THE RTU UNITS ARE AVAILABLE TO RUN 247. OPERATION SHALL BE SCHEDULED USING AN ELECTRONIC <br />SCHEDULER. THIS SCHEDULER SHALL HAVE AN OVER RIDE FEATURE SUCH THAT THE FACILITY CAN BE USED <br />DURING OFF HOURS. THE RTU SHALL START AT LEAST ONE HOUR PRIOR TO SCHEDULED OCCUPANCY FOR <br />MORNING WARM UP SEQUENCE. THE PURPOSE OF THIS IS TO PURGE THE BUILDING AND TEMPER THE <br />OCCUPIED BUSINESS.ADDITIONALLY, A I FOR A PERIOD OF <br />LEAST Pr - <br />BUSINESS CONCLUSION OF THE <br />EACH RTU HAS OUTSIDE AIR AND RELIEF AIR PATHS THAT PROVIDE FOR VENTILATION. MINIMUM VENTILATION AT <br />THE RTU UNITS SHALL BE SET FOR THE SUM OF THE IMC VENTILATION CALCULATIONS (PUBLISHED IN THIS <br />DRAWING SET) FOR EACH RTU. BEYOND VENTILATION, OUTSIDE AIR WILL ALWAYS BE USED IN AN ECONOMIZER <br />FUNCTION TO PROVIDE FREE COOLING ON DAYS WHERE OUTSIDE AIR TEMPERATURE SUPPORTS SUCH AN <br />APPROACH. IF THE UNIT IS IN COOLING AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN 55®F, MECHANICAL <br />COOLING SHALL BE LOCKED OUT. AS THE INDOOR AIR TEMPERATURE AND OUTDOOR AIR TEMPERATURE BOTH <br />RISE, THE CONTROLS WILL EXECUTE AN ALGORITHM USING A PID LOOP TO SET UNIT DISCHARGE AIR <br />TEMPERATURE. THE PREFERENCE IS FOR THE CALCULATED DISCHARGE AIR TEMPERATURE TO BE MAINTAINED <br />WITHOUT USING MECHANICAL COOLING, HOWEVER, IN THE COOLING SEASON THERE WILL BE TIMES WHEN THE <br />OUTDOOR AIR TEMPERATURE DOES NOT SUPPORT THIS, EITHER FULLY OR IN PART. IN THIS CONDITION, OUTSIDE <br />IS USED FOR VENTILATION ONLY AS DESCRIBED ABOVE TO MEET THE PUBLISHED VENTILATION RATE AND <br />MECHANICAL COOLING WILL BE USED TO SET THE DISCHARGE AIR TEMPERATURE. <br />DURING THE EXTREMES OF HEATING AND COOLING SEASON, THERE MAY BE INFREQUENT OCCURRENCE WHERE <br />THE iOTEMPERATURE THAN * O GREATERTHAN 88*F DURING TIMES WHEN THE BUILDING <br />IS NOT OCCUPIED. IN SUCH AN EVENT,THEHVAC SHALLD — INDOOR <br />AIR TEMPERATURE TO A MINIMUM OF 60*F OR COOLING TO BRING THE INDOOR AIR TEMPERATURE DOWN TO 85'F. <br />THE UNOCCUPIED DEAD BAND IS BETWEEN 60-F AND 85-F, AND WHEN THE INDOOR TEMPERATURES ARE IN THIS <br />RANGE, THE HVAC SYSTEM SHALL NOT RUN. THE ONLY EXCEPTION IS THE SPLIT SYSTEM EQUIPMENT THAT <br />SUPPORTS PROCESS LOADS, <br />HEATING AND COOLING SET POINTS ARE ADJUSTABLE BUT SHALL BE INITIALLY SET AT 707 FOR HEATING AND <br />777 FOR COOLING. THE WIDTH OF THE DEAD BAND SHALL ALWAYS REMAIN A MINIMUM OF 5®F AS REQUIRED <br />BY THE WSEC. <br />GREATEST.EXTERIOR ZONES HAVE THE ADVANTAGE OF FAN POWERED TERMINAL UNITS WITH AUXILIARY HEAT. THIS <br />PROVIDES AN ADDITIONAL HEATING MECHANISM TO THE AREAS WHERE HEAT LOSS IS EXPECTED TO BE THE <br />POWERED TERMINALO VENTILATION FUNCTION R THE SPACES THEY <br />THE CONTROLS SHALL POLE THE SENSORS IN THE SPACES TO DETERMINE THE SPACE CONDITIONS THAT EXIST. <br />THE DEFAULT OF THE SYSTEM SHALL BE HEATING. HOWEVER, IF TWO OR MOVE FPTU ZONES ON ANY RTU <br />CALLS FOR COOLING, THE RTU SHALL GO INTO COOLING USING A CALCULATED PID ALGORITHM TO COOL THESE <br />TWO ZONES WITHOUT DRASTICALLY OVERCOOLING THE REMAINDER OF THE SPACES. <br />RELATED TO PROCESS COOLING LOADS, EACH SPLIT SYSTEM HAS A PROGRAMMABLE ROOM SENSOR LOCATED IN <br />THE SPACE IT SERVES, THESE UNITS SHALL RUN 240 SINCE THEY SUPPORT PROCESS LOADS. <br />� •� i � - i r *ii r,�: <br />ALLOWIHE CONTROLS CONTRACTOR SHALL PROVIDE A USER INTERFACE. THIS USER INTERFACE SHALL O-. <br />ENVIRONMENTALSYSTEM CHECKS TO CONFIRM i i AND THE STATE <br />OF D iN _ <br />THE USER INTERFACE SHALL PROVIDE AN ALARM FUNCTION RELATED TO MAJOR EQUIPMENT FAILURES (RTU, FPTU <br />AND <br />PROCESS <br />:...- D SPLIT <br />A._ WELL r _IGH AND/OR <br />LOW TEMPERATURE <br />fir -RE ALARMS. <br />38898 � � <br />o��S joNaL <br />SIGNED: 12/11 /2020 <br />REVISIONS <br />1. PERMIT SET <br />2. <br />3. <br />4. e <br />5. <br />m- <br />JOB NUMBER <br />120010 <br />12-11-2020 <br />SHEET SIZE <br />ARCH D: 24" x 36" <br />SHEET TITLE <br />SHEET 21 OF 22 <br />