<br />R1, SEPARATE SANITARY FACILITIES SHALL BE PROVIDED FOR EACH SEX WHEN THE
<br />NUMBER OF EMPLOYEES EXCEEDS FOUR, PLUMBING FACILITIES SHALL BE
<br />PROVIDED IN ACCORDANCE WITH CHAPTER 20,
<br />R2. ALL TOILET ROOMS SHALL BE VENTILATED WITH 5 AIR CHANGED PER HOUR BY
<br />MECHANICAL MEANS.
<br />R3. PROVIDE ADEQUATE CONCEALED .BLOCKING AND ANCHORING FOR ALL CEILING
<br />AND WALL MOUNTED EQUIPMENT, HARDWARE AND ACCESSORIES.
<br />R4. ALL RESTROOM WALLS AND THE WALLS OF ANY OTHER ROOM CONTAINING
<br />WATER SOURCES SHALL BE FINISHED WITH CEMENT BACKING BOARD (OR
<br />EQUAL), FULL HEIGHT OF THE WALLS.
<br />CONSTRUCTION INSPECTIONS
<br />CI-1 GENERAL CONTRACTOR SHALL PROVIDE AND COORDINATE ALL INSPECTIONS
<br />NECESSARY FOR CONSTRUCTION ACCORDING TO THE CITIES REQUIREMENTS,
<br />IF •
<br />26. ALL CONDUIT AND OTHER ELECTRICAL EQUIPMENT MUST BE SUPPORTED FROM
<br />THE STRUCTURE ABOVE, ABSOLUTELY NO EQUIPMENT MAY BE SUPPORTED
<br />FROM THE CEILING, ANY OPENINGS CUT INTO THE ACOUSTICAL CEILING TILES
<br />SHALL BE CUT TO THE EXACT SIZE REQUIRED IN ORDER TO MAINTAIN ANY
<br />MATERIAL RATINGS
<br />27, ELECTRICAL DESIGN HAS BEEN BASED ON THE INSTALLATION OF 75 DEGREES C
<br />CONDUCTORS CONNECTED TO TERMINAL EQUIPMENT,
<br />O S CONNE L LUGS AND EQUIPM N , UL LISTED FOR
<br />A MINIMUM 75 DEGREES C CONDUCTORS TERMINATED ON EQUIPMENT WITH A
<br />LOWER RATING (60 DEGREES C) OR NO RATING SHOWN, SHALL HAVE
<br />CONDUCTOR SIZE INCREASED TO CONFORM TO N.E.C. TABLE 310-16 AND UL
<br />NO.4B9 REQUIREMENTS
<br />2, ALL SWITCHBOARDS, PANEL BOARDS, DISCONNECT SWITCHES AND
<br />CONTRACTORS, SHALL BE PROVIDED WITH LUGS LABELED AND RATED FOR A
<br />MINIMUM 75 DEGREES C. SWITCHBOARDS, SPC, PANEL BOARDS, DISCONNECT
<br />SWITCHES,N RS AND "LISTED"
<br />CONTRACTORS � TRANSFORMERS ARE TO BE �ISTED AND
<br />"IDENTIFIED"
<br />AS RATED FOR A MINIMUM OF 75 DEGREES C CONDUCTOR
<br />TERMINATION
<br />2, AT THE CONCLUSION OF THIS PROJECT, THE ELECTRICAL CONTRACTOR SHALL
<br />PROVIDE AN UPDATED TYPEWRITTEN DIRECTORY INSIDE EACH PANEL BOARD
<br />PROPERLY IDENTIFYING EACH CIRCUIT USED AND THE SPECIFIC LOAD SERVED
<br />30. CONTRACTOR SHALL COORDINATE INSTALLATION OF UTILITIES ABOVE THE
<br />CEILING TO PROVIDE THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION
<br />OF AND FURTHER CHANGES TO THE MECHANICAL, PLUMBING AND FIRE
<br />SPRINKLER SYSTEM, TEC, CONDUIT AND PIPE TO BE RUN TO MAXIMIZE USE OF
<br />CEILING SPACE FOR USE BY OTHER TRADES
<br />31, ALL CIRCUIT BREAKERS, FUSES AND ELECTRICAL EQUIPMENT SHALL HAVE AN
<br />�O
<br />INTERRUPTING RATING NOT LESS THAN THE MAXIMUM SHORT CIRCUIT
<br />CURRENT TO WHICH THEY MAY BE SUBJECTED
<br />32. ALL DEVICES INSTALLED OUTSIDE OR IN DAMP LOCATIONS SHALL BE APPROVED
<br />WEATHERPROOF
<br />33, THE E,C, SHALL NOT BORE, OTCH OR IN ANYWAY CUT INTO ANY STRUCTURAL
<br />MEMBER WITHOUT WRITTEN APPROVAL FROM THE ARCHITECT OR STRUCTURAL
<br />ENGINEER, INSTALL CONDUITS FOR ROOF MOUNTED EQUIPMENT BELOW ROOF
<br />AND STUB -UP AT EACH PIECE OF EQUIPMENT. FLASH AND SEAL ALL
<br />PENETRATIONS
<br />34. THE ENTIRE WIRING SYSTEM SHALL BE TESTED FOR SHORT CIRCUITS,
<br />GROUNDS AND INSULATION RESISTANCE BETWEEN CONDUCTORS AND TO
<br />GROUND
<br />35, PROVIDE PERMANENT PLASTIC LAMINATE NAME PLATE FOR ALL ELECTRICAL
<br />EQUIPMENT, INCLUDING SWITCH GEAR, , PANELS SWITCHES CONTROLS ECT.
<br />NAME PLATE SHALL SHOW EQUIPMENT TAG, r r VOLTAGE PHASE CURRENT RATING
<br />AND FEED SOURCE
<br />36. PROVIDE PERMANENT PLASTIC LAMINATE NAMEPLATE AT ALL SERVICE
<br />DISCONNECT DEVICES TO INDICATE "SERVICE DISCONNECTING MEANS"
<br />37. VERIFY EXACT LOCATIONS AND SIZE OF MECHANICAL EQUIPMENT AND POINTS
<br />OF CONNECT WITH INSTALLING CONTRACTOR PRIOR TO ROUGHING IN FOR
<br />SAME
<br />38. ALL CONDUIT IN EXPOSED AREAS SHALL BE ROUTED TIGHT TO THE UNDERSIDE
<br />OF THE STRUCTURE ABOVE
<br />30, CONTRACTOR SHALL TANDEM WIRE (I) LAMP OR (3) LAMP FLUORESCENT LIGHT
<br />FIXTURES WHENEVER FIXTURE IS RECESSED MOUNTED AND WITHIN 10° OF
<br />EACH OTHER OR IS SURFACE OR PENDANT MOUNTED WITHIN l' OF EACH OTHER
<br />40. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL HARDWARE REQUIRED FOR
<br />COMPLETE INSTALLATION, WHETHER OR NOT INDICATED BY FIXTURE CATALOG
<br />NUMBER, REFER TO ELECTRICAL SPECIFICATIONS
<br />41. ALL, LIGHT FIXTURES MOUNTED IN WE OR DAMP LOCATION TO CARRY
<br />APPROPRIATE U.L. LABEL,
<br />42, ALL FLUORESCENT FIXTURES SHALL HAVE ENERGY SAVING C.E.C. APPROVED T3
<br />LAMPS AND ELECTRONIC BALLASTS
<br />43. WHERE APPLICABLE, RECESSED INCANDESCENT AND H.I.D. FIXTURES ARE TO
<br />BE USED WITH BATT-TYPE INSULATION, CUT 3" MINIMUM AROUND FIXTURE AND
<br />ARE TO HAVE THERMAL PROTECTION
<br />44. CONTRACTOR TO PROVIDE ALL LAMPS NOT FURNISHED WITH FIXTURES
<br />45. FOR ANY DEVIATION FROM SPECIFIED LIGHT FIXTURES AND EQUIPMENT, IT
<br />WILL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO GUARANTEE
<br />LIGHT LEVELS PROVIDED IN THE ORIGINAL DESIGN
<br />46. ELECTRICAL ENGINEER IS NOT RESPONSIBLE FOR TYPE OF CEILING BEING
<br />INSTALLED. REFER TO ARCHITECTURAL PLANS FOR EXACT CEILING TYPE,
<br />CONTRACTOR SHALL VERIFY CEILING TYPE/FIXTURE COMPATIBILITY BEFORE
<br />ORDERING FIXTURES
<br />47. IT IS UNDERSTOOD BY ALL PARTIES THAT ANY SUBSTITUTIONS OF SPECIFIED
<br />PRODUCTS ARE DONE FOR THE PURPOSE OF COST SAVINGS TO THE OWNER,
<br />THEREFORE, ANY MATERIALS SUBSTITUTIONS OR DEVIATIONS PROPOSED BY
<br />THE CONTRACTOR SHALL BE INCLUDED WITH THE INITIAL BID AND SHALL
<br />SHOW A LINE ITEM CREDIT TO THE OWNER FOR EACH ITEM SUBSTITUTED IN
<br />LIEU OF SPECIFIED PRODUCTS
<br />48. PROVIDE ALL EXIT SIGNS WITH DIRECTIONAL ARROWS AS REQUIRED.