Laserfiche WebLink
6A <br />45 <br />FT <br />FA <br />oa <br />TABLE R402.1.1 <br />INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT <br />CLIMATE ZONE <br />5 AND MARINE 4 <br />FENESTRATION U-FACTOR <br />0.30 <br />SKYLIGHT U-FACTOR <br />0.50 <br />CEILING R-VALUE <br />49 <br />WOOD FRAME WALL R-VALUE <br />21 int <br />FLOOR R-VALUE <br />30 <br />BELOW -GRADE WALL R-VALUE <br />10/15/21 int + TB <br />SLAB R-VALUE & DEPTH <br />10, 2 ft <br />WHOLE HOUSE MECHANICAL VENTILATION SYSTEM <br />(CHECK THE BOX ADJACENT TO THE WHOLE HOUSE VENTILATION SYSTEM CHOSEN) <br />Effective July 1, 2016 <br />M1507.3 Whole -house mechanical ventilation system. Whole house mechanical ventilation systems shall be designed in accordance with <br />Sections M1507.3.1 through M1507.3.7. <br />M1507.3.1 System design. Each dwelling unit or guestroom shall be equipped with a ventilation system complying with Section M1507.3.4, <br />M1507.3.5, M1507.3.6 or M1507.3.7. Compliance is also permitted to be demonstrated through compliance with the International Mechanical <br />Code. <br />M1507.3.2 Control and operation. <br />1. Location of controls. Controls for all ventilation systems shall be readily accessible by the occupant. <br />2. Instructions. Operating instructions for whole -house ventilation systems shall be provided to the occupant by the installer of the system. <br />3. Local exhaust systems. Local exhaust systems shall be controlled by manual switches, dehumidistats, timers, or other approved means. <br />4. Continuous whole -house ventilation systems. Continuous whole -house ventilation systems shall operate continuously. Exhaust fans, <br />forced -air system fans, or supply fans shall be equipped with "fan on" as override controls. Controls shall be capable of operating the <br />ventilation system without energizing other energy -consuming appliances. A label shall be affixed to the controls that reads "Whole House <br />Ventilation (see operating instructions)." <br />5. Intermittent whole -house ventilation systems. Intermittent whole -house ventilation systems shall comply with the following: <br />5.1. They shall be capable of operating intermittently and continuously. <br />5.2. They shall have controls capable of operating the exhaust fans, forced -air system fans, or supply fans without energizing other <br />energy -consuming appliances. <br />5.3. The ventilation rate shall be adjusted according to the exception in Section 403.8.5.1. <br />5.4. The system shall be designed so that it can operate automatically based on the type of control timer installed. <br />5.5. The intermittent mechanical ventilation system shall operate at least one hour out of every four. <br />5.6. The system shall have a manual control and automatic control, such as a 24-hour clock timer. <br />5.7. At the time of final inspection, the automatic control shall be set to operate the whole -house fan according to the schedule used to <br />calculate the whole -house fan sizing. <br />5.8. A label shall be affixed to the control that reads "Whole House Ventilation (see operating instructions)." <br />M1507.3.2.1 Operating instructions. Installers shall provide the manufacturer's installation, operating instructions, and a whole -house <br />ventilation system operation description. <br />M1507.3.3 Mechanical ventilation rate. The whole -house mechanical ventilation system shall provide outdoor air to each habitable space at a <br />continuous rate of not less than that determined in accordance with Table M1507.3.3(1). <br />Exception: The whole -house mechanical ventilation system is permitted to operate intermittently where the system has controls that enable <br />operation for not less than 25 percent of each 4-hour segment and the ventilation rate prescribed in Table M1507.3.3(1) is multiplied by the <br />factor determined in accordance with Table M1507.3.3(2). <br />® WHOLE -HOUSE VENTILATION USING EXHAUST FANS <br />M1507.3.4 Whole -house ventilation using exhaust fans. This section establishes minimum prescriptive requirements for whole -house <br />ventilation systems using exhaust fans. A system which meets all the requirements of this section shall be deemed to satisfy the <br />requirements for a whole -house ventilation system. <br />M1507.3.4.1 Whole -house ventilation fans. Exhaust fans providing whole -house ventilation shall have a flow rating at 0.25 inches water gauge <br />as specified in Table M1507.3.3(1). Manufacturers' fan flow ratings shall be determined according to HVI 916 or AMCA 210. <br />M1507.3.4.2 Fan noise. Whole -house fans located 4 feet or less from the interior grille shall have a sone rating of 1.0 or less measured at 0.1 <br />inches water gauge. Manufacturer's noise ratings shall be determined as per HVI 915 (March 2009). Remotely mounted fans shall be <br />acoustically isolated from the structural elements of the building and from attached duct work using insulated flexible duct or other <br />approved material. <br />M1507.3.4.3 Fan controls. The whole -house ventilation fan shall meet the requirements of Section <br />M 1507.3.2 and M 1507.3.2.1. <br />M1507.3.4.4 Outdoor air inlets. Outdoor air shall be distributed to each habitable space by individual outdoor air inlets. Where outdoor air <br />supplies are separated from exhaust points by doors, provisions shall be made to ensure air flow by installation of distribution ducts, <br />undercutting doors, installation of grilles, transoms, or similar means. Doors shall be undercut to a minimum of 1/2 inch above the surface of <br />the finish floor covering. <br />Individual room outdoor air inlets shall: <br />1. Have controllable and secure openings; <br />2. Be sleeved or otherwise designed so as not to compromise the thermal properties of the wall or window in which they are placed; <br />3. Provide not less than 4 square inches of net free area of opening for each habitable space. Any inlet or combination of inlets which provide <br />10 cfm at 10 Pascals are deemed equivalent to 4 square inches net free area. <br />Inlets shall be screened or otherwise protected from entry by leaves or other material. Outdoor air inlets shall be located so as not to take <br />air from the following areas: <br />1. Closer than 10 feet from an appliance vent outlet, unless such vent outlet is 3 feet above the outdoor air inlet. <br />2. Where it will pick up objectionable odors, fumes or flammable vapors. <br />3. A hazardous or unsanitary location. <br />4. A room or space having any fuel -burning appliances therein. <br />5. Closer than 10 feet from a vent opening of a plumbing drainage system unless the vent opening is at least 3 feet above the air inlet. <br />6. Attic, crawl spaces, or garages. <br />WHOLE -HOUSE VENTILATION INTEGRATED WITH A FORCED -AIR SYSTEM <br />M1507.3.5 Whole -house ventilation integrated with a forced -air system. This section establishes minimum prescriptive requirements for <br />whole -house ventilation systems integrated with forced -air ventilation systems. A system which meets all the requirements of this section <br />shall be deemed to satisfy the requirements for a whole -house ventilation system. <br />M1507.3.5.1 Integrated whole -house ventilation systems. Integrated whole -house ventilation systems shall provide outdoor air at the rate <br />calculated using Section M1507.3.3. Integrated forced -air ventilation systems shall distribute outdoor air to each habitable space through <br />the forced -air system ducts. Integrated forced -air ventilation systems shall have an outdoor air inlet duct connecting a terminal element on <br />the outside of the building to the return air plenum of the forced -air system, at a point within 4 feet upstream of the air handler. The <br />outdoor air inlet duct connection to the return air stream shall be located upstream of the forced -air system blower and shall not be <br />connected directly into a furnace cabinet to prevent thermal shock to the heat exchanger. The system will be equipped with a motorized <br />damper connected to the automatic ventilation control as specified in Section M1507.3.2. The required flow rate shall be verified by field <br />testing with a flow hood or a flow measuring station. <br />M1507.3.5.2 Ventilation duct insulation. All supply ducts in the conditioned space shall be insulated to a minimum of R-4 <br />M1507.3.5.3 Outdoor air inlets. Inlets shall be screened or otherwise protected from entry by leaves or other material. Outdoor air inlets <br />shall be located so as not to take air from the following areas: <br />1. Closer than 10 feet from an appliance vent outlet, unless such vent outlet is 3 feet above the outdoor air inlet. <br />2. Where it will pick up objectionable odors, fumes or flammable vapors. <br />3. A hazardous or unsanitary location. <br />4. A room or space having any fuel -burning appliances therein. <br />5. Closer than 10 feet from a vent opening of a plumbing drainage system unless the vent opening is at least 3 feet above the air inlet. <br />6. Attic, crawl spaces, or garages. <br />WHOLE -HOUSE VENTILATION USING A SUPPLY FAN <br />M1507.3.6 Whole -house ventilation using a supply fan. This section establishes minimum prescriptive requirements for whole -house ventilation <br />systems using an inline supply fan. A system which meets all the requirements of this section shall be deemed to satisfy the requirements for <br />a whole -house ventilation system. <br />M1507.3.6.1 Outdoor air. Supply fan ventilation systems shall distribute outdoor air to each habitable space through the forced -air system <br />ducts or through dedicated ducts to each habitable space. Supply fans shall have the capacity to provide the amount of outdoor air specified <br />in Table M1507.3.3(1) at 0.40 inches water gauge as per HVI 916. The outdoor air must be filtered before it is delivered to habitable spaces. <br />The filter may be located at the intake device, in line with the fan, or, in the case of a connection to the return plenum of the air handler, <br />using the furnace filter. An outdoor air inlet shall be connected to either the supply or return air stream. <br />M1507.3.6.2 Ducts. An outdoor air inlet duct connection to the supply air stream shall be located downstream of the forced -air system <br />blower. An outdoor air inlet duct connection to the return air stream shall be located at least 4 feet upstream of the forced -air system <br />blower and its filter. Neither type of duct shall be connected directly into a furnace cabinet to prevent thermal shock to the heat exchanger. <br />The outdoor air inlet duct shall be prescriptively sized in accordance with Table M1507.3.6.2. The terminal element on the outside of the <br />building shall be sized 2 inches in diameter larger than the outdoor air inlet duct. <br />TABLE M1507.3.6.2 <br />PRESCRIPTIVE SUPPLY FAN DUCT SIZING <br />Supply Fan Tested CFM at 0.40" w.g. <br />SPECIFIED <br />MINIMUM <br />MINIMUM <br />VALUE FROM <br />SMOOTH DUCT <br />FLEXIBLE DUCT <br />TABLE <br />DIAMETER <br />DIAMETER <br />M1507.3.3(1) <br />50-90 cfm <br />4 inch <br />5 inch <br />90-150 cfm <br />5 inch <br />6 inch <br />150-120 cfm <br />6 inch <br />7 inch <br />250-400 cfm <br />7 inch <br />8 inch <br />M1507.3.6.3 Dampers. The system shall be equipped with a back -draft damper and one of the following: <br />1. A calibrated manual volume damper installed and set to meet the measured flow rates specified in Table M1507.3.3(1) by field testing with <br />a pressure gauge and/or following manufacturer's installation instructions; or <br />2. A manual volume damper installed and set to meet the measured flow rates specified in Table <br />M1507.3.3(1) by field testing with a flow hood or a flow measuring station; or <br />3. An automatic flow -regulating device sized to the specified flow rates in Table M1507.3.3(1) which provides constant flow over a pressure <br />range of 0.20 to 0.60 inches water gauge. <br />M1507.3.6.4 Ventilation duct insulation. All supply ducts in the conditioned space shall be insulated to a minimum of R-4. <br />M1507.3.6.5 Outdoor air inlets. Inlets shall be screened or otherwise protected from entry by leaves or other material. Outdoor air inlets <br />shall be located so as not to take air from the following areas: <br />1. Closer than 10 feet from an appliance vent outlet, unless such vent outlet is 3 feet above the outdoor air inlet. <br />2. Where it will pick up objectionable odors, fumes or flammable vapors. <br />3. A hazardous or unsanitary location. <br />4. A room or space having any fuel -burning appliances therein. <br />5. Closer than 10 feet from a vent opening of a plumbing drainage system unless the vent opening is at least 3 feet above the air inlet. <br />6. Attic, crawl spaces, or garages. <br />❑ WHOLE -HOUSE VENTILATION USING A HEAT RECOVERY VENTILATION SYSTEM <br />M1507.3.7 Whole -house ventilation using a heat recovery ventilation system. This section establishes minimum prescriptive requirements for <br />whole -house ventilation using a heat recovery ventilation system. <br />M1507.3.7.1 Heat recovery ventilation systems. All duct work in heat recovery systems shall be sized and installed per the manufacturer's <br />instructions. System minimum flow rating shall be not less than that specified in Table M1507.3.3(1). Heat recovery ventilation systems shall <br />have a filter on the upstream side of the heat exchanger in both the intake and exhaust airstreams with a minimum efficiency rating value <br />(MERV) of 6. <br />M1507.3.7.2 Ventilation duct insulation. All supply ducts in the conditioned space installed upstream of the heat exchanger shall be insulated <br />to a minimum of R-4. <br />M1507.3.7.3 Outdoor air inlets. Inlets shall be screened or otherwise protected from entry by leaves or other material. Outdoor air inlets <br />shall be located so as not to take air from the following areas: <br />1. Closer than 10 feet from an appliance vent outlet, unless such vent outlet is 3 feet above the outdoor air inlet. <br />2. Where it will pick up objectionable odors, fumes or flammable vapors. <br />3. A hazardous or unsanitary location. <br />4. A room or space having any fuel -burning appliances therein. <br />5. Closer than 10 feet from a vent opening of a plumbing drainage system unless the vent opening is at least 3 feet above the air inlet. <br />6. Attic, crawl spaces, or garages. <br />TABLE M1507.3.3(1) <br />CONTINUOUS WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS <br />DWELLING UNIT <br />NUMBER OF BEDROOMS <br />FLOOR AREA <br />(square feet) <br />0-1 <br />2-3 <br />4-5 <br />6-7 <br />>7 <br />< 1,500 <br />30 <br />45 <br />60 <br />75 <br />90 <br />1,501-3,000 <br />45 <br />60 <br />75 <br />90 <br />105 <br />3,001-4,500 - 1 <br />60 <br />75 <br />90 <br />105 <br />120 <br />4,501-6,000 <br />75 <br />90 <br />105 <br />120 <br />135 <br />6,001-7,500 <br />90 <br />105 <br />120 <br />135 <br />150 <br />> 7,501 <br />105 <br />120 <br />135 <br />150 <br />165 <br />For SI: 1 square foot = 0.029m , 1 cubic foot Oer minute = 0.0004719m/s 3 <br />TABLE M1507.3.3(2) <br />INTERMITTENT WHOLE -HOUSE MECHANICAL VENTILATION RATE FACTORS a,b <br />RUN-TIME PERCENTAGE IN <br />EACH 4-HOUR SEGMENT <br />25% <br />33% <br />1 50% <br />1 66% <br />75% <br />100% <br />FACTOR a <br />4 <br />3 <br />1 2 <br />1 1.5 <br />1.3 <br />1.3 <br />a. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation. <br />b. Extrapolation beyond the table is prohibited. <br />R406.3 ADDITIONAL ENERGY REQUIREMENTS <br />SMALLDWELLING UNIT: ...................................................................................................... 3.0 <br />DWELLING UNITS LESS THAN 1500 SQUARE FEET IN CONDITIONED FLOOR AREA WITH <br />I MCC TU A AI 4nn C V: nE: =_nlf=QTD ATfnnl A Dr - A <br />CREDIT(S) REQUIRED = 3.0 CREDITS PROVIDED = 3.5 <br />FUEL NORMALIZATION CREDITS FRO TABLE 406.2 <br />SYSTEM <br />TYPE <br />DESCRIPTION <br />CREDITS <br />FOR HEATING SYSTEM BASED ON ELECTRIC RESISTANCE WITH A DUCTLESS MINI -SPLIT <br />4 <br />HEAT PUMP SYSTEM IN ACCORDANCE WITH SECTION R403.7.1 INCLUDING THE EXCEPTION. <br />0.5 <br />ENERGY CREDITS FROM TABLE 406. <br />OPTION <br />DESCRIPTION <br />CREDITS <br />EFFICIENT BUILDING ENVELOPE <br />1.3 <br />Prescriptive compliance is based on Table R402.1.1 with the following modifications: <br />0.5 <br />Vertical fenestration U = 0.28 <br />Floor R-38 <br />V2- k c') <br />AIR LEAKAGE CONTROL AND EFFICIENT VENTILATION <br />2.1 <br />COMPLIANCE BASED ON R402.1.2: <br />0.5 <br />REDUCE THE TESTED AIR LEAKAGE TO 3.0 AIR CHANGES PER HOUR AT 50 PASCALS <br />AND <br />ALL WHOLE HOUSE VENTILATION REQUIREMENTS AS DETERMINED BY SECTION M1507.3 <br />OF THE IRC SHALL BE MET WITH A HIGH EFFICIENCY FAN(S) (MAXIMUM 0.35 WATTS/CFM). <br />HIGH EFFICIENCY HVAC EQUIPMENT OPTION <br />DUCTLESS MINI -SPLIT HEAT PUMP SYSTEM, ZONAL CONTROL. <br />3.4 <br />IN HOMES WHERE THE PRIMARY SPACE HEATING SYSTEM IS ZONAL, ELECTRIC HEATING, <br />1.5 <br />A DUCTLESS MINI -SPLIT HEAT PUMP WITH A MINIMUM HSPF OF 10.0 SHALL BE INSTALLED <br />AND PROVIDE HEATING TO THE LARGEST ZONE OF THE HOUSING UNIT. <br />APPLIANCE PACKAGE OPTION <br />7.1 <br />ALL OF TEH FOLLOWING APPLIANCES SHALL BE NEW AND INSTALLED IN THE DWELLING <br />UNIT AND SHALL MEET THE FOLLOWING STANDARDS: <br />0.5 <br />DISHWASHER - ENERGY STAR RATED <br />REFRIGERATOR (IF PROVIDED) - ENERGY STAR RATED <br />WASHING MACHINE - ENERGY STAR RATED <br />DRYER - ENERGY STAR RATED, VENTLESS DRYER WITH A MINIMUM CEF RATING OF 5.2 <br />S <br />U <br />DRNBY: J.HEILMAN <br />DATE: MAY 2022 <br />FILENAME: 22-05-02 <br />CD <br />00 <br />cc <br />00 <br />W <br />U. <br />-,I- <br />_J <br />i <br />C/) W< <br />Z <br />0 <br />• <br />MOO <br />0 <br />0 <br />0 <br />0 <br />SHEET <br />