE AXES, PLUS SIMULATENOUS ROTATION AROUND
<br />THOSE AXES, CONNECTOR SHALL BE CAPABLE TO RETRAIN DISPLACEMENT WITHOUT FAILURE FOR SEISMIC REQUIREMENTS LISTED IN SECTION BC 1621.1
<br />C. PROVIDE ACCEPTANCE BY OFFICE OF TECHNICAL CERTIFICATION AND RESEARCH (OTCR) TO UTILIZE THIS FLEXIBLE CONNECTOR FOR SEISMIC RESISTANCE IN
<br />GAS PIPING, IN ADDITION, CONNECTOR SHALL BE TESTED, LISTED AND LABELLED TO UL 536-2003 BY AN APPROVED AGENCY AND AS REQUIRED PER AC 28-113.4,
<br />ACCEPTABLE BRAIDED FLEXIBLE STAINLESS STEEL PIPE CONNECTOR SHALL BE SIMILAR TO TRI-FLEX LOOP AS MANUFACTURED BY FLEX HOSE.
<br />PART 3 - EXECUTION
<br />3.1 INSTALLATION
<br />A. GAS SERVICE AND GAS DISTRIBUTION PIPING, NUMBER AND DISTRIBUTION OF APPLIANCES, SHALL BE INSTALLED AS INDICATED ON THE DRAWINGS AND SHALL BE
<br />IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THE GAS COMPANY AND ACCORDING TO THE LATEST REGULATIONS OF THE ADMINISTRATIVE CODE OF
<br />THE CITY OF NEW YORK AND SHALL MEET THE REQUIREMENT OF THE DEPARTMENT OF BUILDINGS.
<br />1. CONTRACTOR SHALL ARRANGE FOR INSPECTION AND ADJUSTMENT OF ALL GAS APPLIANCES OF THE CONTRACT, SO THAT THEY WILL PROPERLY AND SAFELY
<br />OPERATE WITH NATURAL GAS.
<br />B. THE CONTRACTOR SHALL NOTIFY THE AUTHORITY WHEN ALL IS READY FOR THE GAS COMPANY TO EXTEND THEIR SERVICE PIPE TO THE STREET LINE; AND AGAIN
<br />AFTER TESTS, WHEN ALL IS IN READINESS FOR THE INSTALLATION OF THE METERS, THE METERS, OF THE PULSATING KIND IF A LONWORKS NETWORK IS
<br />PROVIDED, SHALL THEN BE CONNECTED WITH THE SERVICE PIPES, AND WITH THE SEVERAL LINES OF DISTRIBUTING PIPES. THE SETTING, PIPING AND
<br />CONNECTING UP OF THE METERS SHALL BE DONE IN ACCORDANCE WITH THE RULES OF THE GAS COMPANY,
<br />C. JOINT SEALING MATERIALS (PIPE DOPE) USED WITH SCREWED FITTING SHALL BE APPLIED SPARINGLY AND ONLY TO THE MALE THREADS OF PIPE JOINTS. THE
<br />BURRS MADE IN CUTTING THE PIPE SHALL BE REMOVED. PLUGGED TEES IN PLACE OF ELBOWS SHALL BE USED WHEREVER DIRECTED. WHERE PIPES OF
<br />DIFFERENT SIZES COME TOGETHER, REDUCING FITTINGS SHALL BE USED. NO BUSHING WILL BE PERMITTED.
<br />D. PIPING INSTALLED BELOW GRADE SHALL BE CONNECTED BY WELDING BY APPROVED CERTIFIED WELDERS, OR WITH COMPRESSION TYPE FITTINGS AS SPECIFIED
<br />AND APPROVED BY THE GAS COMPANY.
<br />a. SERVICE PIPING BELOW GRADE SHALL BE MILL WRAPPED IN ACCORDANCE WITH THE GAS COMPANY REGULATIONS.
<br />b. BACKFILL OPERATIONS SHALL BE STARTED ONLY AFTER WELDING INSPECTION, COATING INSPECTION AND TESTING HAVE BEEN COMPLETED AS PER
<br />REGULATIONS OF THE GAS COMPANY,
<br />E. INTER -CONNECTIONS BETWEEN PIPING AT DIFFERENT PRESSURE LEVELS IS NOT PERMITTED.
<br />F. GAS METER PIPING SUPPLYING GAS TO A BUILDING AT A PRESSURE IN EXCESS OF 1/2 PSIG SHALL BE PROVIDED WITH A PRESSURE REGULATOR TO REDUCE THE
<br />GAS PRESSURE TO 112 PSIG OR LESS UNLESS NOTED OTHERWISE.
<br />G. PROVIDE GAS LUBRICATED PLUG VALVES WHERE SPECIFIED, SHOWN ON DRAWINGS OR OTHERWISE REQUIRED FOR CONTROL OF GAS IN THE DISTRIBUTION
<br />PIPING; MAINS, BRANCHES AND AT THE BASE OF EACH RISER. INSTALL SLEEVES IN FLOORS FOR RISERS TO PASS THROUGH. AN ACCESSIBLE MANUAL GAS COCK
<br />OR LUBRICATED PLUG VALVE OF THE SAME SIZE AS THE PIPE SHALL BE INSTALLED AT EACH PIECE OF GAS BURNING EQUIPMENT, TO ALLOW FOR ISOLATION OF
<br />THE EQUIPMENT AND WHERE INDICATED ON DRAWINGS, ALL VALVES AND COCKS FOR GAS THROUGHOUT THE BUILDING SHALL BE TAGGED WITH NUMBERED
<br />METAL TAGS, INSTALL DRIP, CONSISTING OF NIPPLE AND CAP, AT THE BASE OF ALL RISERS AND CHANGES IN ELEVATION,
<br />H. GAS VALVES SHALL NOT BE INSTALLED IN CONCEALED LOCATIONS AND FURNACE PLENUMS. WALL ENCLOSURES, PIPE SPACES OR OTHER RECESS IN WHICH GAS
<br />VALVES ARE INSTALLED MUST BE VENTED TO AN ADJOINING VENTILATED AREA.
<br />1. IN NO CASE SHALL A GAS PIPE RUN THROUGH A HEAT DUCT OR STAIRWELL. THE CONTRACTOR SHALL DO ALL CUTTING AND BORING OF HOLES NECESSARY FOR
<br />EXTENDING PIPES AND BRANCHES, MAKING ALL NECESSARY OPENINGS IN WALLS, AND SHALL MAKE ALL REPAIRS TO SAME.
<br />J. ONLY GAS RANGES AND DRYER UNITS MAY BE CONNECTED WITH "FLEXIBLE CONNECTORS". ALL OTHER GAS BURNING EQUIPMENT MUST BE CONNECTED WITH A
<br />RIGID CONNECTION.
<br />K. FINAL CONNECTIONS TO BURNER PILOT LIGHTS AND BOILER GAS TRAINS SHALL BE MADE BY THE PLUMBING CONTRACTOR.
<br />L. ALL GAS PIPING TO EQUIPMENT ON ROOF SHALL BE RUN ON ROOF AND BE SUPPORTED SECURELY AS SPECIFIED IN HANGERS AND SUPPORTS,
<br />3.9 FLEXIBLE CONNECTORS
<br />A. FLEXIBLE RANGE CONNECTORS SHALL BE OF THE MINIMUM PRACTICAL LENGTH AND SHALL NOT EXTEND FROM ONE ROOM TO ANOTHER NOR PASS THROUGH
<br />ANY WALLS, PARTITIONS, CEILINGS OR FLOORS,
<br />B. FLEXIBLE CONNECTORS SHALL NOT BE USED 1N ANY CONCEALED LOCATIONS,
<br />C. FLEXIBLE CONNECTORS SHALL BE PROTECTED AGAINST PHYSICAL AND THERMAL DAMAGE AND SHALL BE PROVIDED WITH GAS SHUT OFF VALVES (COCKS) IN
<br />READILY ACCESSIBLE LOCATIONS IN RIGID PIPING UPSTREAM FROM THE FLEXIBLE CONNECTORS.
<br />3.10 PAINTING
<br />A. PAINTS AND COATINGS USED IN THE INTERIOR OF BUILDING TO MARK PIPING FOR IDENTIFICATION PURPOSES SHALL NOT:
<br />1. EXCEED THE VOC CONTENT LIMITS ESTABLISHED IN THE GREEN SEAL STANDARD GS-11 PINTS, FIRST EDITION, MAY 20, 1993.
<br />2. EXCEED THE VOC CONTENT LIMIT OF 250 G/L ESTABLISHED IN THE GREEN SEAL STANDARD GC-03, ANTI -CORROSIVE PAINTS, SECOND EDITION, JANUARY 7,
<br />1997.
<br />B. ALL EXPOSED GAS PIPE SHALL RECEIVE ONE (1) COAT OF TNEMEC 10-99 OR BENJAMIN MOORE IRON CLAD RETARDO RUST INHIBITIVE PRIMER PAINT AND ONE(1)
<br />FINISHED COAT OF SAFETY YELLOW. GAS VENT PIPING EXPOSED TO PUBLIC VIEW OUTSIDE THE BUILDING SHALL RECEIVE ONE (1) COAT OF TNEMEC 10-99 OR
<br />BENJAMIN MOORE IRON CLAD RETARDO RUST INHIBITIVE PRIMER PAINT AND ONE COAT OF FINISHED PAINT SELECTED BY THE FILING ARCHITECT,
<br />C. MILL -WRAPPED PIPING SHALL NOT BE PAINTED.
<br />D. PIPING AT DIFFERENT PRESSURE LEVELS IN THE SAME SPACE SHALL BE COLOR CODED AND LABELED,
<br />3.11 LABELING
<br />A. GENERAL REQUIREMENTS: GAS PIPING OPERATING AT DIFFERENT PRESSURES SHALL HAVE LABELING MARKERS INDICATING OPERATING PRESSURE WITHIN THAT
<br />PIPING.
<br />B. ALL VALVES SHALL BE SUITABLY TAGGED TO INDICATE THE OPERATING PRESSURE LEVEL WITHIN THE DISTRIBUTION PIPING.
<br />3.13 DEMONSTRATION
<br />A. THE SERVICES OF A FACTORY TRAINED REPRESENTATIVE SHALL BE AVAILABLE ON THE JOB SITE FOR START-UP AND FOR INSTRUCTING THE BUILDING MANAGER
<br />IN THE OPERATION AND MAINTENANCE OF THE GAS SAFETY SHUT-OFF VALVES AND THE CENTRIFUGAL GAS BOOSTER SYSTEM,
<br />3.14 FIELD QUALITY CONTROL
<br />A. TESTING
<br />1. GENERAL
<br />a. GAS PIPE WELDING IS SUBJECT TO ALL TESTS REQUIRED BY THE AUTHORITY AND SPECIAL INSPECTION REQUIREMENTS OF THE MEMPHIS BUILDING
<br />CODE.
<br />b. COOPERATE WITH THE TESTING LABORATORY IN MAKING ALL REQUIRED TESTS.
<br />1. TESTING LABORATORY
<br />a. THE AUTHORITY WILL ENGAGE A TESTING LABORATORY OR SPECIAL INSPECTION AGENCY TO PROVIDE THE INSPECTION AND SPECIALTY TESTING.
<br />b. THE TESTING LABORATORY WILL BE RESPONSIBLE TO AND UNDER THE SUPERVISION OF A SPECIAL INSPECTOR.
<br />c. THE LABORATORY WILL PERFORM THE FOLLOWING TESTING.
<br />1) ALL WELDED GAS DISTRIBUTION PIPING, LESS THAN OR EQUAL TO 3 PSIG: IN ADDITION TO INDEPENDENT PRESSURE TESTING OF THE ENTIRE
<br />SYSTEM, AT LEAST TEN (10) PERCENT OF ALL WELDS OTHERWISE NOT REQUIRED TO BE NON-DESTRUCTIVELY TESTED WILL BE SUBJECT TO NOW
<br />DESTRUCTIVE TESTING (RADIOGRAPHED AND/OR SUBJECTED TO ULTRASONIC TESTING). THE MINIMUM SAMPLING SHALL BE FIVE (5) WELDS.. ALL
<br />WELDS SHALL BE RADIOGRAPHED AT THE CONTRACTOR'S EXPENSE IF ANY FAILURE OF ANY OF THE SAMPLES IS FOUND. CONTRACTOR SHALL MAKE
<br />ALL NECESSARY REPAIRS AT NO COST TO THE OWNER.
<br />2) ALL GAS DISTRIBUTION AND METER PIPING OVER 3 PSIG: ALL WELDS WILL BE RADIOGRAPHED.
<br />2 SPECIAL INSPECTOR
<br />THE AUTHORITY WILL ASSIGN A SPECIAL INSPECTOR TO SUPERVISE THE TESTING. THE SPECIAL INSPECTOR WILL VERIFY THE QUALIFICATIONS OF THE
<br />WELDER
<br />3. NOTIFICATION: BEFORE ANY WORK IS COMMENCED ON AN ITEM OF CONSTRUCTION REQUIRING SPECIAL INSPECTION, ALL PERSONS RESPONSIBLE FOR SUCH
<br />SPECIAL INSPECTIONS SHALL BE NOTIFIED IN WRITING AT LEAST SEVENTY TWO (72) HOURS PRIOR TO SUCH COMMENCEMENT.
<br />3.16 FLEXIBLE GAS PIPE PASSING THROUGH A BUILDING SEISMIC JOINT
<br />A. INSTALL BRAIDED STAINLESS STEEL FLEXIBLE PIPE CONNECTOR AT BUILDING EXPANSION JOINTS AND /OR WHERE REQUIRED TO MANAGE PIPE MOVEMENT THAT
<br />IS DUE TO A SEISMIC EVENT. PIPE CONNECTOR SHOULD NOT BE SUBJECTED TO TORSIONAL, TENSILE OR EXCESSIVE BENDING STRESSES.
<br />1. INSTALLATION GUIDELINES SHALL BE AS PER THE MANUFACTURER'S INSTRUCTIONS.
<br />2. PROTECT FLEXIBLE PIPE CONNECTOR AGAINST MECHANICAL INJURY.
<br />3. INSTALLATION OF THE FLEXIBLE PIPE CONNECTOR IS SUBJECT TO THE SPECIAL INSPECTION REQUIREMENTS OF THE MEMPHIS FUEL GAS CODE.
<br />4. ALL SHIPMENTS AND DELIVERIES OF THIS FLEXIBLE PIPE SHALL BE ACCOMPANIED BY A CERTIFICATE OR LABEL DECLARING THAT THE MATERIALS SHIPPED
<br />OR DELIVERED ARE EQUIVALENT TO THOSE TESTED AND APPROVED.
<br />0
<br />0
<br />U
<br />ID
<br />a
<br />a
<br />a
<br />a
<br />a
<br />Q
<br />c
<br />m
<br />Permit/Seal
<br />2021-03-05
<br />Project No.:
<br />File Name: N/A
<br />Author Designer Checker 03/05/21
<br />Dwn. Dsgn. Chkd. YYYY.MM.DD
<br />Title
<br />GAS SPECIFICATIONS
<br />Revision:»
<br />{ Y 7 IT
<br /><Pick location in Project Information>
<br />3/5/2021 7:10:31 PM
<br />
|