NOTES: <br />1. CEILINGS CONSTRUCTED OF SCREW -OR -NAIL ATTACHED GYPSUM BOARD ON ONE <br />LEVEL THAT AREA SURROUNDED BY AND CONNECTED TO WALLS OR SOFFITS DETAILS REFERENCE: NORTHWEST ALL A CEILING BUREAU <br />THAT ARE LATERALLY BRACED TO THE STRUCTURE ABOVE ARE EXEMPT FROM <br />MAXIMUM RECOMMENDED LENGTHS FOR SEISMIC DESIGN REQUIREMENTS. REFERENCE 401-REVISED 12/2017 SUSPENSION SYSTEMS FOR ACOUSTICAL LAY -IN <br />VERTICAL STRUTS 2. CEILING AREAS EXCEEDING 1,000 SF, HORIZONTAL RESTRAINT OF THE CEILING T <br />THE STRUCTURAL SYSTEM (LATERAL FORCE BRACING) SHALL BE PROVIDED. CEILINGS SEISMIC DESIGN CATEGORIES D, E, AND F. <br />3. LATERAL FORCE BRACING IS THE USE OF VERTICAL STRUTS (COMPRESSION REFERENCED SOURCES PER HIERARCHY: 2015 INTERNATIONAL BUILDING CODE (IBC) <br />POSTS) & SPLAY WIRES. ' ' <br />EMT CONDUIT <br />1/2" <br />TO 6-10" <br />3/4" <br />TO T-8„ <br />V, <br />TO Y-9" <br />STEELSTUDS <br />1-5/8 X 20 GA. <br />TO 12'-0" <br />DDL 1-5/3 X 20 GA <br />TO 15'-0" <br />2-1/2" X 20 GA <br />TO 13'-6" <br />DBL 2-1/2" X 20 GA <br />TO 15-0" <br />ki <br />SCALE: NTS <br />4. <br />LATERAL FORCES BRACES SHALL BE 12' O.C. (MAX) AND BEGIN NO FURTHER THA <br />(AM. SOCIETY OF CIVIL ENGINEERS (ASC) 7-10, AMERICAN SOCIETY OF TESTING <br />5. <br />6 FROM WALLS. <br />SEISMIC SPLAY WIRES ARE TO BE 4 -12 GA. WIRES ATTACHED TO THE MAIN BEAN <br />MATERIALS (ASTM) C635, ASTM C636, ASTM E 580/E5 0M, AND CEILING AND INTERIOR <br />WIRES ARE ARRAYED 90' FROM EACH OTHER AND AT AN ANGLE NOT EXCEEDING <br />SYSTEMS CONSTRUCTION ASSOC. (CISCA). <br />45' FROM THE PLANE OF THE CEILING. <br />6 <br />SEISMIC SPLAY WIRES SHALL BE ATTACHED TO THE GRID AND TO THE <br />STRUCTURE IN SUCH A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF <br />NOT LESS THAN 200 POUNDS OR THE ACTUAL DESIGN LOAD WITH A FACTOR OF 2, <br />GENERAL RECOMMENDATIONS: <br />WHICHEVER IS GREATER. <br />7. <br />POWDER ACTUATED FASTENERS (PAFS), WHEN USED FOR SEISMIC APPLICATIONS <br />1. PARTITIONS THAT ARE TIED TO THE CEILING AND ALL PARTITIONS GREATER THAN 6 FEET IN HEIGHT SHALL BE LATERALLY <br />ARE PART OF THE PRESCRIPTIVE PATH IN SEISMIC DESIGN CATEGORIES D, E, AND <br />BRACED TO THE STRUCTURE. BRACING SHALL BE INDEPENDENT OF THE CEILING SPLAY BRACING SYSTEM. <br />F, AND SHALL HAVE AN ICC-ES FOR APPROVAL AND REQUIRE "SPECIAL <br />2 FOR FURTHER INFORMATION ON BRACING OF NON -LOAD BEARING PARTITIONS REFER TO THE NWCB TECHNICAL DOCUMENT <br />INSPECTION" IRRESPECTIVE OF THE TYPE OF OCCUPANCY CATEGORY THE <br />#200-501 <br />STRUCTURE IS IN. PAF ANCHORS FOR KICKER WIRES (SPLAYED WIRES INSTALLED <br />3. ALL MAIN BEAMS ARE TO BE HEAVY DUTY (HD). <br />FOR PURPOSES OTHER THAN SEISMIC RESTRAINT) ARE EXEMPT FORM THIS REQ. <br />4. CEILINGS LESS THAN 144 SQ. FEET AND SURROUNDED BY WALLS CONNECTED TO THE STRUCTURE ABOVE ARE EXEMPT FROM <br />8. <br />SPLAY WIRES ARE TO BE WITHIN 2 INCHES OF THE CONNECTION OF THE VERTICAL <br />THE SEISMIC DESIGN REQUIREMENTS. <br />STRUT TO SUSPENDED CEILING. <br />5. THESE RECOMMENDATIONS ARE INTENDED FOR SUSPENDED CEILINGS AND RELATED COMPONENTS IN AREAS THAT REQUIRE <br />9. <br />RIGID BRACING MAY BE USED IN LIEU OF SPLAY WIRES. <br />RESISTANCE TO THE EFFECTS OF EARTHQUAKE MOTIONS. <br />10. <br />CEILINGS WITH PLENUMS <12 INCHES TO STRUCTURE ARE NOT REQUIRED TO <br />HAVE LATERAL FORCE BRACING. <br />ELECTRICAL FIXTURES <br />1. LIGHT FIXTURES WEIGHING < 10 LBO SHALL HAVE ONE 12 GAGE HANGER WIRE CONNECTED FROM THE FIXTURES TO THE <br />STRUCTURE ABOVE, THIS WIRE MAY BE SLACK. <br />2. LIGHT FIXTURES WEIGHING > 10 LBS. AND < 56 LBS. SHALL HAVE TWO 12 GAGE WIRES ATTACHED AT OPPOSING CORNERS OF <br />THE LIGHT FIXTURE TO THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK. <br />3. LIGHT FIXTURES WEIGHING > 56 LBS, SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE BY APPROVED HANGERS. <br />4. PENDANT MOUNTED FIXTURES SHALL BE DIRECTLY SUPPORTED FROM THE STRUCTURE ABOVE USING A 9 GA. WIRE OR AN <br />APPROVED ALTERNATE SUPPORT WITHOUT USING THE CEILING SUSPENSION SYSTEM FOR DIRECT SUPPORT. <br />5. TANDEM FIXTURES MAY UTILIZE COMMON WIRES. <br />`3 <br />MECHANICAL SERVICES <br />1. TERMINALS OR SERVICES WEIGHING < 20 LBS. SHALL BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION MAIN RUNNERS <br />OR TO CROSS RUNNERS THAT HAVE THE SAME CARRYING CAPACITY AS THE MAIN RUNNERS. <br />(MAX. ANGLE MAX. 45° ANGLE 2. TERMINALS OR SERVICES WEIGHING > 20 LBS. BUT NOT MORE THAN 56 LBS. SHALL HAVE, IN ADDITION TO 5.4.1, TWO 12 GAGE <br />WIRES CONNECTING THEM TO THE CEILING SYSTEM HANGERS OR THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK, <br />3. TERMINALS OR SERVICES WEIGHING MORE THAN 56 LBS. SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE BY <br />APPROVED HANGERS. <br />NOTES: <br />SPRINKLERS <br />1. HANGER AND PERIMETER WIRES MUST BE PLUMB WITHIN 1 IN 6 UNLESS COUNTER SLOPING WIRES ARE PROVIDED. <br />WIRE &TIES TO BE 3 TIGHT TURNS AROUND ITSELF WITHIN 3". <br />1. FOR CEILING WITHOUT RIGID BRACING, SPRINKLER HEAD PENETRATIONS SHALL HAVE A 2 IN. OVERSIZE RING, SLEEVE, OR <br />2. HANGER WIRES SHALL BE 12 GAGE AND SPACED 4 FEET ON CENTER OR 10 GAGE SPACED 5' O.C. ANY <br />ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF AT LEAST 1 IN. IN ALL HORIZONTAL DIRECTIONS. <br />CONNECTION DEVICE AT THE SUPPORTING CONSTRUCTION SHALL BE CAPABLE OF CARRYING NOT LESS THAN 100 # <br />FLEXIBLE HEAD DESIGN THAT CAN ACCOMMODATE 1 INC. FREE MOVEMENT SHALL BE PERMITTED AS AN ALTERNATE. <br />3. POWDER ACTUATED FASTENERS (PAFs) ARE AN APPROVED METHOD OF ATTACHMENT FOR HANGER WIRES. <br />4. TERMINAL ENDS OF EACH MAIN BEAM AND CROSS TEE MUST BE SUPPORTED WITHIN 8"OF EACH WALL WITH A <br />PERIMETER WIRE. <br />5. WIRES SHALL NOT ATTACH TO OR BEND AROUND INTERFERING MATERIAL OR EQUIPMENT. A TRAPEZE OR <br />EQUIVALENT DEVICE SHALL BE USED WHERE OBSTRUCTIONS PRECLUDE DIRECT SUSPENSION. TRAPEZE <br />SUSPENSIONS SHALL BE ABLE TO RESIST THE DEAD LOAD AND LATERAL FORCES APPROPRIATE FOR THE SEISMIC <br />CATEGORY, <br />SCALE: NTS <br />WOOD <br />2X SUBPURLIN OR 4X <br />PURLIN OR GLB <br />CONNECTION a@ CENTERLINE <br />MEMBER <br />3 TURNS <br />_VERTICAL WIRE <br />HANGER-300# MIN. <br />2X6 MIN. SUBPURLIN OR 4X <br />PURLIN OR GLB <br />(2) 5/16"X21AG SCREWS <br />MTL STUD VERTICAL BRACE <br />SIZE PER CHART DETAIL 1, <br />ATTAU"14MENTS @ WID"' D'IEUN, <br />NTS <br />WALL MOLDINGS: <br />1. WALL MOLDINGS (PERIMETER CLOSURE ANGLES) ARE REQUIRED TO HAVE A HORIZONTAL <br />FLANGE 2 INCHES WIDE, ONE END OF THE CEILING GRID SHALL BE ATTACHED TO THE WALL 8" MA <br />MOLDING, THE OTHER END SHALL HAVE A 3/4 INCH CLEARANCE FROM THE WALL AND FREE WALL <br />TO SLIDE. <br />2. WHERE SUBSTANTIATING DOCUMENTATION HAS BEEN PROVIDED TO THE LOCAL <br />JURISDICTION, PERIMETER CLIPS MAY BE USED TO SATISFY THE REQUIREMENTS FOR THE 2" 0 <br />CLOSURE ANGLE. U` 0 <br />3. THE GRID SHALL BE ATTACHED AT TWO ADJACENT WALLS (POP RIVETS OR APPROVED <br />METHOD) SOFFITS EXTENDING TO A POINT AT LEAST LEVEL WITH THE BOTTOM PLANE OF 3/4" MIN. AT UNATTACH <br />THE GRID AND INDEPENDENTLY SUPPORTED AND LATERALLY BRACED TO THE STRUCTURE <br />ABOVE ARE DEEMED TO BE EQUIVALENT TO WALLS. T 2" MIN. <br />SPREADER BARS: <br />1. TERMINAL ENDS OF MAIN RUNNERS AND CROSS MEMBERS SHALL BE TIED TOGETHER OR HAVE <br />SOME OTHER APPROVED MEANS TO PREVENT THEIR SPREADING, STABILIZER BARS, CROSS 8" MA <br />TEES OR OTHER MEANS TO PREVENT SPREADING SHALL OCCUR WITHIN 8 IN. OF EACH WALL, WALL <br />2. SPREADER BARS ARE NOT REQUIRED AT PERIMETERS WHERE RUNNERS ARE ATTACHED <br />DIRECTLY TO CLOSURE ANGLES. <br />3. SPREADER BARS ARE NOT REQ. IF A 90 DEGREE INTERSECTING CROSS OR MAIN IS WITHIN 8 � <br />INCHES OF THE PERIMETER WALL. <br />4. WHERE SUBSTANTIATING DOCUMENTATION HAS BEEN PROVIDED TO THE LOCAL JURISDICTION, 3/4" MIN. AT UNATTA / <br />PERIMETER CLIPS MAY BE USED TO SATISFY THE REQUIREMENTS FOR SPREADER BARS. <br />2" MIN, <br />WALL MOLDINGS: <br />SPRE"ADER BAR & WALL MOLDING <br />NTS <br />RIMETER HANGER WIRE <br />3/4" MIN. FLANGE <br />NOTES: POP RIVET <br />1 FOR CEILING AREAS EXCEEDING 2,500 SQ. FT., A SEISMIC SEPARATION JOINT OR FULL HEIGHT WALL PARTITION THAT BREAKS THE <br />CEILING SHALL BE PROVIDED UNLESS ANALYSES ARE PERFORMED OF THE CEILINGS BRACING SYSTEM, CLOSURE ANGLES AND <br />PENETRATIONS TO PROVIDE SUFFICIENT CLEARANCE. <br />2. THE LAYOUT AND LOCATION OF THE SEISMIC SEPARATION JOINT SHALL BE PER THE DESIGNER OF RECORD AND NOTED ON THE <br />PLANS. IF A SEISMIC SEPARATION JOINT IS REQ. BY THE DESIGNER, THE DESIGNER MAY USE THE GENERIC JOINT DETAILED <br />DETAILED IN THIS DOCUMENT OR PROPRIETARY JOINT, THE AMOUNT OF FREE MOVEMENT (GAP DESIGN) SHALL BE A MINIMUM OF <br />3/4". <br />3. IN LIEU OF SEISMIC SEPARATION JOINTS, THE CEILING MAY BE DIVIDED INTO AREAS <2500 SF BY THE USE OF PARTITIONS OR <br />SOFFITS AS FOLLOWS: PARTITIONS SHALL EXCEED A MINIMUM OF 6" ABOVE THE LEVEL PLANE OF THE GRID AND SHALL BE <br />INDEPENDENTLY BRACED TO THE STRUCTURE ABOVE. SOFFITS SHALL EXTEND A POINT AT LEAST LEVEL WITH THE BOTTOM PLANE <br />OF THE GRID AND SHALL BE INDEPENDENTLY SUPPORTED AND LATERALLY BRACED TO THE STRUCTURE ABOVE. <br />SEISMIC SEPARATION JOINT <br />l A 1 <br />SCALE: NTS <br />ATTACHED WALL <br />MOLDING REQ. <br />UNATTACHED WALL <br />MOLDING REQ. <br />SPREADER BAR OR EQUAL TO <br />KEEP PERIMETER COMPONENTS <br />FROM SPREADING APART <br />45' MAX <br />LIGHTING NOTES: <br />SEE SHEET A1.3 FOR CEILING DETAILS <br />PROVIDE FIRE DAMPERS AT ALL SUPPLY AND RETURN AIR OUTLETS, INLETS, OR DUCTS PENETRATING FIRE RAT .D <br />ASSEMBLIES ENCLOSURES WALLS FLOORS OR SURFACES AND AS REQUIRED BY FIRE DEPARTMENT IF APPLI ABLE. <br />CONTRACTOR SHALL OBTAIN APPROVAL FROM ARCHITECT OR BUILDING MANAGER/OWNER FOR ALL THERMOS AT <br />LOCATIONS. <br />ALL REQUIRED EXIT SIGNS SHALL HAVE LETTERS SIX INCHES HIGH MINIMUM, HAVE BATTERY BACK UP, INTEGR TED <br />EMERGENCY LIGHTING AND SHALL CONFORM WITH ALL APPLICABLE CODES. CONTRACTOR TO PROVIDE OR V IFY <br />THAT ALL EMERGENCY PATH LIGHTING MEETS ALL APPLICABLE CODE REQUIREMENTS. EMERGENCY LIGHTING OWN <br />IS FOR INFORMATION ONLY AND MUST BE CONFIRMED ON SITE TO MEET ALL LIFE SAFETY CODES. <br />CEILING HEIGHTS ARE FROM SLAB TO FIN. CEILING. MATCH EXISTING CEILING HTS FOR ALL WORK SHOWN LION <br />LIGHT SWITCHES SHALL BE INSTALLED AT +48" A.F.F. MULTIPLE SWITCHES SHOULD BE GANGED TOGETHER UN ESS <br />OTHERWISE SPECIFIED. <br />CONTRACTOR SHALL PROVIDE EMERGENCY LIGHTING, SENSORS, STROBE LIGHTS, AND AUDIO-VISUAL ALARM TO <br />MEET ALL APPLICABLE CODES. <br />CONTRACTOR TO VERIFY ALL SWITCH LOCATIONS WITH TENANT PRIOR TO INSTALLATION. NUMBER OF SWITC ES FOR <br />OPEN AREA IS BIDDER DESIGN. SWITCHES INDICATED ON DRAWING FOR OPEN AREA ARE FOR REFERENCE 0 Y. <br />CONTRACTOR TO CONFIRM DAY LIGHT AREAS AND PROVIDE SWITCHING TO MEET CURRENT ENERGY CODE <br />REQUIREMENTS FOR DAYLIGHT AREAS IS THESE AREAS ARE AFFECTED BY THE CONSTRUCTION. RESWITCH E STING <br />SWITCH LOCATIONS AS REQUIRED: RESWITCH LIGHTING CIRCUITS AS REQUIRED WHEN AREAS ARE AFFECTE BY <br />DEMOLITION OR CONSTRUCTION. <br />CONTRACTOR SHALL PROVIDE SEISMIC BRACING @ ALL NEW & RELOCATED FIXTURES PER NWCB 12/2017, <br />LIGHTING LEGEND nR®DE BID ALT. TO REPLACE W/ LE <br />EXISTING WALL MOUNTED OR CEILING MOUNTED EXIT SIGN W/ INTEGRATED EMERGENCY PAT <br />ExeT LIGHTING W/ BATTERY BACKUP, SIGN TO INCLUDE DIRECTIONAL ARROW, IF INDICATED OR WHE <br />APPLICABLE. <br />PROVIDE NEW EMERGENCY PATH LIGHTING MOUNTED W/ BATTERY BACK UP AS REQ. PER C DE, <br />VERIFY MOUNTING HEIGHT -MIN. 84" REQ. OR ON CEILING PER MFG. - 3 W <br />B/S EX ARMSTRONG CEILING GRID AND TILE, PATCH AND REPAIR WALLS AS REQUIRED, AND P VIDE <br />B/S NEW ARMSTRONG TILE -PAINT PER FINISH PLAN AFTER REPAIRS/NEW TILE INSTALLED - E GWB <br />CEILING IN BOTH RESTROOMS TO REMAIN, SEE DETAILS THIS SHEET & SHEET A1.3 <br />sT SUSPENDED TRACK LIGHT LIGHTOLIER ADVENT LYTESPAN TH10930NFIB 6101 NBK Oft TRACK OR 103NBK <br />8ft TRACK71200 LUMEN TRACK HEADS IN BLACK -install at 108" floor to bottom of fixture***-16 W P R LAMP <br />L B/S NEW 2 x 2 FLUORESCENT LAY -IN 2'X2' FIXTURE LITHONIA, 2FGG38L835-2-D-UNV-DIM - 33.5 <br />ALT. USE SURFACE MOUNTED IF USE ALT CEILING 2 FOR OFFICE. <br />OF NEW LED CEILING MOUNTED TREATMENT LIGHTING- PHILIPS SONG X772523199N0401-45.5 <br />oQ NEW FRONT DESK PENDANT - PHILIPS TC RD PS E26 THE JOINT/12NC: 828820210723 ***install 80" floor <br />to bottom of fixture*** - 9 W <br />oR DOWNLIGHT-PHI LIPS LYTECASTER-RECESSED CAN - L6RAE1VA / L6R15830WVA -16 W <br />0Rd DOWNLIGHT DIRECTIONAL-PHILIPS LYTECASTER RECESSED CAN - L6RAEIVA / L6RA15830WVA -16 W <br />Qum CAMERA LOCATIONS - LOW VOLTAGE AND SET AT 84" AFF - VERIFY SPECS WITH TENANT, <br />EX.RESTROOM EXHAUST FAN -MEET ALL CURRENT LOCAL CODES FOR RR EXHAUST FAN SYSTEMS - <br />CHECK FOR MECHANICAL INTEGRITY AND REPLACE IF REQUIRED, <br />B/S HVAC VENT LOCATIONS - SHOWN FOR INFORMATION ONLY -ANY CHANGES UNDER A <br />SEPARATE PERMIT <br />NEW LIGHT SWITCH (WITH OCCUPANCY AND DAYLIGHT SENSORS WHERE REQ. PER <br />CODES) SEE SHEET T 1.1 FOR SWITCH INSTALLATION DETAILS. SWITCHES SHOWN ONLY <br />WHERE NEW SWITCHES WILL BE REQUIRED. ALL OTHER LOCATIONS TO REMAIN, CHECK <br />ALL SWITCHES FOR GOOD WORKING ORDER. <br />E EXISTING <br />N NEW RL RELOCATED OR RETROFITTED <br />GENERAL LIGHTING NOTES: <br />0 PATCH & REPAIR GRID AS REQ. REPLACE DAMAGED TILE PRIOR TO PAINTING GRID. SEE SHEET 1 -1. <br />IF NOT REPAIRING GRID, THEN PROVIDE OPEN CEILING W/ NEW MECHANICAL VENTS AND USE ALT . <br />CEILING DETAILS AS SHOWN ON SHEET A1.3 FOR WALLS. NOTE THAT SOME LIGHTING WILL NEED 0 <br />BE CHANGED. VERIFY WITH JACK COLMER, JOINT CHIROPRACTOR'S SENIOR DESIGN ARCHITECT. <br />2 PROVIDE NEW LED LIGHTING PER THE LIGHTING LEGEND. VERIFY LIGHT LOCATIONS WITH <br />SPRINKLER HEAD LOCATIONS AS REQUIRED. NOTE LOCATIONS FOR ALL HVAC VENTS, PATH / <br />LIGHTING AND ALARM SYSTEMS. (UNDER SEPARATE PERMITS). <br />iJ <br />FJ <br />LL- <br />LLE <br />U <br />z <br />o� <br />w <br />[�?] <br />0 <br />U <br />0 <br />1 <br />9 <br />r <br />I� <br />NT <br />I <br />►i <br />I <br />ON <br />IN <br />O <br />c <br />O <br />0 <br />t- <br />w <br />(N <br />04 <br />aco <br />/ I¢ <br />I <br />T ' REFLE-1ICTE'D CLG PL-AN; ,°, , <br />SPLAY WIRES ARE TO BE FOUR 12 GA. WIRES ATTACHED TO THE MAIN BEAM. <br />WIRES ARE ARRAYED 90' FROM EACH OTHER & AT AN ANGLE NOT EXCEEDING <br />- 45' FROM THE PLANE OF THE CLG. HANGER WIRES SHALL BE 12 GA. &4' O.C. OR <br />LATERAL FORCE BRACING (PERSPECTIVE) <br />10 GA. & 5' O.C. TERMINAL ENDS OF EA. MAIN OR CROSS TEE MUST BE <br />- <br />SUPPORTED WITHIN 8" OF EA. WALL. <br />12 GA. HANGER WIRE SPACED <br />4' O.C. ALL WIRE TIES TO BE 3 <br />TIGHT TURNS AROUND ITSELF <br />> WITHIN 3 INCHES. <br />OPTIONAL VERTICAL BRACING <br />SHALL BE 12' O.0 (MAX) AND BEGIN < <br />6' FROM WALLS -SEE CHART FOR <br />SIZES AND VERIFY LOCAL CODE <br />REQ, VERT. STRUTS MUST BE <br />POSITIVELY ATTACHED TO THE <br />COUNTER <br />SUSPENSION SYSTEM AND THE <br />SLOPE/SPLAYED <br />STRUCTURE ABOVE (WHEN USED.) SEISMIC BRACING WIRE <br />ATTACHMENT, SEE <br />CEILING BRACING <br />LAT. FORCE BRACING 4 EA. 12 <br />45' MAX GA, WIRE SECURED TO MAIN <br />ATTACHMENT DETAILS <br />THIS SHEET <br />COUNTER SLOPE/SPLAYED <br />RUNNER WITHIN 2'-0" OF <br />SEISMIC BRACING WIRE ATTACHMENT <br />CROSS TEE AND SPLAYED 900 <br />FROM EA. OTHER @ 12'-0" O.C. <br />1. <br />VERTICAL STRUTS MAY BE EMT CONDUIT, METAL STUDS <br />OR <br />2" <br />BOTH DIRECTIONS W/ FIRST <br />PROPRIETARY COMPRESSION POST. <br />POINT WITHIN 4'-0" FROM EA, <br />2. <br />CEILINGS W/ PLENUMS <12" DO NOT REQUIRE LATERAL FORCE <br />MAIN BEAM WALL <br />BRACING. "PROVIDE ENGINEERING IF PLENUM > I V-0" <br />CROSS TEE <br />NOTES: <br />1. THESE RECOMMENDATIONS ARE INTENDED FOR SUSPENDED CEILINGS <br />INCLUDING GRID, PANEL OR TILE, LIGHT FIXTURES AND AIR TERMINALS <br />WEIGHING NO MORE THAN 4 LBS./SF <br />2. ALL WIRE TIES ARE TO BE THREE INCHES. TWELVE GAGE HANGER WIRE <br />SPACED 4' O.C. CHANGES. <br />3. CHANGES TO CEILING PLANES WILL REQUIRE POSITIVE BRACING. <br />I k1 <br />8' <br />lWORK <br />I PLACE <br />RCHITECTURE <br />4� <br />c <br />C:) <br />fle <br />E- <br />iLr) <br />® 0 <br />®��� <br />U <br />4=1 <br />�s <br />®�� <br />LLA <br />Z U)� N <br />UU <br />fu <br />Go <br />@jam®" <br />®� <br />�U <br />fu <br />_ <br />(T) > <br />4_j� <br />0 <br />N <br />10226 <br />REGIDARC T <br />U) <br />� <br />>�� <br />� <br />Uj�re <br />W <br />®®LLU_ <br />®® <br />� <br />�®® <br />U)nZ) <br />rL <br />U) <br />V) <br />U) <br />W ICJ <br />�� <br />U U <br />N <br />Ljj <br />J <br />® <br />®®® <br />ILL LL <br />Uir� <br />NUS <br />JOB NUMBER: 1 WP-21025 <br />PM: VSS <br />SHEET: <br />SCALE: NTS <br />