6' — p // <br />WATER NOTES <br />1. All work and materials shall conform to the City of Everett <br />Standards and APWA Standard Specifications as noted. <br />2. No part of the water system shall be covered, concealed or put <br />into use until it has been tested, inspected and approved by <br />the City Inspector. <br />3. Approximate locations of existing utilities have been obtained <br />from available records and are shown for convenience. The <br />contractor shall be responsible for verification of locations <br />and to avoid damage to any additional utilities not shown. No <br />warranty is expressed or implied as to the accuracy or <br />completion shown. The contractor shall call Dial -Dig 48 hours <br />prior to construction. If conflicts with existing utilities <br />arise during construcion, the contractor shall notify the <br />Public Works Inspector and any changes required shall be <br />approved by the City Engineer prior to commencement of related <br />construction on the project. <br />4. All water main extensions within the public right-of-way or in <br />easements must be "staked" by survey for "line and grade" <br />prior to starting construction. <br />5. Contractor shall notify engineer a minimum of 48 hours in <br />advance of all requests for staking, testing or inspection. <br />6. Contractor shall furnish shop drawings for approval where <br />required by the detailed specifications and for variation from <br />the engineers design. <br />7. Contractor shall install equipment in accordance with the <br />manufacturers recommendations. <br />8. All water main to be ductile iron pipe Class 52 <br />9. 3 1/2 foot minimum cover. <br />10. Live taps for service connections to be by a contract approved <br />by the City of Everett Public Works Department. <br />11. No changes are to be made without written approval by the <br />City. <br />12. Coordinate service locations with the City Water Department. <br />13. Contractor is responsible for verifying all existing pipe <br />types and sizes for couplings, connections, cut -ins and live <br />taps. <br />14. Contractor is responsible for control required at the time of <br />staking. <br />15. Unstable foundation material shall be removed and replaced <br />with minimum depth of 3 1/2 minus angular foundation rock. <br />16. Deflections limited to City standards. <br />17. Each sheet of this plan set indicates engineering design for <br />items as specified by the sheet title. Other utility <br />locations indicated as background information are approximate <br />only. These are shown to provide information relative to <br />potential conflicts. The specific design sheet must be <br />referenced for detailed construction information for each <br />utility road or any additional construction items. <br />_ 36" —{ <br />I <br />DINT <br />L <br />NOTE: 1. CONCRETE SHALL BE CLASS 5 (1 - 1/2) PORTLAND CEMENT CONCRETE FOUR (4) <br />INCHES THICK OVER A BASE OF 2" OF COMPACTED CRUSHED SURFACING. <br />2. 3/16" JOINT MATERIAL (FULL DEPTH) PLACED AROUND THE_ HYDRANT L'EFORE <br />PLACING CONCRETE. <br />CONCPE"Ttz- NYO1P,QNT z;0 0 <br />IV 77 S <br />II� — MECUA-NIGALLY PLACED <br />Ill ►.1A71VE BA.GKFILL. <br />-� tlli <br />I ci( <br />It /" NAkJD PLACED <br />SELEC-T 6ALKFILL <br />O , <br />W a VARIES <br />U_ 1 io <br />/i1lr� _ -, r/_/rt'- 6EODII.Ict GRAVEL As <br />REDu1RF-0 6Y SOIL COtJDITI0tJ5 <br />TYP I C,AL TREQCu SECT 10 U <br />U0 5C.ALE <br />0 O r__\ Large Meter Box <br />Grownd Levc•1 <br />2" Galy. Iron Pipe <br />Valve Box per <br />Sec. 5.3.12 - <br />(1" Blot.' -off metal <br />MI Cap <br />thrust plaice 1/2 .• 6' <br />(Ford C1G-77 Pack <br />�'•�- <br />- <br />joint w/2"xl„ <br />nrin.) <br />brass bushing) <br />Swing Joint <br />3-2" Galv. Elbows <br />Brass Nipple <br />2' G.V. per Sec. 5.3 12 <br />(1" Ford 1'1700 Corp Stun; <br />_ <br />x 6" Copper or Brass nipple. <br />6' <br />(None on 1") <br />Max. <br />3/4" tie rods -2 required <br />- Concrete AllChor docks - <br />Coia�rcte hlociu ng is Placed <br />oi: vices of pipc - not top <br />and hottom. <br />NOTE 1" DETAIL SHOWN [N <br />PARBN''i'iH.SES ( ) <br />CONCR;TE ANCHOR BLOCKS <br />iS ow - <br />Minimum Size for <br />Off <br />Water Main Size <br />Block <br />Size <br />2" <br />1 cubic ft. <br />1" <br />4" <br />8 cubic ft. <br />2" <br />6" <br />18 cubic ft. <br />2" <br />8" <br />33 cubic ft. <br />_ <br />12" <br />75 cubic ft. <br />16" <br />125 cubic ft. <br />2 BL 0G4/- OFF 5SZ/V48Z)' <br />N. T. S <br />�1/4" Rake Per Ft. From <br />Ground Level <br />Traffic Safety Feature <br />{� Break -off Flange, Break-i <br />off Nuts and Bolts <br />1 j <br />Cate Valve <br />SEE NOTE ; I I <br />F.BAA #106 <br />/RETAINER GLANDS- <br />Paint per 5.3.15.1 <br />Cast Iron Adjustable Valve Box <br />per Sec. 5.3.12 (see Note 10) <br />Cast Iron Tee <br />MJxMJxFL or <br />MJxMJxFL <br />• o <br />Tapping Tee <br />Pp g <br />9. . <br />18"xl8"x4" Come. Blk. <br />MJxFL Valve <br />I, <br />1 <br />NDISTURBED HYDRANT CONNECTION PIPE TO BE DUCTILE IRON <br />EARTH CLASS 53. ANY INTERMEDIATE JOINTS TO BE MJ <br />1/2 CU. YD. WASHED ROCK WITH RETAINER GLANDS <br />1-1/2" Minus <br />NOTES: <br />1. Hvdrants and all materials to be APWA or AWWA approved (Mueller, A-423), <br />(H. and H. 429 Reliant). <br />2. 5-1/4" Valve Minimum. <br />3. 1-1/4" Operating Nut and Cap Nuts. <br />4. National Standard Threads on 2-1/2" Ports. <br />5. Everett/Puyallup Thread on the 4-1/4" Port. <br />6. If Hydrar.t Rises Through Concrete, Use Expansion Strip Around Hydrant Barrel. In <br />Addition, the Installation of the Hydrant On Private Property Shall Equal or <br />Exceed STandards Set Forth for the Installation of Public Fire Hydrants in the <br />City of Everett. <br />7. Provide for Vehicular Traffic Protection When Necessary. <br />8. Steamer fort to be Facing Street or Roadway for Fire Engine Access. <br />9. Break -off Flange to be 2" Above Ground Level. <br />10, When Located in Concrete or Asphalt, Use Cast Iron Valve Box. A Plastic Boy. <br />With Iron Lid May be Used in Sod Areas. <br />171Y401PlI N T 45SZ/VOZ y <br />7-s <br />Pit'ESSUiPc� TA/1' <br />O/ , ,gP�/fvvEo E <br />BOOSTE/P �UMr <br />%a 6/l,9CCG/v <br />✓E�FU/�P - ®E.f <br />�'/ODEL S h'S <br />/!Pf'/PO//ED EQ <br />J'CiPEEn/ED <br />/�iPESSU/PE /f zkL ii4LVE+ <br />�L UMB TO OUT S/OE Of <br />BU/LO/N6 <br />PiPESSI//PE GU/4GE� <br />i <br />70 f/OLfSE <br />�,PESSU/PE Sh//TG"h" <br />OFF � 40Ps/' <br />ON ® 30 Psi" <br />.BOOSTER PUrlP : �— <br />%2 h .5'N�GLOIf/ GYEIL <br />JE TPPUMP -BE/P�ELE� <br />i'-/OOE/ S.fS Opt' <br />Af'P/POf/ED EQU,9G <br />Z 6�6�8'v <br />iNsv�4 rEo Doo.P <br />J <br />�-�PiPESSU/PE TANK: <br />.BE/E'KELEY <br />f fE- f'ieZ 1/17/ZEO <br />lVATE/P TA/Vrt' <br />MODEL BT /ZO O/P <br />APP/PO!/EO EQC/,4L <br />SCoPEENEO <br />CO/✓TiPOL /PANEL <br />CNEMA-/ E/VCLOSUPEi 0 <br />I <br />b <br />'Zow-, <br />/�L/MP Sf1UT-OFF <br />60o G/9LC O1V (-i1i/VJ //vATE/P S'TO/P,4GE TANA- <br />�UNOE/PG/POUNO 9/�i�iPO!/EO FO/P f'OTfLBL E <br />�vgTE,�J <br />/A0L//yii0 14100SE_ LAYOUT <br />yATE.P N. 7 S. <br />syvT-OFF <br />vvv ��`��,. , ,,,,•J .,�,.PAGE <br />TANS �UNo�.�G�OUNO, ,4�i�iR��'ED FOP <br />IOTA L E l�YArEP� <br />SECT/O/V <br />/uers <br />,11Z4S7_EiP d1C9TE/P /A1 TE/P <br />UT/L/TX vAUL T .3642- L'A—% <br />D/P ='_cVa,4L <br />EX/ST//V6 T/P,4NS/`%/SS'/ON P/r'� <br />S C'/TY OF EI/E/PETT TO <br />�iLi'iN.� � h/OT T/9/' A/✓O P/POI�/D <br />0 cSE/F i�/CE TO L//VE <br />6 "O./.P (-Cl.SZJ <br />eESSU/PE /PEDUC/NG ! ZkL -, <br />ET FO/P SO A-.S/" <br />FLOAT !/.4L!/E <br />tSSOTGOiPAG'E O7XIV //V� LYATEiP <br />ZE���4 <br />• <br />LOl/v !1/4TE/P <br />PUMP "ZIr- OFF <br />� �� - CO3Pi-OR,47-101V sTO� <br />- CY.9TE�f' METE.P <br />- f'/FEcSS'U/PE /PE.DUC//1/G l��lL!/E <br />< <br />BOO�S'TEiP PUMP : <br />"�0 � 3 - GATE ///9L JiE <br />P.PEss. SA117C/v <br />OFF ¢pPs/ <br />/2 h SA14_1Z01y My ZZ JET PL/Mf <br />BE/i'KELEY MODEL S NS O,P <br />on/ � j0 Ps, <br />gfi�iPOIiEO EQ//.9L <br />- TEE <br />�PESSUeE /PEL/EF l/4Ll/E <br />i'PESSU/PE TANK:-3 <br />- !/N/ON <br />BE.PKELE�' /�iPE-f%F'ESSU.P/cE0 T.4Nii' <br />MODES BT 120 0/ , <br />h/a SE BiBB <br />,4f�iPO/�EO EQL/.9L <br />PRESS!/,PE GUgGE <br />P - �S'TO�P�4GE <br />8" Iin • ,,, <br />CO�//1/ECT/ON <br />O�'T,q/< <S <br />ocoJ �� <br />o �!o Z4 <br />Nv� 5 <br />W� 0 =>�0 <br />Z Z Y� I Z F <br />�? J CZ <br />J <br />WO <br />WZI=I,,v 0M <br />V OR 11L V <br />N <br />(� <br />N <br />in <br />a\ - Romac, Rockwell, or Mueller single or OL -- Meter Shall: <br />double strap service clamp with C.C. 3/4" *Ford 1-31-23, O <br />thread or I.P. thread to be used )n all Mueller 11-14200 <br />mains less than 6" diameter and on all A.C. Ford L-31-23 w/1115073 <br />mains. Double strap clamps to be Used Mueller IP14200 w/1115426 v <br />for 2" services. 1"`Ford 1. 31-44, Mueller <br />1114200 <br />aII — Corporation Stops Ford 1-31-44 w/15073 <br />3/4" *Mueller H15000, Ford 1`1000, 1100 Mueller H-14200 01115426 <br />1" Mueller 1115005, Ford F1000, 1100 2" Ford LF-3177 <br />2" Ford FB400, 500 w/c/-14-77 or <br />C-84-77 if 900 ell is used atrl o- AM1crter Boxl� <br />w/ss insert. C-86-77 for Pfi 1'.ipc. 3/4" Brooks standard series 1� <br />Copper, Polyethylene or polybutyl€ne 1419 (plastic) <br />line per Sec. 5.3.18. Fog Tice fi1D (concrete) <br />1" Brooks standard scrip <br />Meter Stops 1419 (plastic) `�1J <br />3/4"*Ford KV23-332W, ;luelier 11-14:50 Fug 'Fit, ") D (concrcte) <br />Ford KV23-332W w/1115073 2" Brooks .Jumbo series 132.4 <br />Mueller H14250 w/H15426 (Plastic) <br />1" *Ford KV23-444W, Mueller H14'50 Fog Titr '12D (concrete) <br />Ford KV23-444W w/1115073 Fog t to shall have full <br />Mueller 1114250 w/H15426 sized lids. <br />2" Ford KVC-3-777W <br />Q- Meters to reacl F1 <br />V4" Badger model #25, 9" E�f'�IM/NED ,4N0 Af9�iPOIVE0 FO,P COI/STiP�/CT16W <br />NO'rli: All new taps on existing water laying length. q <br />mains will be done by the City 1" Badret model 11F40,10-3/4" 71 Q 4)1 0/ / <br />Water Department it the• dove]opers' laying Ic'nglh. / <br />or c•onCrnctcrrs' cxlicnsc'• �" I'adre•r np,d,•I t!I:'(I, 17" <br />lavLug Ic�ngtl:. <br />*Denotes fittings to be used with C�_ Pack Joint /Comhres>loll Fittin�,. <br />copper services. C/Ty OF Z-i1f/PE%1T j T/TLE L <br />`V472 P �S'EiP!//CE 0ET.4/L o <br />2 of z <br />