Laserfiche WebLink
7/12/2022 Page <br /> City of Everett <br /> 6:43:02AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. FA2202-007 Site Address 2118 38TH ST <br /> Applied 2/15/2022 Applicant DESIREE FORQUIGNON Lot <br /> Approved 3/2/2022 Owner GKR LLC Block <br /> Issued 3/3/2022 Contractor GUARDIAN SECURITY Tract <br /> Parent Permit No. Description FIRE ALARM SYSTEM,INSTALLING(70)DEVICES <br /> Notes <br /> Scheduled Completed Tyne Inspector Result Remarks Inspector's Comments <br /> 4/25/2022 AM 4/25/2022 FA 01-FIRE KAB CORRECTION See Notes (3/30/2022 11:48 AM KAB) <br /> ALARM SYSTEM Greg Tisdel 425-231-7401 <br /> (4/25/2022 1:19 PM KAB) <br /> 4/25/22 Fire Alarm Acceptance Test:24 <br /> hour battery test,Initiation Devices, <br /> Audible&Visual,and Self-closing doors, <br /> Passed. <br /> Corrections needed:Flow Test,Control <br /> Valves,two horn/strobes needed to be <br /> located on the exterior of the buildings,One <br /> hom/strobe needed to be located in break <br /> room,and FACP signs needed on exterior of <br /> all bildings directing to the appropriate <br /> FACP location. <br /> 7/11/2022 AM 7/11/2022 FA 01-FIRE JA APPRVD-PERt eTRAKiT Inspection 7/6/2022 11:19 AM Charity Odushkin <br /> ALARM SYSTEM Request Ivan Odushkin 360-820-5851 we are <br /> requesting a 3pm FF <br /> Contact Name:Charity Odushkin <br /> Site Address:2118 38TH ST <br /> Phone:4252002724 <br /> e-Mail:cdushkin@guardiansecurity.com <br /> INSP12 C SYE.TE S <br />