ELECTRICAL SPECIFICATION <br />INTRODUCTION <br />THE CONTRACTING FOR INSTALLATION OF THE ELECTRICAL SYSTEM WILL BE ACCOMPLISHED IN THE FIELD AT THE <br />DIVISION LEVEL. THESE SPECIFICATIONS ARE TO AID IN PREPARATION OF DIVISION LEVEL STORE PLANS AND CONTRACT <br />DOCUMENTS. IN CASE OF A CONFLICT BETWEEN THIS SPECIFICATION AND THE CONTRACT DOCUMENTS PROVIDED BY <br />THE DIVISION CONSTRUCTION MANAGER, THE DIVISION'S PLANS AND SPECIFICATIONS SHALL PREVAIL. <br />DEFINITIONS <br />THE FOLLOWING DEFINITIONS APPLY TO THIS PROJECT. <br />FURNISH - TO SUPPLY THE MATERIAL NECESSARY TO PERFORM THE TASK. <br />INSTALL - TO SUPPLY THE LABOR NECESSARY TO COMPLETE THE TASK. <br />PROVIDE - TO FURNISH AND INSTALL MATERIAL AND LABOR TO COMPLETE THE TASK. <br />1. SCOPE <br />1.1 E.C. TO PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT (U.N.O.) REQUIRED TO EXECUTE WORK PER NEC AND <br />ALL APPLICABLE ELECTRICAL CODES IN FORCE AT THE TIME OF PROJECT COMPLETION. <br />1.2 THIS WORK INCLUDES, BUT IS NOT LIMITED TO: ELECTRICAL SERVICE AND DISTRIBUTION SYSTEMS, PANELBOARDS, <br />DISCONNECT SWITCHES, LIGHTING FIXTURES, POWER AND CONTROL WIRING WITH FINAL CONNECTIONS TO ALL <br />EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM. <br />1.3 E.C. TO VERIFY TYPE OF POWER SERVICE AVAILABLE (UNDERGROUND OR OVERHEAD) AND <br />MAXIMUM SHORT CIRCUIT CURRENT PRIOR TO SUBMITTING A PROPOSAL. <br />1.4 E.C. TO VERIFY TYPE OF TELEPHONE SERVICE AVAILABLE (UNDERGROUND OR OVERHEAD) <br />PRIOR TO SUBMITTING A PROPOSAL. <br />1.5 E.C. TO VERIFY METERING, IN ACCORDANCE WITH LOCAL ELECTRIC UTILITY COMPANY REQUIREMENTS, FOR <br />GENERAL SERVICE SCHEDULE. <br />1.6 E.C. SHALL INSTALL 3-PHASE 4-WIRE 120/208V WYE SERVICE, IF FOR ANY REASON, THIS IS <br />NOT AVAILABLE, THE E.C. SHALL NOTIFY 7-ELEVEN, IN WRITING PRIOR TO SUBMITTING OF <br />PROPOSAL (U.N.O.). <br />1.7 E.C. TO PROVIDE PANELBOARD NAMEPLATES. PROVIDE LAMINATED PLASTIC NAMEPLATES WITH 3/4 INCH <br />MINIMUM CONTRASTING -COLOR ENGRAVED LETTERS IDENTIFYING EACH PANELBOARD. <br />2. INSTALLATION <br />2.1 THE INSTALLATION SHALL COMPLY WITH ALL LAWS IN EFFECT AT THE TIME OF CONSTRUCTION APPLYING TO <br />ELECTRICAL INSTALLATION, AND WITH THE REGULATIONS OF THE NEC, WHERE SUCH REGULATIONS DO NOT <br />CONFLICT WITH THE LAWS IN EFFECT, AND WITH THE PUBLIC UTILITY COMPANY FURNISHING THE SERVICE. <br />2.1.1 THE E.C. SHALL UPGRADE THESE SPECIFICATIONS AS REQUIRED TO MEET COMPLIANCE WITH ALL <br />APPLICABLE CODES IN EFFECT; HOWEVER, WHERE THESE SPECIFICATIONS MAKE STIPULATIONS OVER AND <br />ABOVE THE MINIMUM REQUIREMENTS OF APPLICABLE CODES, THE CONTRACTOR SHALL NOT DOWN -GRADE <br />THESE SPECIFICATIONS TO MINIMUM CODE REQUIREMENTS WITHOUT PRIOR WRITTEN APPROVAL FROM <br />7-ELEVEN. <br />2.2 E.C. SHALL PROVIDE ALL REQUIRED ELECTRICAL CONDUIT AND WIRING FOR ALL MOTORS, MOTOR STARTERS <br />AND ELECTRICAL CONTROLS, U.N.O. E.C. SHALL MAKE ALL LINE VOLTAGE ELECTRICAL CONNECTIONS AS <br />REQUIRED FOR HVAC SYSTEMS. <br />2.3 E.C. SHALL INSTALL THE CONNECTIONS TO ALL RECEPTACLES, SALES COUNTERS, <br />GONDOLAS AND FINAL CONNECTIONS TO ALL FIXTURES AFTER FIXTURES ARE IN PLACE. <br />2.4 E.C. SHALL VERIFY EXACT LOCATION OF ALL SIGNS WITH 7-ELEVEN REPRESENTATIVE, PROVIDE ALL CONDUITS AND <br />WIRES WITH STUB -UPS AS DIRECTED BY THE 7-ELEVEN CORPORATION AND INSTALL FINAL CONNECTIONS AS <br />REQUIRED. <br />2.5 WIRING <br />2.5.1 ALL WORK SHALL BE COMPLETED IN A NEAT AND WORKMAN -LIKE MANNER. THE E.C. SHALL <br />CONTACT THE 7-ELEVEN CORPORATION REPRESENTATIVE SHOULD THIS PLAN REQUIRE MODIFICATION TO <br />COMPLY WITH LOCAL CODES. <br />2.5.2 ALL CONDUCTORS SHALL BE RUN IN APPROVED METALLIC RACEWAY OR CONDUIT AND SHALL BE UNIFORMLY <br />COLOR CODED THROUGHOUT THE ENTIRE SYSTEM, SPLICES, TAPS, AND TERMINALS SHALL BE MADE ONLY IN <br />J BOXES, OUTLET BOXES AND PANELBOARDS. <br />2.5.3 THE E.C. SHALL ENSURE THE CONDUCTORS UTILIZED ARE IN KEEPING WITH GOOD PRACTICE FOR THE <br />CIRCUIT/PROTECTIVE DEVICES EMPLOYED. THE NEUTRAL CONDUCTOR (WHERE USED) SHALL HAVE <br />THE SAME AMPACITY AS THE ASSOCIATED PHASE. <br />2.5.4 THE E.C. SHALL ENSURE THAT CIRCUIT AMPACITY AND SHORT CIRCUIT/OVERLOAD PROTECTION IS <br />APPROPRIATE FOR THE EQUIPMENT BEING INSTALLED. UL LISTING CONDITIONS SHALL BE OBSERVED. <br />2.5.5 TO COMPLY WITH NEC/UL LISTING CONDITIONS, ROOFTOP UNITS MAY BE SHOWN WITH FUSED <br />DISCONNECT SWITCHES: <br />2.5.5.1 ALL FUSES SERVING MOTOR LOADS WILL BE OF THE DUAL ELEMENT TYPE. <br />2.5.5.2 DUE TO DIFFERENT INTERRUPTING CHARACTERISTICS, PANELBOARD CIRCUIT BREAKERS MAY BE <br />RATED HIGHER THAN THE DUAL ELEMENT FUSES THEY SUPPLY TO ENSURE SUFFICIENT STARTING <br />CURRENT. <br />2.5.6 WIRE SIZES LISTED ARE MINIMUM. CONDUCTORS SHALL BE SELECTED SUCH THAT THE MAXIMUM VOLTAGE <br />DROP (AT FULL LOAD AMPS) SHALL NOT EXCEED THE FOLLOWING GUIDELINES: <br />2.5.6.1 PANEL FEEDERS --2% OF CIRCUIT VOLTAGE AT SERVICE. <br />2.5.6.2 ALL BRANCH LOADS--3% OF CIRCUIT VOLTAGE AT SERVICE. <br />2.5.6.3 TOTAL VOLTAGE DROP (SERVICE TO LOAD)--5% OF CIRCUIT VOLTAGE AT SERVICE. <br />2.5.7 SPECIAL NOTES ON SERVICES: <br />2.5.7.1 120/208V, 3-PHASE, WYE <br />THE E.C. SHALL CHECK THE REQUIREMENTS OF ALL EQUIPMENT AND WILL INSTALL <br />AUTOTRANSFORMERS (BUCK AND BOOST TRANSFORMERS) AS REQUIRED. <br />2.5.8 THE E.C. SHALL PROVIDE DEDICATED CIRCUITS WITH ISOLATED GROUND FOR ALL CIRCUITS <br />ORIGINATING FROM PANEL S. THE PURITY OF THE ISOLATED GROUND SHALL BE MAINTAINED BY USING ONLY <br />INSULATED GROUNDING CONDUCTORS AND ISOLATED GROUND. THE GROUNDING CONDUCTOR FOR THE. <br />ISOLATED GROUND SHALL NOT MAKE ELECTRICAL CONTACT WITH THE COMMON EQUIPMENT GROUND OR <br />ANY ITEM CONNECTED TO THE COMMON EQUIPMENT GROUND (I.E. CONDUITS, "J"-BOXES, SWITCH BOXES, <br />ETC.) AT ANY POINT OTHER THAN AT THE SERVICE GROUNDING TERMINAL. SEE NEC 250.96(B). <br />2.6 WHEN REQUIRED, E.C. TO ENSURE INTEGRITY OF FIRE RATED WALLS WHERE ELECTRICAL EQUIPMENT <br />PENETRATES WALLS. SEAL PER SPECIFICATIONS FOR FIRE STOPPING, <br />2.7 ALL PENETRATIONS THROUGH EXTERIOR WALLS ARE TO BE MADE WITH LB CONDULETS OF THE APPROPRIATE <br />SIZE PER NEC. ALL PENETRATIONS ARE TO BE SEALED PER NEC. HORIZONTAL OR VERTICAL SUPPORTS FOR <br />RACEWAYS ARE TO COMPLY WITH NEC. WIRE TIES ARE NOT TO BE USED, U.N.O. <br />3. MATERIALS: <br />ALL MATERIALS AND DEVICES SHALL BE UL APPROVED AND SHALL CONFORM TO THE STANDARDS OF NEMA, NEC, <br />AND IEEE. <br />3.1 LIGHT FIXTURES: PER SCHEDULE ON ELECTRICAL PLAN, <br />3.2 RACEWAYS: ALL CONDUIT SHALL BE EITHER RIGID STEEL OR ELECTRICAL METALLIC TUBING (EMT). FOR IN SLAB <br />AND UNDERGROUND INSTALLATIONS, PVC OR RIGID STEEL SHALL BE USED. REFER TO FUELING SHEETS FOR <br />APPROVED FUELING SYSTEMS CONDUIT. INSTALL PER NEC. <br />3.3 FITTINGS AND BUSHINGS:ALL REQUIRED BENDS, FITTINGS, JUNCTION BOXES, ETC., WHETHER OR NOT THEY ARE <br />SHOWN ON THE DRAWINGS, SHALL BE INSTALLED TO SATISFY ALL APPLICABLE ELECTRICAL CODES AND STANDARDS <br />OF GOOD PRACTICE. ALL CONDUCTORS ENTERING/LEAVING A CONDUIT OR RACEWAY SHALL BE AFFORDED <br />ABRASION PROTECTION BY AN ADEQUATE BUSHING OR OTHER APPROVED MEANS. <br />3.4 OUTLET BOXES: SHALL BE STANDARD, STAMPED GALVANIZED STEEL BOXES; "J"-BOXES AND OUTLET BOXES USED AS <br />A PULL BOX SHALL BE PROVIDED WITH A SUITABLE COVER OF SAME MATERIAL AS BOX. <br />3.5 WIRING DEVICES: <br />INSTALL ON EACH AND EVERY OUTLET BOX, A WIRING DEVICE AND/OR COVERPLATE, ALL AS INDICATED BY SYMBOL <br />ON THE DRAWINGS. <br />3.5.1 WALL SWITCHES: <br />3.5.1.1 SINGLE POLE SWITCHES: <br />SINGLE POLE WALL SWITCHES SHALL BE SIMILAR AND EQUIVALENT; TO "LEVITON" <br />#CS120-2W 20A, 120-277VAC TOGGLE SWITCH (WHITE) WITH COVERPLATE FOR SINGLE <br />GANG OR (WHITE) COVERPLATE FOR DOUBLE GANG. <br />3.5.1.2 3-WAY SWITCHES: <br />3-WAY SWITCHES SHALL BE SIMILAR AND EQUIVALENT TO "BRYANT" #4503-120A, <br />120-277VAC 3-WAY SWITCH (WHITE HANDLE) AND (WHITE) COVERPLATE FOR <br />SINGLE GANG OR (WHITE) COVERPLATE FOR DOUBLE GANG. <br />3.5.1.3 SINGLE THROW, DOUBLE POLE EVAPORATOR SWITCH <br />SINGLE THROW, DOUBLE POLE SWITCHES SHALL BE SIMILAR AND EQUIVALENT TO "BRYANT" <br />#30322D 120-600VAC NEMA 3R ENCLOSED AC MANUAL MOTOR CONTROLLER/DISCONNECT. <br />3.5.2 NOT USED <br />3.5.3 CONVENIENCE OUTLET (20A): <br />20A CONVENIENCE OUTLETS SHALL BE SIMILAR AND EQUIVALENT TO "LEVITON" #CR20-W <br />2 POLE, 3 WIRE, 20 A 125V, DUPLEX GROUNDING RECEPTACLE WITH (WHITE) COVERPLATE <br />SIMILAR AND EQUIVALENT TO "LEVITON" #88003 FOR SINGLE DUPLEX OR "LEVITON" <br />#88016 FOR DOUBLE DUPLEX (QUAD). <br />3.5.4 OUTLET, ISOLATED GROUND (20A): <br />ISOLATED GROUND OUTLETS SHALL BE SIMILAR AND EQUIVALENT TO "LEVITON" #5362-IG <br />2 POLE, 3 WIRE, 20A, 125V, SINGLE, ISOLATED GROUND RECEPTACLE (ORANGE) WITH <br />(WHITE) COVERPLATE. <br />3.5.5 GFCI CONVENIENCE OUTLETS (INDOOR & OUTDOOR): <br />OUTDOOR GFCI OUTLETS SHALL BE WEATHER RESISTANT (WR) LABELED, EQUIVALENT TO <br />THE "LEVITON" #WR899-W 20A OUTLET WITH OUTDOOR COVERPLATE #4500B AND BACK <br />PLATE #63101. INDOOR GFCI OUTLETS SHALL BE EQUIVALENT TO "LEVITON" #7899-W, 20A <br />WITH (WHITE) COVERPLATE. <br />3.5.6 NOT USED <br />3.5.7 SAFETY SWITCHES: <br />SAFETY SWITCHES SHALL BE UL APPROVED GENERAL DUTY SAFETY SWITCHES WITH LOCK OFF <br />HANDLES SIMILAR AND EQUIVALENT TO THOSE MANUFACTURED BY "SQUARE-D". SWITCHES <br />WILL BE FUSIBLE OR NON -FUSIBLE AS INDICATED ON PLANS/LOCAL CODES AND WILL BE NEMA <br />TYPE 1 FOR INDOOR (DRY) INSTALLATION OR A NEMA TYPE 3R ENCLOSURE FOR OUTDOOR <br />INSTALLATION. FUSED SWITCHES SHALL HAVE REJECTION STYLE FUSE HOLDERS TO MATCH <br />LPN-RK CLASS RK1 FUSES. <br />3.5.8 NOT USED <br />3.5.9 PHOTO CELL (OUTDOOR): <br />ELECTRONIC LIGHT SENSOR SHALL BE THE TORK EPC-1. ENCLOSED IN A LEXAN HOUSING <br />WITH A 1/2" CONDUIT MOUNTING AND 180 DEGREE SWIVEL. INSTALL IN A WEATHER <br />TIGHT JUNCTION BOX ON THE ROOF PER MANUFACTURER'S RECOMMENDATIONS. SET <br />SENSOR TO 100 FOOT-CANDLE LEVEL. <br />3.5.9.1 LIGHTING CONTROLLER (OUTDOOR LIGHTING CONTROL): <br />THE LIGHTING CONTROLLER SHALL BE THE TORK LC-200 IN A NEMA 1 ENCLOSURE. <br />THE LC-200 IS USED IN CONJUNCTION WITH THE TORK EPC-1 PHOTOCELL. LIGHTING <br />CONTROLLER HAS A 2 TO 100 FOOT-CANDLE LIGHT ADJUSTMENT. <br />3.5.10 CONTACTOR (OUTDOOR LIGHTING CONTROL): <br />THE LIGHTING CONTACTORS FOR USE WITH THE OUTDOOR PHOTO CELLS SHALL BE <br />SIMILAR AND EQUIVALENT TO "SQUARE-D" ELECTRICALLY HELD LIGHTING CONTACTOR <br />CLASS 8903 TYPE LG-80 FORM F WITH 120V CONTROL COIL, NORMALLY OPEN CONTACTS <br />RATED AT 30 AMPS CONTINUOUS, IN NEMA TYPE 1 ENCLOSURE WITH FUSED CONTROL <br />CIRCUIT, REF LIGHTING CONTACTOR DETAIL. <br />3.5.11 PHOTO CELL BYPASS SWITCH: <br />THE PHOTOCELL BYPASS SWITCH SHALL BE A "BRYANT" #4801-L SINGLE POLE LOCK <br />TYPE 15A 120-277 VOLT SWITCH WITH KEY #6006 AND COVERPLATE (WHITE). <br />NOTE: NO SUBSTITUTION SHALL BE PERMITTED UNLESS THE E.C. CAN PROVE TO THE 7-ELEVEN <br />CORPORATION REPRESENTATIVE THAT THE PROPOSED SUBSTITUTE WILL OPERATE WITH <br />"BRYANT" KEY #6006. THE KEY SHALL BE TURNED OVER TO THE 7-ELEVEN CORPORATION <br />REPRESENTATIVE AT ACCEPTANCE (NOT LEFT IN SWITCH, CASH REGISTER, ETC.). <br />3.5.12 HEAT TRACE - FREEZER PIPE FREEZE PROTECTION (WHEN REQUIRED): <br />HEATING CABLE: FURNISH RAYCHEM 5XL1-CR WITH RAYCLIC-PC ELECTRICAL CONNECTION. XL <br />TRACE BY TYCO THERMAL CONTROLS, LLC. FOR EXTRA INFORMATION CONCERNING HEAT TRACE <br />SYSTEM CONTACT DAN PETERSEN WITH INDUSTRIAL HEATER (901-382-4761). <br />CIRCUIT BREAKER: PROVIDE SQUARE 'D' QO120EPD OR EQUIVALENT GFCI CIRCUIT BREAKER WITH <br />30mA TRIP. <br />NOTE: MECHANICAL CONTRACTOR TO INSTALL SELF REGULATING HEATING CABLE PER <br />MANUFACTURER'S REQUIREMENTS ON CONDENSATE DRAIN LINES INSIDE FREEZER BOXES THAT <br />ARE TO OPERATE AT OR BELOW 32 DEGREES F. <br />3.6 SERVICE/DISTRIBUTION EQUIPMENT: <br />PANEL AND DISTRIBUTION PANEL SHALL BE SQUARE 'D'. ALL SWITCH GEAR TO BE FURNISHED FROM <br />GRAYBAR, U.N.O. FOR PRICING AND PLACING ORDERS, CONTACT '7-ELEVEN' FOR THE APPROPRIATE <br />SALES DEPARTMENT. <br />3.6.1 NOT USED. <br />3.6.2 PANELBOARDS: <br />SQUARE'D' PANELBOARDS USED I -LINE CIRCUIT BREAKERS AND FITTED <br />WITH SQUARE 'D' BRANCH CIRCUIT BREAKERS ARE AS INDICATED ON PLANS. <br />USE AN APPROPRIATE SQUARE 'D' CIRCUIT BREAKER WITH EACH PANEL. CIRCUIT <br />BREAKERS SHALL BE TYPE QOXXX-"QO"-FRAME <br />3.6.2.1 PANEL 'F', IF REQUIRED, SHALL BE FED BY A SQUARE 'D' NO.8903SQG2VO2 CONTACTOR <br />AND SHALL BE WIRED FOR EMERGENCY SHUT DOWN. <br />3.6.2.2 UPON COMPLETION OF WORK, E.C. SHALL PROVIDE A TYPED DIRECTORY IN EACH <br />PANELBOARD. INCLUDE SYSTEM VOLTAGE, PHASING, CIRCUIT NUMBERING AND DESCRIPTIONS. <br />NOTE: PANEL RATINGS REQUIRED FOR HIGHER AIC REQUIREMENTS SHALL BE PRESENTED TO THE <br />DISTRIBUTOR FOR MODIFICATIONS TO THE GEAR SUBMITTAL. <br />3.6.3 WIREWAY: <br />THE WIREWAY SHALL BE SIMILAR AND EQUIVALENT TO "SQUARE D COMPANY" WIREWAY WITH <br />APPROPRIATE FITTING FOR THE PARTICULAR INSTALLATION. E.C. SHALL SIZE TO INSTALLATION <br />IN ACCORDANCE WITH NEC, GOOD PRACTICE AND CODES IN EFFECT AT TIME OF <br />INSTALLATION. <br />3.7 <br />OVERCURRENT/SHORT CIRCUIT PROTECTIVE DEVICES: <br />3.7.1 PANELBOARD BRANCH/FEEDER CIRCUIT BREAKERS: <br />ALL DOWNSTREAM BREAKERS MUST BE SQUARED' TO MAINTAIN SERIES LISTING. IF <br />FUSIBLE DISCONNECTS ARE USED, SQUARE 'D' PANEL BOARDS AND CIRCUIT BREAKERS <br />SHALL BE USED. <br />3.7.2 GROUND FAULT CIRCUIT INTERRUPTER (GFCI) BREAKERS: <br />GROUND FAULT CIRCUIT INTERRUPTER (GFCI) TYPE CIRCUIT BREAKERS SHALL BE <br />SIMILAR TO THE PANELBOARD CIRCUIT BREAKERS BUT WITH GROUND FAULT <br />PROTECTION WITH MATCHING A.I.C. RATING. GFCI BREAKERS SHALL BE UL <br />APPROVED AS CLASS A DEVICES IN ACCORDANCE WITH UL STANDARD #943. <br />3.7.3 FUSES, MAIN SWITCHBOARD: <br />MAIN SWITCHBOARD FUSES, IF REQUIRED, SHALL BE CLASS J CURRENT LIMITING FUSES <br />AS INDICATED ON PLANS. <br />3.7.4 FUSES, EQUIPMENT: <br />EQUIPMENT FUSES, IF REQUIRED, SHALL BE OF THE DUAL ELEMENT, TIME DELAY VARIETY <br />AS INDICATED ON PLANS. FUSES FOR HVAC/REFRIGERATION SHALL BE SIMILAR AND EQUIVALENT <br />TO COOPER BUSSMANN FUSE TYPE LPN-RK-SP, CLASS RK1 FOR THE APPROPRIATE AMPERAGE. <br />3.8 SPD SHALL BE PROVIDED BY GRAYBAR. <br />3.9 CONDUCTORS: <br />ALL CONDUCTORS SHALL BE COPPER, TYPE THHN, UNO. MINIMUM CONDUCTOR SIZE SHALL BE <br />#12 AWG. CONDUCTORS #10 AWG AND LARGER SHALL BE STRANDED. INSULATION TYPE SHALL <br />CONFORM WITH N.E.C. OR MANUFACTURER REQUIREMENTS. LIGHT FIXTURES SOMETIME REQUIRE <br />90 DEGREE WIRE. FOR THE PARTICULIAR APPLICATION. USE TYPE THWN IN WET LOCATIONS. <br />3.91 NM CABLE (ROMEX) SHALL NOT BE USED. <br />3.9.2 ALUMINUM CONDUCTORS SHALL NOT BE USED U.N.O. <br />3.9.3 METAL -CLAD CABLE (MC) SHALL BE PERMITTED FOR USE AS BRANCH CIRCUITS <br />IN WALL, CEILING OR CABINETRY. <br />4. TESTING AND INSPECTION <br />4.1 TESTING: <br />4.1.1 THE E.C. SHALL TEST, PRIOR TO ENERGIZING FOR THE FIRST TIME, <br />ALL PIECES OF ELECTRICAL EQUIPMENT TO ASSURE THEY HAVE THE <br />PROPER PHASE TO PHASE AND PHASE TO GROUND INSULATION AND TO BE <br />FREE OF SHORTS. AFTER ENERGIZING, EACH LUMINAIRE SHALL BE LIT <br />AND TESTED. <br />4.1.2 THE VARIOUS CIRCUITS SERVED FROM THE PANELBOARDS VARY IN LOADING. <br />THE E.C. SHALL CAREFULLY BALANCE THE LOAD ON EACH LEG OF <br />THE SERVICE. WHEN ALL LOAD IS TURNED ON AND THE SYSTEM IS OPERATING <br />AT 100%, THE INITIAL UNBALANCE SHALL NOT EXCEED 10%. <br />NOTE: WITH 3 PHASE DELTA, PHASES A AND C SHALL BE BALANCED WITHIN 10% PHASE B <br />(HIGH LEG) SHALL BE BALANCED AS CLOSELY AS POSSIBLE. <br />4.2 INSPECTION: <br />E.C. SHALL FURNISH AT THE COMPLETION OF THE PROJECT OR <br />EACH INSPECTION POINT OF THE PROJECT, AN INTERMEDIATE OR FINAL INSPECTION <br />CERTIFICATE FROM THE LOCAL INSPECTING AUTHORITY. <br />4.3 PERFORMANCE REQUIRED: <br />4.3.1 ALL EQUIPMENT AND FIXTURES SHALL BE PROPERLY CONNECTED WITH <br />ADEQUATE POWER AND CHECKED THOROUGHLY FOR PROPER OPERATION. <br />4.3.2 ALL EXPOSED EQUIPMENT SHALL BE INSTALLED AS PER DRAWINGS AND IS <br />SUBJECT TO INSPECTION FOR WORKMAN -LIKE APPEARANCE. <br />5. INDUSTRY -STANDARDS <br />5.1 THE FOLLOWING IS A LIST OF ABBREVIATIONS USED IN THE ELECTRICAL NOTES AND <br />SPECIFICATIONS. <br />NEC .....................NATIONAL ELECTRIC CODE, REF. COVERSHEET FOR APPLICABLE VERSION <br />NEMA, ................. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION <br />UL......,,................UNDERWRITERS LABORATORIES, INC. <br />HVAC...................HEATING, VENTILATING AND AIR CONDITIONING <br />IEEE ......................INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS <br />GFCI.....................GROUND FAULT CIRCUIT INTERRUPTER <br />AIC .......................AMPERES INTERRUPTING CAPACITY <br />UNO.....................UNLESS NOTED OTHERWISE <br />EC.........................ELECTRICAL CONTRACTOR <br />GC.........................GENERAL CONTRACTOR <br />6. UTILITY ACCOUNT OPEN PROCESS <br />6.1 GENERAL CONTRACTOR (GC) WORKS WITH THE UTILITY COMPANIES TO SET UP ALL <br />REQUIRED METERS AND ACCOUNTS ( ELECTRIC, NATURAL GAS, WATER) UNDER THE <br />GC COMPANY NAME <br />6.2 FOR CORPORATE AND NON BCP FRANCHISEE, GC OBTAINS OPEN FACILITY REQUEST <br />FORM FROM DEVELOPMENT PROJECT MANAGER (DPM). BLANK FORM IS LOCATED AT <br />7-ELEVEN HUB / OPERATIONS / DEVELOPMENT PROGRAM MANAGEMENT QUICK LINKS <br />6.3 AT LEAST FIFTEEN (15) DAYS PRIOR TO THE STORE OPEN DATE, GC MAILS <br />COMPLETED OPEN FACILITIES REQUEST FORM TO ECOVA AT <br />7-ELEVENOPCL@ECOVA.COM WITH A COPY TO THE DPM <br />6.4 BCP FRANCHISEES SET UP THEIR OWN UTILITIES AND THIS SET UP DOES NOT GO <br />THROUGH 7-ELEVEN,INC <br />rev 6/2016 <br />i <br />r • 110111 lei <br />Corporate Office: <br />3025 Highland Parkway, Suite 850 <br />Downers Grove, IL 60515 <br />Phone: 312.756,7778 <br />info@sevansolutions.com www.sevansolutions.com <br />Regional Office: <br />37704 Hills Tech Drive <br />Farmington Hills, MI 48331 <br />INTEGRITY I RESPECT I TEAMWORK I EXCELLENCE I CHARITY <br />Q REVISIONS <br />NO. DATE DESCRIPTION <br />1 11/04/20 OWNER/PEER REVIEW COMMENTS <br />II CONSULTANT II <br />3343 NORTH RIDGE AVENUE <br />ARLINGTON HEIGHTS, IL 60004 <br />TEL C847> 966-0290 <br />WWW,DEI-PE.COM <br />SEAL <br />AS <br />w � <br />36369 9 <br />��+�� EGI3T?,, <br />SIGNATURE <br />11/04/2020 <br />DATE <br />I I CUSTOMER I I <br />I I PROJECT DESCRIPTION I I <br />MAW KI-111A <br />I I PROJECT LOCATION <br />60 <br />7 SE EVERETT MALL <br />EVERETT, WA WAY <br />SHEET TITLE <br />SHEET MANAGEMENT <br />PROJECT NO.: _ 41564 <br />DATE ISSUED: 08-10-20 <br />DRAWN BY: SR <br />REVIEWED BY: DD <br />THIS DOCUMENT IS AND SHALL REMAIN THE PROPERTY OF <br />SEVAN MULTI -SITE SOLUTIONS, INC. <br />REPRODUCTION OR ALTERATION OFTHIS DOCUMENT WITHOUTTHE EXPRESSED <br />WRITTEN PERMISSION OF SEVAN MULTI -SITE SOLUTIONS, INC. IS PROHIBITED. <br />NOT PUBLISHED: ALL RIGHTS RESERVED.) <br />COPYRIGHT BYSEVAN MULTI -SITE SOLUTIONS, INC. 2073 <br />SHEET NUMBER <br />SF: 1.00 CC <br />JN:H:\20029.34 <br />FN: E3.0 ELECTRICAL_ SPECIFICATIONS <br />