GENERAL STRUCTURAL NOTES (GSN): <br />GOVERNING CODE THE "INTERNATIONAL BUILDING CODE" (IBC) 2015 EDITION, AS ADOPTED AND MODIFIED BY THE CITY <br />OF EVERETT GOVERNS THE DESIGN, CONSTRUCTION, AND ALL MATERIALS WORKMANSHIP OF THIS PROJECT. <br />REFERENCE STANDARDS: WHERE OTHER STANDARDS ARE NOTED IN THE DRAWINGS, THE LATEST EDITION OF THE <br />MATERIALS REFERENCE STANDARDS SHALL BE USED.THE CONTRACTOR SHALL CONFORM WITH THE SECTIONS REFERRED <br />TO THE IBC AND WITH THE ENTIRE MATERIALS REFERENCE STANDARDS NOTED BELOW. <br />ARCHITECTURAL DRAWINGS: REFER TO THE ARCHITECTURAL DRAWINGS FOR INFORMATION INCLUDING, BUT NOT LIMITED <br />TO: DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND WINDOW OPENINGS, NON -BEARING WALLS, STAIRS, ELEVATORS, <br />CURBS, DRAINS, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES AND OTHER NONSTRUCTURAL ITEMS. <br />STRUCTURAL DETAILS: THE STRUCTURAL DRAWINGS ARE INTENDED TO SHOW THE GENERAL CHARACTER OF THE <br />PROJECT AND ARE NOT INTENDED TO SHOW ALL DETAILS OF THE WORK. USE ALL DETAIL SHEETS AND ALL SPECIFIC <br />DETAILS REFERENCED IN THE PLAN AS "TYPICAL" WHEREVER THEY APPLY. <br />INSPECTIONS: THE CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL INSPECTIONS REQUIRED. NOTIFY <br />BUILDING DEPARTMENT FOR INSPECTIONS REQUIRED BY LOCAL JURISDICTION AND IN ACCORDANCE WITH <br />CHAPTER 17 PER IBC. <br />DISCREPANCIES: ANY DISCREPANCY FOUND BETWEEN THE DRAWINGS, NOTES, SPECIFICATIONS, SITE CONDITIONS, AND <br />PLANS SHALL BE REPORTED TO THE ARCHITECT AND ENGINEER WHO SHALL CORRECT THE DISCREPANCY IN WRITING. <br />ANY WORK COMPLETED AFTER DISCOVERY OF THE DISCREPANCY SHALL BE DONE AT THE CONTRACTOR'S RISK. <br />CONTRACTOR/DESIGNER/OWNER IS RESPONSIBLE FOR PROVIDING CORRECT SITE INFORMATION. ALL UNDERGROUND UTILITIES <br />SHALL BE DETERMINED BY THE CONTRACTOR PRIOR TO EXCAVATION OR DRILLING. <br />SITE VERIFICATION: THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE PRIOR TO <br />FABRICATION AND/OR CONSTRUCTION. CONFLICTS BETWEEN THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE <br />BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE WORK. ALL UNDERGROUND UTILITIES <br />SHALL BE DETERMINED BY THE CONTRACTOR PRIOR TO EXCAVATION OR DRILLING. <br />CONSTRUCTION LOADS: LOADS ON THE STRUCTURE DURING CONSTRUCTION SHALL NOT EXCEED THE DESIGN LOADS OR <br />THE CAPACITY OF THE PARTIALLY COMPLETED CONSTRUCTION. ALL STRUCTURAL SYSTEMS WHICH ARE TO BE <br />COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, <br />DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER. <br />CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR STRUCTURE AND STRUCTURAL COMPONENTS UNTIL ALL FINAL <br />CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS CONFORM TO ASCE 37-02 "DESIGN LOADS <br />ON STRUCTURES DURING CONSTRUCTION" <br />ALL STRUCTURAL SYSTEMS WHICH ARE TO BE COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE <br />SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND ERECTION IN <br />ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER. <br />CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND STRUCTURAL COMPONENTS UNTIL ALL <br />FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS. CONFORM TO ASCE 37-02 "DESIGN <br />LOADS ON STRUCTURES DURING CONSTRUCTION." <br />DESIGN CRITERIA: <br />ROOF LOADS: DEAD LOADS 15 PSF <br />LIVE LOADS 25 PSF <br />FLOOR LOADS: DEAD LOADS 10 PSF <br />LIVE LOADS 40 PSF <br />DECKS LIVE LOAD 60 PSF <br />SNOW LOAD: ROOF SNOW LOAD Ps = 25 PSF; SNOW EXPOSURE FACTOR Ce = 1.0; SNOW IMPORTANCE FACTOR <br />Is = 1.0; THERMAL FACTOR Ct = 1.0. <br />WIND DESIGN: BASIC WIND SPEED (3-SECOND GUST), V = 110 MPH; WIND IMPORTANCE FACTOR, Iw = 1.0; <br />OCCUPANCY CATEGORY = II; EXPOSURE CATEGORY = B; WIND SPEED-UP FACTOR Kzt=1.0; <br />SEISMIC DESIGN: SEISMIC IMPORTANCE FACTOR le = 1.0; OCCUPANCY CATEGORY = II; Ss = 1.310g; S1 <br />0.464g; SEISMIC DESIGN CATEGORY = D; Sds = 0.873g; SEISMIC DESIGN <br />CATEGORY = D; BASIC SEISMIC FORCE RESISTING SYSTEM (BEARING WALL SYSTEMS) <br />LIGHT --FRAMED WALLS WITH WOOD STRUCTURAL PANELS RATED FOR SHEAR RESISTANCE AND <br />FLEXIBLE DIAPHRAGMS; Cs =0.134; R =6.5; Cd=4; OMEGA=2.5; SEISMIC BASE SHEAR = 17.74 KIPS, <br />ANALYSIS PROCEDURE=EQUIVALENT LATERAL FORCE PROCEDURE PER ASCE 7, SEC 12.8 <br />DEFLECTIONS: TOTAL LOAD DEFLECTION LIMIT: L/240 <br />LIVE LOAD DEFLECTION LIMIT: L/360 <br />DEFERRED SUBMITTALS DESIGN -BY -OTHERS),: SUBMIT PRODUCT DATA AND PROOF OF ICC APPROVAL FOR FRAMING <br />MEMBERS AND FASTENERS THAT HAVE BEEN PREPARED BY THE SPECIALTY STRUCTURAL ENGINEER (SSE) IN THE STATE <br />OF WASHINGTON FOR ALL MEMBERS AND CONNECTIONS ALONG WITH SHOP DRAWINGS. DESIGN SHALL BE SUBMITTED TO <br />THE ARCHITECT/DESIGNER AND STRUCTURAL ENGINEER OF RECORD (SER) FOR REVIEW PRIOR TO SUBMISSION TO THE <br />JURISDICTION FOR APPROVAL. THE SSE SHALL SUBMIT TO THE ENGINEER FOR REVIEW CALCULATIONS AND SHOP <br />DRAWINGS THAT ARE STAMPED AND SIGNED BY THE SSE. REVIEW OF THE SSE'S SHOP DRAWINGS IS FOR GENERAL <br />COMPLIANCE WITH DESIGN CRITERIA AND COMPATIBILITY WITH THE DESIGN OF THE PRIMARY STRUCTURE AND DOES NO] - <br />RELIEVE THE SSE OF RESPONSIBILITY FOR THAT DESIGN. <br />ALL NECESSARY BRIDGING, BLOCKING, BLOCKING PANELS AND WEB STIFFENERS SHALL BE DETAILED AND FURNISHED <br />BY THE SUPPLIER. TEMPORARY AND PERMANENT BRIDGING SHALL BE INSTALLED IN CONFORMANCE WITH THE <br />MANUFACTURER'S SPECIFICATIONS. DEFLECTION LIMITS SHALL BE AS NOTED UNDER DESIGN LOADS SECTION. THESE <br />ELEMENTS INCLUDE BUT ARE NOT LIMITED TO: <br />-HANDRAILS & GUARDRAILS <br />-ENGINEERED WOOD BEAMS <br />-PREFABRICATED WOOD COMPONENETS-SHEAR WALLS/WOOD PANELS <br />-TEMPORARY SHORING SYSTEMS <br />SOILS AND FOUNDATIONS <br />REFERENCE STANDARDS: CONFORM TO IBC CHAPTER 18 "SOILS AND FOUNDATIONS." <br />FOUNDATIONS: EXTEND FOOTINGS TO FIRM AND UNYIELDING NATIVE SOIL OR STRUCTURAL FILL WITH AN ALLOWABLE SOIL <br />BEARING CAPACITY OF 1500 PSF. BOTTOM OF EXTERIOR FOOTINGS SHALL BE V-6" MIN BELOW OUTSIDE FINISHED GRADE. <br />MAINTAIN A MINIMUM 6" SEPARATION BETWEEN FINISH GRADE & UNTREATED WOOD FRAMING. <br />EXTERIOR PERIMETER FOOTINGS SHALL BEAR NOT LESS THAN 12 INCHES BELOW ADJACENT FINISHED GRADE, OR BY <br />THE BUILDING OFFICIAL. INTERIOR FOOTINGS SHALL BEAR NOT LESS THAN 12 INCHES BELOW FINISH FLOOR. FOOTINGS <br />SHALL BE CENTERED BELOW COLUMNS OR WALLS ABOVE, U.N.O. <br />FOUNDATION STEM WALLS: THE HEIGHT OF THE STEM WALL SHALL BE AS NOTED ON THE DRAWINGS TO FIT THE <br />HOLDOWN REQUIREMENTS. MAINTAIN A MINIMUM 6" SEPARATION BETWEEN FINISH GRADE & UNTREATED WOOD FRAMING. <br />BACKFILLING: BACKFILL BEHIND FOUNDATION WALLS SHALL BE OF FREE -DRAINING MATERIAL PLACED IN MAXIMUM LOOSE <br />LIFTS OF 12". BACKFILL SHALL BE COMPACTED USING HAND -OPERATED EQUIPMENT ONLY. THE CONTRACTOR SHALL <br />REFRAIN FROM OPERATING HEAVY EQUIPMENT BEHIND FOUNDATION WALLS WITHIN A DISTANCE EQUAL TO OR GREATER <br />THAN THE HEIGHT OF THE WALL. <br />STRUCTURAL FILL: UNLESS OTHERWISE SPECIFIED BY A GEOTECHNICAL ENGINEER, FOOTINGS SHALL BE PLACED ON <br />COMPACTED MATERIAL AND SHALL BE WELL -GRADED GRANULAR MATERIAL WITH NO MORE THAN 5% PASSING A #2 <br />SIEVE. FILLS PLACED SHALL BE IN MAXIMUM 8" LIFTS AND ALL BEARING SOILS SHALL BE COMPACTED TO 95% <br />MAXIMUM DENSITY AT OPTIMUM MOISTURE CONTENT USING THE MODIFIED PROCTOR TEST. <br />COMPACTION: UNLESS OTHERWISE SPECIFIED BY A GEOTECHNICAL ENGINEER, FOOTINGS SHALL BE PLACED ON <br />COMPACTED MATERIAL AND SHALL BE WELL -GRADED GRANULAR MATERIAL WITH NO MORE THAN 5% PASSING A #2 <br />SIEVE. FILLS PLACED SHALL BE IN MAXIMUM 8" LIFTS AND ALL BEARING SOILS SHALL BE COMPACTED TO 95% <br />MAXIMUM DENSITY AT OPTIMUM MOISTURE CONTENT USING THE MODIFIED PROCTOR TEST. <br />GEOTECHNICAL <br />ALLOWABLE SOIL PRESSURE AND LATERAL EARTH PRESSURE ARE ASSUMED AND THEREFORE MUST BE VERIFIED BY A <br />QUALIFIED SOIL ENGINEER OR APPROVED BY BUILDING OFFICIAL. NO SOIL REPORT PROVIDED. IF SOILS ARE FOUND TO <br />BE OTHER THAN ASSUMED, NOTIFY THE STRUCTURAL ENGINEER FOR POSSIBLE FOUNDATION REDESIGN. <br />ALLOWABLE BEARING CAPACITY -STRUCTURAL FILL 1500 PSF (ASSUMED) <br />CAST -IN -PLACE CONCRETE <br />REFERENCE STANDARDS: CONFORM TO: <br />(1) ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY". <br />(2) IBC CHAPTER 19, CONCRETE. <br />FIELD REFERENCE: THE CONTRACTOR SHALL KEEP A COPY OF ACI FIELD REFERENCE MANUAL, SP-15, "STANDARD <br />SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301) WITH SELECTED ACI AND ASTM REFERENCES." <br />CONCRETE SHALL ATTAIN A 28-DAY STRENGTH OF f'c=3000 PSI AND MIX SHALL CONTAIN NOT LESS THAN 5-1/2 <br />SACKS OF CEMENT PER CUBIC YARD OF CONCRETE AND SHALL BE PROPORTIONED TO PRODUCE A SLUMP OF 5" OR <br />LESS. ALL CONCRETE WITH SURFACES EXPOSED TO STANDING WATER SHALL BE AIR -ENTRAINED WITH AIR -ENTRAINING <br />AGENT CONFORMING TO ASTM C260, C494, AND C618. TOTAL AIR CONTENT FOR FROST -RESISTANT CONCRETE SHALL <br />BE IN ACCORDANCE WITH ASTM C666. <br />CONCRETE COVER: CONFORM TO THE FOLLOWING COVER REQUIREMENTS FROM ACI 301, TABLE 3.3.2.3: <br />CONCRETE CAST AGAINST EARTH 3" <br />CONCRETE EXPOSED TO EARTH OR WEATHER (#5 & SMALLER) 1-1/2" <br />CONCRETE EXPOSED TO EARTH OR WEATHER (#6 & LARGER) 2" <br />BARS IN SLABS AND STEM WALLS 3/4" <br />MATERIALS: <br />REINFORCING BARS ASTM A615, GRADE 60, DEFORMED BARS, fy =60000 PSI. <br />SMOOTH WELDED WIRE FABRIC ASTM A185 <br />EXCEPTIONS ARE ANY BARS SPECIFICALLY SO NOTED ON THE DRAWINGS. REINFORCING SHALL BE GRADE 40, <br />fy=40000 PSI AND GRADE 60, fy=60000 PSI. <br />FORMWORK: CONFORM TO ACI 301 SEC 2 "FORMWORK AND FORM ACCESSORIES." REMOVAL OF FORMS SHALL <br />CONFORM TO SEC 2.3.2 EXCEPT STRENGTH INDICATED IN SEC 2.3.2.5 SHALL BE 0.75 Vc. <br />MEASURING, MIXING AND DELIVERY: CONFORM TO ACI 301 SEC 4.3. <br />HANDLING PLACING - CONSTRUCTING AND CURING: CONFORM TO ACI 301 SEC 5 AND SEC 3.3.2 "PLACEMENT." <br />PLACING TOLERANCES SHALL CONFORM TO SEC 3.3.2.1 "TOLERANCES." <br />EMBEDDED ITEMS: POSITION AND SECURE IN PLACE EXPANSION JOINT MATERIAL, ANCHORS AND OTHER STRUCTURAL <br />AND NON --STRUCTURAL EMBEDDED ITEMS BEFORE PLACING CONCRETE. CONTRACTOR SHALL REFER TO MECHANICAL, <br />ELECTRICAL, PLUMBING AND ARCHITECTURAL DRAWINGS AND COORDINATE ALL OTHER EMBEDDED ITEMS. <br />FABRICATION: CONFORM TO ACI 301, SEC 3.2.2 "FABRICATION", AND ACI SP-66 "ACI DETAILING MANUAL." <br />WELDING: CONFORM TO AWS D1.4/D1.4M. WELDERS SHALL BE CERTIFIED IN ACCORDANCE WITH (AWS AND WABO) <br />REQUIREMENTS. USE E70 ELECTRODES OF TYPE REQUIRED FOR MATERIALS TO BE WELDED. <br />SPLICES: CONFORM TO ACI 301, SEC 3.3.2.7. REFER TO "LAP SPLICE SCHEDULE" OR PLANS FOR TYPICAL SPLICES. <br />THE SPLICES INDICATED ON INDIVIDUAL SHEETS CONTROL OVER THE SCHEDULE. USE CLASS B SPLICES UNLESS <br />OTHERWISE NOTED, <br />FIELD BENDING: CONFORM TO ACI 301 SEC 3.3.2.8. "FIELD BENDING OR STRAIGHTENING." BAR SIZES #3 THROUGH #5 <br />MAY BE FIELD BENT COLD THE FIRST TIME , PROVIDED REINFORCING BAR TEMPERATURE IS ABOVE 32°F. FOR OTHER <br />BARS SIZES REQUIRE PREHEATING BEFORE FIELD BENDING. DO NOT TWIST BARS. <br />NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT. <br />CORNERS BARS: PROVIDE MATCHING -SIZED "L" CORNER BARS FOR ALL HORIZONTAL WALL AND FOOTING BARS WITH <br />THE APPROPRIATE SPLICE LENGTH, UNO. <br />ANCHORAGE <br />-EPDXY-GROUTED ITEMS (THREADED RODS OR REINFORCING BAR) SPECIFIED ON THE DRAWINGS SHALL BE INSTALLED <br />USING "SET-XP" EPDXY ADHESIVE AS MANUFACTURED BY THE SIMPSON STRONG TIE COMPANY. INSTALL IN STRICT <br />ACCORDANCE WITH ICC-ESREPORT ESR--2508. SUBSTITUTIONS PROPOSED BY THE CONTRACTOR SHALL BE SUBMITTED <br />FOR REVIEW WITH CURRENT ICC REPORTS INDICATING EQUIVALENT OR GREATER LOAD CAPACITIES. SPECIAL INSPECTION <br />OF INSTALLATION IS REQUIRED. RODS SHALL BE ASTM A36, UNO. <br />-HEAVY DUTY THREADED CONCRETE ANCHORS SPECIFIED ON THE DRAWINGS SHALL BE "TITAN HD SCREW ANCHOR" AS <br />MANUFACTURED SY THE SIMPSON STRONG TIE COMPANY. INSTALL IN STRICT ACCORDANCE WITH ICC-ES REPORT <br />ESR-2713. INCLUDING MINIMUM EMBEDMENT AND EDGE DISTANCE REQUIREMENTS. SUBSTITUTIONS PROPOSED BY THE <br />CONTRACTOR SHALL BE SUBMITTED FOR REVIEW WITH CURRENT ICC REPORTS INDICATING EQUIVALENT OR GREATER <br />LOAD CAPACITIES. <br />-DRIVE PINS AND OTHER POWDER -ACTUATED FASTENERS SHALL BE LOW VELOCITY TYPE (PDPWL- 300MG. 0.145' <br />DIAMETER. UNO) AS MANUFACTURED BY THE SIMPSON STRONG TIE COMPANY OR AN APPROVED EQUIVALENT IN <br />STRENGTH AND EMBEDMENT. INSTALL IN STRICT ACCORDANCE WITH ICC-ES REPORT ESR-2138, MINIMUM EMBEDMENT <br />IN CONCRETE SHALL BE 1", UNO. MAINTAIN AT LEAST 3" TO NEAREST CONCRETE EDGE. <br />WOOD FRAMING <br />REFERENCE STANDARDS: CONFORM TO: <br />(1) IBC CHAPTER 23 "WOOD", <br />(2) NDS AND NDS SUPPLEMENT - "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION", <br />IDENTIFICATION: ALL SAWN LUMBER AND PRE -MANUFACTURED WOOD PRODUCTS SHALL BE IDENTIFIED BY THE GRADE <br />MARK OR A CERTIFICATE OF INSPECTION ISSUED BY THE CERTIFYING AGENCY. <br />MATERIALS: <br />SAWN LUMBER: ALL LUMBER SHALL BE KILN -DRIED OR MC-19 AND CONFORM TO GRADING RULES OF WWPA, WCLIB <br />OR NLGA. FINGER JOINTED STUDS ACCEPTABLE AT INTERIOR WALLS ONLY. <br />MEMBER USE SIZE SPECIES GRADE MINIMUM BASE VALUE <br />STUDS, PLATES, MISC 2X, 3X HEM -FIR (U.N.O.) NO, 2 Fc=575 PSI <br />JOISTS 2X, 3X 2X6 - 2X12 HEM --FIR NO. 2 Fb=850 PSI <br />BEAMS 4X8 - 4X12 DOUG-FIR NO. 2 Fb=900 PSI <br />BEAMS 6X8 - 6X12 DOUG--FIR NO, 2 Fb=875 PSI <br />POSTS 4X DOUG-FIR NO. 2 Fc=700 PSI <br />POSTS 6X, 8X DOUG-FIR NO. 1 Fc=1000 PSI <br />GLUED LAMINATED TIMBER: MANUFACTURED LUMBER, PSL. LVL, AND LSL, SHALL BE MANUFACTURED UNDER A <br />PROCESS APPROVED BY THE NATIONAL RESEARCH BOARD. EACH PIECE SHALL BEAR A STAMP OR STAMPS NOTING <br />THE NAME AND PLANT NO OF THE MANUFACTURER, THE GRADE, THE NATIONAL RESEARCH BOARD NUMBER, AND THE <br />QUALITY CONTROL AGENCY. ALL PSL, LVL AND LSL LUMBER SHALL BE MANUFACTURED IN ACCORDANCE WITH <br />ICC-ESS REPORT ESR-1387 USING DOUGLAS FIR VENEER GLUED WITH A WATERPROOF ADHESIVE MEETING THE <br />REQUIREMENTS OF ASTM D2559 WITH ALL GRAIN PARALLEL WITH THE LENGTH OF THE MEMBER. THE MEMBERS SHALL <br />HAVE THE FOLLOWING MINIMUM PROPERTIES: <br />GLUED LAMINATED MEMBER BEAMS SHALL NOT BE CAMBERED, UNLESS SHOWN OTHERWISE ON THE PLANS OR <br />SPECIFICATIONS. <br />MANUFACTURED LUMBER PRODUCTS SHALL BE INSTALLED WITH A MOISTURE CONTENT OF 12% OR LESS. THE <br />CONTRACTOR SHALL MAKE PROVISIONS DURING CONSTRUCTION TO PREVENT THE MOISTURE CONTENT OF INSTALLED <br />BEAMS FROM EXCEEDING 12%. EXCESSIVE DEFLECTIONS MAY OCCUR IF MOISTURE CONTENT EXCEED THIS VALUE, <br />MEMBER USE SIZES SPECIES STRESS CLASS USES Fb(PSI) Fv(PSI) <br />GLB ALL DF/DF 24F-1.8E 24F-V4 SIMPLE SPANS 2400 265 <br />ALL DF/DF 24F-1.8E 24F-V8 CANTILEVER SPANS 2400 265 <br />PSL (2.2E) Fb=2900 PSI, Fv=290 PSI <br />LVL (2.OE) Fb=2600 PSI, Fv=285 PSI <br />LSL (1.55E) Fb=2325 PSI, Fv=310 PSI <br />PSL COLUMN (1.8E) Fc=2900 PSI, <br />PLYWOOD SHEATHING SHALL BE APA-RATED STRUCTURAL SHEATHING GRADE C-D EXTERIOR GLUE OR STRUCTURAL II, <br />EXTERIOR GLUE IN CONFORMANCE WITH THE AMERICAN PLYWOOD ASSOCIATION (APA). ORIENTED STRAND BOARD OF <br />EQUIVALENT THICKNESS, EXPOSURE RATING AND PANEL INDEX MAY BE USED IN LIEU OF PLYWOOD. <br />MINIMUM APA RATING <br />LOCATION THICKNESS SPAN RATING PLYWOOD GRADE EXPOSURE <br />ROOF 15/32" 32/16 C-D 1 <br />FLOOR 23/32" 24 OC STURD-1--FLOOR 1 <br />WALLS 15/32" 32/16 C--D 1 <br />PREFABRICATED PLYWOOD WEB JOIST DESIGN SHOWN ON PLANS IS BASED ON JOISTS MANUFACTURED BY THE <br />TRUS-JOIST CORPORATION. ALTERNATE PLYWOOD WEB JOIST MANUFACTURED BY THE TRUSS -JOIST CORPORATION, <br />ALTERNATE PLYWOOD WEB JOIST MANUFACTURERS MAY BE USED SUBJECT TO REVIEW AND APPROVAL BY THE <br />ARCHITECT AND STRUCTURAL ENGINEER. JOIST HANGERS AND CONNECTORS SHALL BE "SIMPSON STRONG -TIE" <br />CATALOG C-C-2017. ALTERNATE JOIST HANGERS AND OTHER HARDWARE MAY BE SUBSTITUTED FOR ITEMS SHOWN <br />PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. ALL JOIST HANGERS AND OTHER <br />HARDWARE SHALL BE COMPATIBLE IN SIZE WITH PLYWOOD WEB JOIST PROVIDED. ALL 2x JOISTS SHALL BE <br />CONNECTED TO FLUSH BEAMS WITH 'LUS" SERIES JOIST HANGERS. ALL TJI JOIST SHALL BE CONNECTED TO FLUSH <br />BEAMS WITH '1US"SERIES JOIST HANGERS. ALL DOUBLE -JOIST BEAMS SHALL BE CONNECTED TO FLUSH BEAMS <br />WITH "MIU" SERIES JOIST HANGERS.WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE 1/2 OF THE NAILS <br />OR BOLTS IN EACH MEMBER. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS <br />BEARING ON WOOD. UNLESS NOTED OTHERWISE ALL NAILS SHALL BE FULL LENGTH COMMON. NAIL STRAPS TO WOOD <br />FRAMING AS LATE AS POSSIBLE IN THE FRAMING PROCESS TO ALLOW THE WOOD TO SHRINK AND THE BUILDING TO <br />SETTLE. <br />ALL SHIMS SHALL BE SEASONED AND DRIED AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. <br />NAILS AND STAPLES: CONFORM TO IBC SEC 2303.6 "NAILS AND STAPLES." UNLESS NOTED ON PLANS, NAIL PER IBC <br />TABLE 2304.10.1, UNLESS NOTED OTHERWISE ALL NAILS SHALL BE COMMON. NAIL SIZES SPECIFIED ON THE DRAWINGS <br />ARE BASED ON THE FOLLOWING SPECIFICATIONS: <br />SIZE LENGTH DIAMETER TYPE <br />8d 2-1/2" 0,131 " COMMON <br />10d 3" 0.148" GUN <br />12d 3-1/4" 0.148" GUN <br />16d 3-1/2" 0.162" GUN <br />NAILING REQUIREMENTS: PROVIDE MINIMUM NAILING IN ACCORDANCE WITH IBC TABLE 2304.10.1 "FASTENING <br />SCHEDULE" EXCEPT AS NOTED ON THE DRAWINGS. NAILING FOR ROOF/FLOOR DIAPHRAGMS/SHEAR WALLS SHALL BE <br />PER DRAWINGS. NAILS SHALL BE DRIVEN FLUSH AND SHALL NOT FRACTURE THE SURFACE OF SHEATHING. <br />IF CONTRACTOR PROPOSES THE USE OF ALTERNATE NAILS, THEY SHALL SUBMIT NAIL SPECIFICATIONS TO THE <br />STRUCTURAL ENGINEER (PRIOR TO CONSTRUCTION) FOR REVIEW AND APPROVAL. <br />LAG BOLTS/BOLTS: CONFORM TO ASTM A307. <br />ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF <br />ALL BOLTS AND LAG BOLTS BEARING ON WOOD. INSTALLATION OF LAG SCREWS SHALL CONFORM TO THE NATIONAL <br />DESIGN SPECIFICATION FOR WOOD CONSTRCTION (2015 EDITION) WITH A LEAD BORE HOLE OF 60-70% OF THE SHANK <br />DIAMETER. LEAD HOLES ARE NOT REQUIRED FOR 3/8" AND SMALLER LAG SCREWS. BOLT HOLES SHALL BE A <br />MINIMUM OF 1/32" TO A MAXIMUM OF 1/16" LARGER THAN THE BOLT DIAMETER. HOLES SHALL BE ACCURATELY <br />ALIGNED IN MAIN MEMBERS AND SIDE PLATES/ MEMBERS. BOLTS SHALL NOT BE OVERDRIVEN. <br />SDS SERIES: WOOD SCREWS CALLED OUT ON PLAN SHALL BE "SIMPSON STRONG -DRIVE" WOOD SCREWS BY SIMPSON <br />COMPANY, AND INSTALLED IN STRICT ACCORDANCE TO ICC-ES REPORT ESR-2236. EQUIVALENT SCREWS BY OTHER <br />MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER LOAD <br />CAPACITIES, LAG SCREWS ARE NOT AN EQUIVALENT SUBSTITUTION. <br />WOOD HOLDOWNS: HOLDOWNS SPECIFIED ARE AS MANUFACTURED BY SIMPSON ANCHOR TIE -DOWN CO., INC. <br />ADDITIONAL FRAMING MEMBERS SHALL BE PROVIDED PER THE SYSTEM REQUIREMENTS. ACCEPTABLE EQUIVALENT <br />PRODUCT SUBSTITUTIONS ARE AVAILABLE FROM OTHER MANUFACTURERS WITH ENGINEER APPROVAL. <br />ENGINEERED WOOD PRODUCTS (I -LEVEE: THE FOLLOWING MATERIALS ARE BASED ON LUMBER MANUFACTURED BY <br />I -LEVEL AND WERE USED FOR THE DESIGN AS SHOWN ON THE PLANS. ALTERNATE PRODUCTS BY OTHER <br />MANUFACTURERS MAY BE SUBSTITUTED PROVIDED THEY HAVE CURRENT ICC APPROVAL FOR EQUIVALENT OR GREATER <br />LOAD AND STIFFNESS PROPERTIES AND ARE REVIEWED AND APPROVED BY THE ENGINEER. <br />A) LAMINATED VENEER LUMBER I_VL : ICC ES REPORT NO. ER-4979 <br />B) PARALLEL STRAND LUMBEE- PSL): ICC ES REPORT NO. ER-4979 <br />C) LAMINATED STRAND LUMBER (LSL): ICC ES REPORT NO. ER-4979 <br />D)1-JOISTS: ICC ES REPORT NO. ER-4979, ESR-1153. <br />PRODUCTS SHALL BE TESTED AND EVALUATED IN ACCORDANCE WITH ASTM D5055. THE MANUFACTURER SHALL DESIGN <br />THE JOISTS FOR THE SPANS AND CONDITIONS SHOWN ON THE PLANS. JOISTS SHALL HAVE WOOD CHORDS AND <br />SOLID WOOD WEBS. <br />STANDARD LIGHT -FRAME CONSTRUCTION: UNLESS NOTED ON THE PLANS, CONSTRUCTION SHALL CONFORM TO <br />16C 2015 SEC 2308 "CONVENTIONAL LIGHT -FRAME CONSTRUCTION" AND SEC 2304 "GENERAL CONSTRUCTION <br />REQUIREMENTS", THE AITC "TIMBER CONSTRUCTION MANUAL", AND THE AF&PA "NATIONAL DESIGN SPECIFICATION FOR <br />WOOD CONSTRUCTION". MINIMUM NAILING, UNLESS NOTED OTHERWISE SHALL CONFORM TO TABLE 2304.10.1. OF THE <br />IBC. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS. <br />WALL FRAMING: UNLESS OTHERWISE NOTED, ALL INTERIOR WALLS SHALL BE 2X4 @ 16"OC AND ALL EXTERIOR WALLS <br />SHALL BE 2X6 @ 16"OC. PROVIDE (2)BUNDLED STUDS MIN AT WALL ENDS AND EACH SIDE OF ALL OPENINGS. UNO, <br />ALL SOLID SAWN LUMBER HEADERS SHALL BE SUPPORTED BY A MINIMUM OF (1)TRIM AND (1)KING STUD AND ALL <br />GLULAM OR ENGINEERED WOOD HEADERS BY (2)TRIM AND (2)KING STUDS. AT FRAMED WALLS, UNO ALL SOLID SAWN <br />LUMBER BEAMS SHALL BE SUPPORTED ON A MINIMUM OF (2) BUNDLED 2X STUDS AND ALL GLULAM OR ENGINEERED <br />WOOD BEAMS ON A MINIMUM OF (3) BUNDLED 2X STUDS. STITCH -NAIL BUNDLED STUDS WITH (2)10D @ 12"0C. <br />UNO, ALL INTERIOR AND EXTERIOR HEADERS SHALL BE 4X10 DF#2. PROVIDE SOLID BLOCKING THRU FLOORS TO <br />SUPPORTS BELOW FOR BEARING WALLS AND POSTS. PROVIDE CONTINUOUS SOLID BLOCKING AT MID -HEIGHT OF ALL <br />STUD WALLS OVER 10'-0" IN HEIGHT. <br />ALL WALLS SHALL HAVE A SINGLE BOTTOM PLATE. END NAIL TOP PLATE AND BOTTOM PLATE TO EACH STUD <br />WITH THREE 10d NAILS. FACE NAIL DOUBLE TOP PLATES WITH 10d AT 12"OC AND LAP MINIMUM 4'-0" AT JOINTS <br />AND PROVIDE TWELVE 10d NAILS AT 4"OC EACH SIDE OF JOINT. AT TOP PLATE INTERSECTIONS PROVIDE THREE 10d <br />FACE NAILS. <br />ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD FRAMING BELOW WITH TWO <br />ROWS OF 10d NAILS AT 16"OC, OR ATTACHED TO CONCRETE BELOW WITH 5/8" DIAMETER ANCHOR BOLTS <br />AT 4'-O"OC EMBEDDED 7" MINIMUM, UNO. THERE SHALL BE A MINIMUM OF TWO BOLTS PER PLATE SECTION WITH <br />ONE BOLT LOCATED NOT MORE THAN 12" OR LESS THAN 4 M" FROM EACH END OF THE PLATE SECTION. INDIVIDUAL <br />MEMBERS OF BUILT-UP POSTS SHALL BE NAILED TO EACH OTHER WITH TWO ROWS OF 10d AT 16"OC. UNLESS <br />NOTED OTHERWISE, GYPSUM WALLBOARD SHALL BE FASTENED TO THE INTERIOR SURFACE OF ALL STUDS AND <br />PLATES WITH #6 x 1-1/4" TYPE S OR W SCREWS AT 8"OC. UNLESS NOTED OTHERWISE, 'A" (NOMINAL) APA RATED <br />SHEATHING (SPAN RATING 24/0) SHALL BE NAILED TO ALL EXTERIOR SURFACES WITH 8d NAIL AT 6"OC AT PANEL <br />EDGES AND TOP AND BOTTOM PLATES (BLOCK UNSUPPORTED EDGES) AND TO ALL INTERMEDIATE STUDS AND <br />BLOCKING WITH 8d NAILS AT 12"OC. ALLOW 1/8" SPACING AT ALL PANEL ENDS. <br />ROOF/FLOOR FRAMING: UNLESS OTHERWISE NOTED, PROVIDE DOUBLE JOISTS/RAFTERS UNDER ALL PARALLEL BEARING <br />PARTITIONS THAT EXTEND OVER MORE THAN HALF THE JOIST LENGTH AND SOLID BLOCKING AT ALL BEARING POINTS. <br />PROVIDE DOUBLE JOISTS AROUND ALL ROOF/FLOOR OPENINGS.TOENAIL JOISTS TO SUPPORTS WITH THREE 10d NAILS. <br />ATTACH TIMBER JOISTS TO FLUSH HEADERS OR BEAMS WITH SIMPSON METAL JOIST HANGERS IN ACCORDANCE WITH <br />NOTES PER PLAN. UNO, MULTI-JOISTS/RAFTERS SHALL BE STITCH -NAILED TOGETHER WITH (2)10d @ 12"OC. <br />TOENAIL RIM JOIST TO TOP PLATE WITH 10d AT 6"OC. PROVIDE ROOF SHEATHING EDGE WITH APPROVED CLIPS <br />CENTERED BETWEEN FRAMING AT UNBLOCKED PLYWOOD EDGES. ALL FLOOR SHEATHING SHALL HAVE TONGUE AND <br />GROOVE JOINTS OR BE SUPPORTED BY SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF <br />ROOF/FLOOR SHEATHING. ROOF/FLOOR SHEATHING SHALL BE LAID FACE GRAIN PERPENDICULAR TO FRAMING <br />MEMBERS AND NAILED AT 6"OC WITH 8d NAILS TO FRAMED PANEL EDGES, DRUG -STRUTS, AND OVER STUD WALLS <br />AS PER PLAN AND AT 12"OC TO INTERMEDIATE SUPPORTS.. <br />MOISTURE CONTENT: WOOD MATERIAL USED FOR THIS PROJECT SHALL HAVE MAXIMUM MOISTURE CONTENT OF 19% <br />EXCEPT FOR THE PRESSURE -TREATED WOOD SILL PLATE. <br />TRUSSES SHALL BE DESIGNED TO NOT ALLOW LIMITED STORAGE PER IBC TABLE 1607.1. WEBS SHALL CONFIGURED <br />SO THAT ALL OPENINGS ARE SMALLER THAN 24" WIDE X 42" HIGH. <br />PRESERVATIVE TREATMENT/METAL CONNECTORS: WOOD MATERIALS ARE REQUIRED TO BE "TREATED WOOD" UNDER CERTAIN <br />CONDITIONS IN ACCORDANCE WITH IBC SEC 2304.10.5 "FASTENERS AND CONNECTORS IN CONTACT WITH PRESERVATIVE -TREATED <br />AND FIRE®RETARDANT-TREATED WOOD". CONFORM TO THE APPROPRIATE STANDARDS OF THE AMERICAN WOOD PROTECTION <br />ASSOCIATION (AWPA) FOR SAWN LUMBER, GLUED LAMINATED TIMBER, ROUND POLES, WOOD PILES AND MARINE PILES. FOLLOW <br />AMERICAN LUMBER STANDARDS COMMITTEE (ALSC) QUALITY ASSURANCE PROCEDURES. PRODUCTS SHALL BEAR THE APPROPRIATE <br />MARK. <br />PRESSURE TREATED WOOD FOR ABOVE GROUND USE SHALL BE TREATED TO RETENTION OF 0.25 PCF, WOOD IN CONTINOUS <br />CONTACT WITH FRESH WATER OR SOIL SHALL BE TREATED TO A RETENTION OF 0.40 PCF. SODIUM BORATE (SBX) TRATED WOOD <br />SHALL NOT BE USED WHERE EXPOSED TO WEATHER, FASTENERS AND TIMBER CONNECTORS WITHOUT AMMONIA IN DIRECT CONTACT <br />WITH ACQ-A (UP TO A RETENTION LEVEL OF 0.40 PCF), CBA-A (UP TO A RETENTION LEVEL OF 0.41 PCF), CA-B (UP TO A <br />RETENTION LEVEL OF 0.21 PCF), SHALL BE C185 OR A185 HOT DIPPED OR CONTINUOUS HOT -GALVANIZED PER ASTM A653. <br />FASTENERS AND TIMBER CONNECTORS WITH AMMONIA IN DIRECT CONTACT WITH ACQ-A (OVER A RETENTION LEVEL OF 0.40 PCF), <br />CBA--A (OVER A RETENTION LEVEL OF 0.41 PCF), CA-B (OVER A RETENTION LEVEL OF 0.21 PCF), OR WITH ACZA TREATED WOOD <br />SHALL BE TYPE 304 OR 316 STAINLESS STEEL, <br />HOT -DIPPED GALVANIZED METAL HARDWARE AND FASTENERS HAVE A MINIMUM ZINC CONTENT OF AT LEAST 1.85 OZ/SF AND ITS <br />USE IS COORDINATED BY THE CONTRACTOR AND WOOD SUPPLIER FOR THE EXPECTED ENVIRONMENT AND MOISTURE EXPOSURE FOR <br />APPROPRIATE USE BASED ON THE METHOD OF PRESERVATIVE TREATMENT OF THE WOOD. <br />CONTRACTOR INITIATED STRUCTURAL CHANCES SHALL BE SUBMITTED IN WRITING TO THE ENGINEER FOR APPROVAL PRIOR TO <br />FABRICATION AND CONSTRUCTION. <br />NOTCHES AND HOLES IN WOOD FRAMING: <br />SAWN LUMBER JOISTS AND RAFTERS: NOTCHES ATTHE ENDS OF JOISTS SHALL NOT EXCEED 1/4 THE JOIST DEPTH. <br />NOTCHES 1N THE TOP OR BOTTOM OF JOISTS SHALL NOT EXCEED 1/6 THE JOIST DEPTH BE LONGER THAN 1/3 THE <br />JOIST DEPTH, OR BE LOCATED IN THE MIDDLE 1/3 OF THE SPAN. HOLES SHALL NOT BE WITHIN 2" OF THE TOP OR <br />BOTTOM OF THE JOIST AND THE DIAMETER SHALL NOT EXCEED 1/3 THE JOIST DEPTH. SPACING BETWEEN HOLES <br />SHALL BE A MINIMUM OF (2) TIMES THE DIAMETER OF THE LARGEST HOLE OR 2" AND SHALL BE LOCATED A <br />MINIMUM OF 2" FROM ANY NOTCH. <br />EXTERIOR AND BEARING WALLS: WOOD STUDS ARE PERMITTED TO BE NOTCHED TO A DEPTH NOT EXCEEDING 1/4 OF <br />ITS WIDTH. A HOLE NOT GREATER IN DIAMETER THAN 40% OF THE STUD WIDTH IS PERMITTED IN WOOD STUDS. <br />HOLES SHALL NOT BE WITHIN 5/8" TO THE EDGE OF THE STUD. <br />SPACING BETWEEN HOLES SHALL BE A MINIMUM OF (2) TIMES THE DIAMETER OF THE LARGEST HOLE OR 2" AND <br />SHALL NOT BE LOCATED AT THE SAME SECTION AS A NOTCH. <br />CUTS, NOTCHES, AND HOLES IN MANUFACTURED LUMBER, PREFABRICATED PLYWOOD WEB JOIST AND PREFABRICATED <br />TRUSSES ARE PROHIBITED EXCEPT WHERE NOTED ON STRUCTURAL PLANS OR PERMITTED BY MANUFACTURER'S <br />RECOMMENDATIONS. <br />THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION AND ALL JOB RELATED SAFETY STANDARDS <br />AND SILICA -DUST PROTECTION PER OSHA AND WSHA. THE CONTRACTOR IS RESPONSIBLE FOR THE STRENGTH AND STABILITY OF <br />THE STRUCTURE DURING CONSTRUCTION AND SHALL PROVIDE TEMPORARY SHORING, BRACING AND OTHER ELEMENTS REQUIRED TO <br />MAINTAIN STABILITY UNTIL THE STRUCTURE IS COMPLETED, THE CONTRACTOR IS RESPONSIBLE TO BE FAMILIAR WITH THE WORK <br />REQUIRED IN THE CONSTRUCTION DOCUMENTS AND THE REQUIREMENTS FOR EXECUTING IT PROPERLY. <br />RE � Q Q <br />CONTRACTOR -INITIATED CHANCES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER <br />FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT <br />SATISFY THIS REQUIREMENT. <br />THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR ACTUAL AND/OR DIRECT RESPONSIBILITY FOR THE <br />SPECIFIC WORKING CONDITIONS AT THE SITE AND/OR FOR ANY HAS NO DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR <br />REPORT ANY HEALTH OR SAFETY DEFICIENCY TO THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT <br />SITE. <br />HOLDOWNSHEAR WALL L <br />END STUD <br />CITY <br />MODEL <br />CNN TAP <br />FASTENERSREQUIRED <br />(L) <br />CS16 <br />FLR-TO-FLR STRAP, CS=14" <br />(26) 8d COMMON <br />(2)2x STUDS <br />HF#2 <br />1,705 <br />MST37 <br />FLR-TO®FLR STRAP, CS=18" <br />(20) 16d COMMON <br />(2)2x STUDS <br />2,135 <br />MST48 <br />FLR-TO-FLR STRAP, CS=18" <br />(32) 16d COMMON <br />(2)2x STUDS <br />3,425 <br />MSTC40 <br />FLR-TO-FLR STRAP, CS=18" <br />(28) 16d SINKERS <br />(2)2x STUDS <br />2,320 <br />MSTC48B3 <br />FLR-TO-FLR STRAP, CS=18" <br />(38) 10d SINKERS <br />(2)2x STUDS <br />3,420 <br />MSTC52 <br />FLR-TO-FLR STRAP, CS=18" <br />(44) 16d SINKERS <br />(2)2x STUDS <br />3,645 <br />MSTC66 <br />FLR-TO-FLR STRAP, CS=18" <br />(64) 16d SINKERS <br />(2)2x STUDS <br />5,495 <br />MSTC6683 <br />FLR-TO-FLR STRAP, CS=18" <br />(38) 10d SINKERS <br />(2)2x STUDS <br />3,875 <br />HDU8 <br />"0 CONCRETE THREADED <br />(20) 1/4"Ox21/2" SDS <br />(3)2xDF#2 <br />7,870 <br />ROD <br />WOOD SCREWS <br />STUDS <br />HDU 11 <br />1 "0 THRU FLOOR THREADED <br />2x(30) 1/4" Ox21/2" SDS <br />8x6 DF# 1 <br />11,175 <br />ROD <br />WOOD SCREWS <br />(2)2x STUDS <br />2,250 <br />CONCRETE STRAP, 8" STEM <br />HF#2 MID WALL <br />STHD10/ <br />WALL STANDARD/RIM JOIST <br />(20) 16d SINKERS <br />(2)2x STUDS <br />STHD10RJ <br />EL=25"/EL=39" CS=17"MAX <br />EMBED 10" MIN <br />HF#2 CORNER <br />1,975 <br />(2)2x STUDS <br />HF#2 FEND WALL <br />1,610 <br />(2)2x STUDS <br />3,695 <br />HF#2 MID WALL <br />CONC STRAP, 8" STEM WALL <br />STHD14/ <br />STANDARD EL=27"/ <br />(22) 16d SINKERS <br />(2)2x STUDS <br />STHD14RJ <br />RIM JOIST EL=40" CS=17" <br />HF#2 CORNER <br />3,695 <br />EMBED 14" MIN <br />(2)2x STUDS <br />2,685 <br />HF#2 END WALL <br />NOTES: <br />1. HOLDOWNS SPECIFIED ARE AS MANUFACTURED BY SIMPSON STRONG -TIE CO. INC.; ACCEPTABLE <br />EQUIVALENT PRODUCT SUBSTITUTIONS ARE AVAILABLE FROM OTHER MANUFACTURERS WITH THE ENGINEER <br />APPROVAL. <br />2. LOCATE ALL HOLDOWNS AT ENDS OF ALL SHEAR WALLS & FASTEN TO BUNDLED HEM -FIR END STUDS. <br />3. BUNDLED END STUDS SHOULD BE STITCH -NAILED TOGETHER USING MINIMUM (2) 16d @ 10"OC, UNO. <br />4. LOCATE "HDU#" & "HDC#" HOLDOWNS AT CONCRETE FOUNDATION LEVEL. <br />LOCATE "CMST#" & "MSTC#" STRAPS AT FLOOR -TO -FLOOR CONNECTIONS. <br />5. ALL HOLDOWN ANCHOR BOLTS SHALL BE MIN 4" FROM CONCRETE WALL ENDS, <br />6. USE "SSTB" FOR 2x SILL PLATES & "SSTBL" FOR 3x OR (2)2x SILL PLATES. <br />7, ADDITIONAL END STUD REQUIRED TO MEET MINIMUM 11/2" EDGE DISTANCE FROM CONCRETE CORNER TO <br />"STHD" STRAP. USE "RJ" STYLE WITH "STHD" WHERE RIM JOIST IS PRESENT. <br />8. INSTALL ALL HOLDOWN HARDWARE PER MANUFACTURER'S INSTRUCTIONS & RECOMMENDATIONS. <br />WOOD -FRAMED DIAPHRAGMNAILING SCHEDULE <br />FOR HEM -FIR FLAMING MEMBER <br />DIAPHRAGM BOUNDARY PANEL <br />Lu <br />DIA <br />SW SHEATHING <br />NAIL SIZE & <br />SPACING @ <br />BLOCKING <br />SHEAR LOAD <br />CAPACITY <br />TYPE <br />APA-RATED <br />PANEL EDGES AND FIELD <br />REQUIRED <br />FRAMING MEMBER <br />(SEISMIC) <br />NAILING PATTERN <br />AT ABUTTING <br />PANEL EDGES <br />0.131"0 x Z_ 1/2, <br />DIA-1 <br />15/32" CD-EXT <br />8d @ 6"OC EDGE <br />NO <br />- <br />2x <br />237 <br />LL <br />8d @ 12"OC FIELD <br />� <br />0� <br />0.131"0 x 2 1/2" <br />0.131 "0 x 2. 1/2" <br />DIA-18 <br />15/32" CD-EXT <br />8d @ 6"OC EDGE <br />YES <br />„ <br />COG <br />2x <br />251 <br />8d @ 12"OC FIELD <br />8d @ <br />0.148" 0 x 3" <br />DIA-2 <br />23/32" CD-EXT <br />1Od @ 6"OC EDGE <br />NO <br />- <br />2x <br />265 <br />cc <br />10d @ 12"OC FIELD <br />LL <br />0.148" 0 x 3" <br />DIA-28 <br />23/32" CD-EXT <br />1Od @ 6"OC EDGE <br />YES <br />0.148"0 x 3" <br />2x <br />298 <br />10d @ 12 OC FIELD <br />1Od @ 6 OC <br />STAGGERED <br />NOTES: <br />1. BLOCKED DIAPHRAGM SHALL APPLY TO UNSUPPORTED PANEL EDGES WHERE SHADED PER PLAN. "B" MEANS BLOCKED <br />2. T & G (TONGUE & GROOVE) SHEATHING EDGES IS NOT A SUBSTITUTE FOR THE FLAT BLOCKING. <br />3. H1 CLIP TO EACH TRUSS. H2.5A EACH SIDE OF MULTIPLE TRUSSES. <br />