LEGEND <br />0,4 1 2 3 4 5 0 7 8 9 10 1 1 12 13 14 15 <br />GENERAL MOTES <br />— — A 1. CONDUIT: 1 /2" MINIMUM, 3/4" MINIMUM FOR ALL <br />—_ — — B CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER, <br />GROUND WIRE. <br />2, HOMERUNS UNLESS NOTED OTHERWISE. 3/4" FLEX WITH <br />INSULATION TYPE THHN/THWN, UNLESS OTHERWISE <br />— — — — C NOTED. <br />3. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTORS <br />WHICH DO NOT HAVE APPROPRIATELY COLORED <br />INSUI ARE ACCESSIBLE, IDETION WITH ®RFYAPE INSULATEDVER CONDUCTORS <br />— Q CONDUCTORS PER NEC 250-57(b) EXCEPTION <br />1,b OR c (USING TAPE). COLOR CODE AS FOLLOWS: <br />208Y 120V 480Y 277V <br />A 0 (LEFT BUS IN PNL) BLACK BROWN <br />B 0 CENTER BUS IN PNL) RED ORANGE <br />C 0 RIGHT BUS IN PNL) BLUE YELLOW <br />— — — NEUTRAL WHITE GRAY <br />EQUIPMENT GROUND GREEN GREEN <br />ISOLATED GROUND GRN/YEL* GRN/YEL* <br />*GREEN WITH YELLOW TRACER <br />4. TAPE LABEL EACH RECEPTACLE, JUNCTION/OUTLET <br />BOX AND SWITCH WITH CIRCUIT IDENTIFICATION, <br />J F 5. POST NEW OR REVISED PANEL SCHEDULES UPON <br />COMPLETION OF JOB. <br />—� 6. THE ENTIRE BASEMENT AREA OF THIS BUILDING IS <br />¢ RATED AS HAZARDOUS, CLASS 1, DIV I. PROVIDE <br />EXPLOSION PROOF ELECTRICAL EQUIPMENT AND <br />UP <br />CONDUIT SEALS PER NEC REQUIREMENTS. <br />REFERENCE DRAWINGS <br />45-001-E701-026 A-013 REMOTE 1/0 PANEL ELEVATION <br />AND WIRING (CSI DRAWING) <br />45-001-1 E214 LEAK DETECTION PANEL AB <br />— -- }-� 45-001-E533 LEAK DETECTION SYSTEMS AND DETAILS <br />45-001-E700 LEAK DETECTION PANEL CONTROL <br />4 1 "C, 414, (1)18TSP, 12G <br />rL <br />WIRING DIGRAM (AB) <br />3 <br />2 45-001-OM 170-12A PARTIAL PIPING PLANS <br />ur 45-00`I-M317-1 PROCESS AND INSTRUMENT. DlAGRAI�I <br />[!---.'-REMOTE 1/0 PNL S <br />CONSTRUCTION MOTES <br />4 3/4" C, (1)18TSP 2 — — PROVIDE AND INSTALL REMOTE 1/0 PANEL. SEE CSI <br />DETAIL SHEET FOR REQUIREMENTS. COORDINATE EXACT <br />3 3 MOUNTING LOCATION WITH BOEING CONSTRUCTION <br />MANAGER. <br />9 <br />#12G <br />TO PLC, COL N/4.5 \ 2e PROVIDE AND INSTALL HOMERUN CONDUITS WITH WIRE <br />AND FIBER CABLES AS INDICATED. PROVIDE CORE <br />199C, 3PR FO C 'LE UP <br />DRILLING THROUGH BASEMENT WALLS TO LOCATION <br />A TO PLC, COL /4.5 SHOWN. CORE DRILL THROUGH CEILING TO THE FIRST <br />— — FLOOR, THEN SURFACE MOUNT TO NEW PLC PANEL. <br />6 C5yyyp 14 TO MCG-12 A <br />1 "C PROVIDE EXP. PROOF SEALS. <br />9 471 / 9 C6 6 � <br />I,--� PROVIDE AND INSTALL VALVES, FLOW, PRESSURE, AND <br />LEVEL INSTRUMENTS PER MECHANICAL DRAWINGS. <br />2 UP TO 1ST FLOOR <br />PROVIDE AND INSTALL CONDUIT AND WIRE FROM <br />INTRINSICALLY SAFE REMOTE 1/0 PANE TO <br />INSTRUMENTS. TERMINATE CONDUITS IN NEMA 4X <br />JBOXES. ROUTE INSTRUMENT CABLES INTO JBOX <br />USING EXPLOSION PROOF CGB CONNECTORS. <br />1 1 <br />5. PROVIDE "INSTRINSICALLY SAFE" LABELS ON CONDUIT <br />q — — — m A AND ENCLOSURES PER NEC 504.80. <br />0.4 1 3 3 7 9 11 13 15 <br />, PROVIDE AND INSTALL HOMERUN CONDUITS AND <br />i f A CONDUCTORS AS INDICATED. PROVIDE CORE DRILLING <br />THROUGH BASEMENT WALLS TO LOCATION SHOWN. <br />c CORE DRILL THROUGH CEILING TO THE FIRST FLOOR <br />J / TO MCC. PROVIDE EXP. PROOF SEALS. <br />E <br />i G <br />— — — <br />CL P // DE210 N I <br />® ❑ i <br />K <br />0 <br />Q <br />R <br />a <br />KEY PLAN BLDG. 45-01 <br />I <br />SOLE: NONE <br />I <br />PLAN VI EW <br />n ineern <br />/ 99- 7 99 <br />SCALE: 1 1 -1 -0 <br />N <br />3545 FACTORIA BOULEVARD SE'., SUITE 200 <br />DELLEvt/E, WA 98006 <br />m <br />(425) 522-1000 WWW. CASNE. COI JOB NO. 191-171 <br />SYM <br />REVISION <br />BY <br />APPROVED <br />DATE <br />SYM <br />REVISION <br />BY <br />APPROVED <br />DATE <br />SAND/O <br />DRAWN <br />DATE <br />10.02.19 <br />SUBTITLE <br />CURRENT REVISION <br />SYMBOL <br />A <br />DATE <br />AI <br />CONTROLS <br />20808468 <br />06.20.20 <br />ORIG <br />A 0808468 <br />SITE PUMP INDUSTRIAL WASTE 2 <br />AS <br />C �lE <br />JEA <br />03.20.20 <br />THIS <br />CHECASCKED <br />SPECIFICATION IS APPROVED <br />SHEET <br />A <br />SITE PUMP INDUSTRIALWASTE — RF1-007 20808468 <br />vA,S�IE <br />EE!� <br />00.29.20 <br />® <br />APPROVED BY <br />DEPT. <br />DATE <br />ENGlN R <br />TITLE SITE PUMP INDUSTRIAL WASTE <br />OE21 0 <br />CHECKED <br />BUILDG I, <br />JOB NO. <br />COMP NO. <br />APPROVED <br />0 <br />APPROVED <br />ELECTRICAL MASTER COL. A-R/1-15 <br />EVERETT, WA <br />owc Nfl. 45-01-OE210 <br />