LARGE SMALL O.D.
<br />EXAM EXAM RECEPTION
<br />HVAC -- PLAN
<br />SCALE: 1/4" - V-0"
<br />I LL f REGISTER'
<br />l FF ALE
<br />TAG
<br />SERVICE
<br />(MOUNTING
<br />MFR
<br />MODEL
<br />MODULE SIZE
<br />FINISH
<br />NOTES
<br />S1
<br />SUPPLY
<br />SURFACE
<br />TITUS
<br />OMNI
<br />24" X 24"
<br />PAINT TO MATCH
<br />1, 2, 3
<br />AIR
<br />CEILING
<br />S2
<br />SUPIPRLY
<br />LAY -IN
<br />TITUS
<br />OMNI
<br />24" X 24"
<br />S T DI WHITE
<br />2
<br />R1
<br />RETURN
<br />SURFACE
<br />TITUS
<br />50F
<br />24" X 24"
<br />PAINT TO MATCH
<br />1, 2, 3
<br />AIR
<br />CEILING
<br />R2
<br />RETURN
<br />SURFACE
<br />TITUS
<br />50F
<br />24" X 12"
<br />PAINT TO MATCH
<br />1, 2, 3
<br />AIR
<br />CEILING
<br />R3
<br />RETURN
<br />LAY -IN
<br />TITUS
<br />50F
<br />24" X 12"
<br />STD. WHITE
<br />2
<br />AIR
<br />FINISH
<br />NOTES/ACCESSORIES
<br />1. SECTORIZING BAFFLES FOR DIRECTIONAL CONTROL WHERE NOTED ON DRAWINGS
<br />2. PROVIDE YOUNGS REGULATOR TO CONTROL
<br />BALANCING
<br />DAMPER IN AREAS WITH GYPSUM
<br />BOARD CEILING. INSTALL
<br />YOUNGS REGULATOR
<br />ON FACE OF
<br />AIR DEVICE PER DETAIL M014 ON M001.
<br />3. PAINT DIFFUSER TO MATCH THE ADJACENT CEILING
<br />FINISH.
<br />TAG MODEL TONS E.A.
<br />DI31WB
<br />RTU-1- -- YHC036E3RM - 3 80/67
<br />RTU-2 YHC092F3RM 7.5 80/67
<br />NOTES.
<br />1. EQUIPMENT IS SUPPLIED BY TENANT AND INSTALLED BY THE MECHANICAL CONTRACTOR.
<br />2. Provide hail guards
<br />3. Provide with comparative enthalpy economizer with barometric relief damper
<br />4. Provide MERV 13 filters.
<br />5. Provide hinged access panels.
<br />6. Provide hot gas reheat.
<br />1.110 7�1►�C
<br />I
<br />FAN CFM O:A. ESP
<br />HIP
<br />0.75 1280 150 0.5
<br />2.75 2520 280 0.5
<br />INPUT
<br />MBH
<br />80
<br />150
<br />ONT
<br />OIE
<br />DE CABLE OPERATED DAMPERS WHERE DAMPERS ARE INSTALLED OVER
<br />iM BOARD CEILING. PROVIDE YOUNGS REGULATOR AND BOWDEN CABLE
<br />APPLICABLE. IN AREAS WITH LAY -IN CEILING, ONLY A MANUAL VOLUME
<br />-R IS REQUIRED.
<br />)�N OVER NOTES (CONTRACTOR TO
<br />)VIDE TO THE PM THE FOLLOWING PRIOR
<br />INITIAL PUNCHLIST);
<br />1. AIR BALANCE REPORT TO STATE EQUIPMENT INFORMATION INCLUDING
<br />MODEL NUMBER, SERIAL NUMBER, RATED AND TESTED AMP DRAW, RATED
<br />AND TESTED VOLTAGE AND ANY ALTERATIONS OF THE EQUIPMENT
<br />REQUIRED TO ACHIEVE DESIGN AIR FLOW.
<br />2. CHANGE FILTER MEDIA PRIOR TO TURN OVER.
<br />3. DEMONSTRATE EQUIPMENT HEATS AND COOLS.
<br />4. CLEAN DRAIN PANS PRIOR TO TURN OVER.
<br />PROVIDE FIRE STOPPING FOR ALL PENETRATIONS OF FIRE WALLS. PROVIDE
<br />THROUGH WALL FIRE STOPPING FOR ALL LOCATIONS WHERE JUNCTION BOXES
<br />ARE LOCATED IN A DEMISING WALL, OR OTHER FIRE WALL.
<br />THESE DRAWINGS ARE RA D INDICATE WORK.
<br />CONTRACTORAD PROPER A
<br />ALL MECHANICAL SYSTEMS. THE CONTRACTOR SHALL PROVIDE D
<br />REQUIREDFITTINGS WHICH MAY BE DUE TO SPACE CONSTRAINTS
<br />ROUTE ALL NEW DUCTWORK AS TIGHT TO ROOF DECK AS POSSIBLE. NEW DUCTWORK SMALL BE
<br />ROUTED BETWEEN ROOF STRUCTURE AS NEEDED. COORDINATE WITH ALL TRADES AND PROVIDE
<br />OFFSETS AS REQUIRED TO AVOID CONFLICT.
<br />TAG
<br />ISTYLE
<br />jCFM
<br />I MAN UFACTURERI
<br />MODEL
<br />ISTATIC
<br />IVOLTAGE
<br />I POWER
<br />INOTES
<br />CEF-1
<br />CEILING I
<br />100
<br />LOREN-COOK
<br />GC-144
<br />1
<br />0.3751
<br />120
<br />104W
<br />1 1
<br />NOTES:
<br />1. CONTROL FAN WITH ROOM SWITCH
<br />OUTPUT VOLT/
<br />MCA
<br />MAX
<br />WT. DIMENSIONS
<br />NOTES
<br />MBH
<br />PHASE
<br />FUSE
<br />LENGTH (fl) WIDTH (ft)
<br />64
<br />208/3
<br />21
<br />30
<br />767
<br />5.82 1
<br />3.69
<br />1-6
<br />120
<br />208/3
<br />42
<br />1
<br />50
<br />1291
<br />7.39 1
<br />4.44
<br />1-7
<br />10 KEY NOTES - MECHANICAL PLAN I
<br />1. PROVIDE DAMPERS PER DETAIL.
<br />2. PROVIDE DUCT TAKE OFFS PER DETAIL. HIGH EFFICIENCY FITTINGS SHALL BE USED. SEE DETAIL.
<br />3. INSULATE ALL SUPPLY DUCTWORK PER APPLICABLE ENERGY/MECHANICAL CODE - MOST
<br />RESTRICTIVE TO GOVERN.
<br />4. REMOTE SENSOR. CONNECT TO MAIN THERMOSTAT.
<br />5. NOT USED.
<br />6. NOT USED.
<br />7. EXTEND 8" EXHAUST DUCT TO LANDLORD PROVIDED EXHAUST MAIN, VERIFY LOCATION IN
<br />FIELD, COORDINATE WORK WITH LANDLORD.
<br />8. CONTROL FAN WITH ROOM OCCUPANCY SENSOR.
<br />9. PROVIDE NEW THERMOSTAT WIRING FROM DEVICE TO RTU CONTROLLER. CONCEAL ALL
<br />CONTROL WIRING WITHIN WALLS AND ABOVE CEILING.
<br />10. INSTALL SMOKE DETECTOR IN RETURN DUCT ADJACENT TO ACCESS PANEL.
<br />11. PROVIDE NEW ROOF TOP UNIT (RTU) IN PLACE OF EXISTING WITH CURB ADAPTER. FIELD VERIFY
<br />EXACT LOCATION AND EXISTING CONDITIONS PRIOR TO BID.
<br />12. PROVIDE NEW ROOF TOP UNIT (RTU) IN LOCATION AS SHOWN WITH NEW 14" ROOF CURB.
<br />GENERAL NOTES - MECHANICAL PLAN
<br />A. ALL WORK MUST COMPLY WITH THE REQUIREMENTS OF LOCAL CODES AND ORDINANCES.
<br />WHERE INSPECTIONS ARE REQUIRED BY AUTHORITIES HAVING JURISDICTION, WORK MUST
<br />NOT BE CONCEALED UNTIL INSPECTIONS AND TESTING ARE COMPLETED AND ACCEPTED.
<br />B. PRIOR TO BID, GENERAL CONTRACTOR MUST BECOME THOROUGHLY FAMILIAR WITH THE
<br />REQUIREMENTS OF THE GENERAL NOTES AS WELL AS ALL OTHER NOTES SHOWN ON THE
<br />CONTRACT DOCUMENTS. VISIT THE SITE TO ESTABLISH THE EXISTING CONDITIONS PRIOR TO
<br />BID AND PRIOR TO ANY DUCT, PIPE OR EQUIPMENT FABRICATION, SYSTEMS MUST BE
<br />ERECTED USING GENERAL CONTRACTOR'S FIELD MEASUREMENTS FOR COORDINATION WITH
<br />EQUIPMENT, STRUCTURE, FIRE PROTECTION AND ELECTRICAL CONDITIONS IN THE SPACE.
<br />C. ALL CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
<br />ARRANGEMENTS OR GEOMETRICAL RELATIONSHIPS OF EQUIPMENT AND SERVICES. THEY ARE
<br />NOT INTENDED TO SPECIFY OR SHOW EVERY OFFSET, SEQUENCE, DEVICE, OPTION, FITTING,
<br />OR COMPONENT.
<br />D. THE CONTRACT DOCUMENTS REFLECT A SYSTEM DESIGNED AROUND SPECIFIC REFERENCE
<br />PRODUCTS, THE SELECTION OF WHICH HAS IMPACTED THE DESIGNS OF OTHER TRADES. IF
<br />ALTERNATE MANUFACTURERS ARE SUBMITTED OR BID, IT IS THE RESPONSIBILITY OF THIS
<br />GENERAL CONTRACTOR TO COORDINATE ALL DIFFERENCES AND IMPACTS WITH ALL
<br />TRADES PRIOR TO BID, INCLUDING COSTS ASSOCIATED WITH REQUIRED CHANGES TO OTHER
<br />TRADES. NO EXTRAS WILL BE ALLOWED FOR CHANGES REQUIRED TO OTHER TRADES IF
<br />ALTERNATE EQUIPMENT IS BID OR INSTALLED AT THE GENERAL CONTRACTOR'S OPTION.
<br />E. EXISTING MECHANICAL INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS
<br />AND FIELD WORK. THE GENERAL CONTRACTOR SHALL FIELD VERIFY THE EXISTING
<br />CONDITIONS FOR ACCURACY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED FOR
<br />REVISIONS TO THE DESIGN TO CORRECT FOR EXISTING CONDITIONS NOT AS INDICATED ON
<br />THE PLANS.
<br />F. GENERAL CONTRACTOR SHALL NOTIFY TENANT, ARCHITECT AND ENGINEER OF ANY
<br />SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN
<br />THE DOCUMENTS.
<br />G. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING/PATCHING RELATED TO
<br />THEIR WORK.
<br />H. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION
<br />MATERIALS ABOVE CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME
<br />SPREAD AND 50 SMOKE DEVELOPMENT FINISH RATING, WIRING SHALL BE LABELED PLENUM
<br />RATED TYPE PER NFPA 70.
<br />1. COORDINATE LOCATION AND ELEVATION OF MECHANICAL WORK WITH ALL DUCTWORK,
<br />LIGHT FIXTURES, AND OTHER CEILING BUILT-IN FIXTURES. CONTACT ENGINEER OR ARCHITECT
<br />IMMEDIATELY SHOULD ANY CONFLICT ARISE.
<br />J. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY A LANDLORD
<br />APPROVED ROOFING GENERAL CONTRACTOR AT THIS GENERAL CONTRACTOR'S EXPENSE.
<br />COORDINATE ROOF PENETRATIONS AND ROOFTOP EQUIPMENT LOCATIONS WITH
<br />LANDLORD AND GENERAL CONTRACTOR.
<br />K. NOTHING 1S PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF
<br />DECK. GENERAL CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF
<br />THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE TENANT SPACE,
<br />L. ALL ROOFTOP UNITS TO BE LOCATED ON FACTORY SUPPLIED ROOF CURBS.
<br />M. MAINTAIN A MINIMUM OF 10' CLEARANCE TO ANY OUTSIDE AIR INTAKES ON ROOF FOR ALL
<br />EXHAUST FANS.
<br />N. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE
<br />NUMBER AND EQUIPMENT IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND
<br />STANDARDS.
<br />O. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM
<br />INCLUDE ANGLE OF DIVERGENCE OF 15 DEGREE.
<br />P. DUCT SIZES INDICATED REPRESENT CLEAR INTERIOR SHEET METAL DIMENSIONS AND IF
<br />INTERNAL INSULATION IS SPECIFIED THE DIMENSIONS INCLUDE ALLOWANCE FOR INTERNAL
<br />INSULATION.
<br />Q. ALL SUPPLY AIR DUCTWORK NOT EXPOSED OR INTERNALLY LINED SHALL BE EXTERNALLY
<br />INSULATED. REFER TO SPECIFICATIONS.
<br />R. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE
<br />INDICATED. ALL ROUND DUCT ELBOWS SHALL BE LONG SWEEP, 1-1/2 TIMES THE CENTERLINE
<br />RADIUS. ALL CONDENSATE PIPING SHALL BE COPPER, AND INSULATED BELOW ROOF LINE.
<br />GENERAL CONTRACTOR SHALL VERIFY, PRIOR TO BID, THE CORRECT METHOD AND
<br />LOCATION OF CONDENSATE DISCHARGE FROM UNITS WITH THE LANDLORD,
<br />S. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR
<br />CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR
<br />THROUGH PRE -MANUFACTURED PIPING CURB.
<br />T. GENERAL CONTRACTOR MUST REPLACE ALL AIR FILTERS IN HVAC UNITS WITH NEW CLEAN
<br />FILTERS BEFORE AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT,
<br />U. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO VISIT THE JOB SITE PRIOR
<br />TO CONSTRUCTION TO FAMILIARIZE HIMSELF WITH MAJOR ITEMS SUCH AS STRUCTURAL
<br />ELEMENTS, PLUMBING LOCATIONS, ELECTRICAL RUNS AND POINTS OF CONNECTION TO
<br />EXISTING DUCT SYSTEMS. ADDITIONALLY, MECHANICAL CONTRACTOR SHALL VERIFY EXACT
<br />LOCATIONS AND DIMENSIONS OF SUCH ITEMS AS HVAC EQUIPMENT, DUCTWORK, ETC.
<br />PRIOR TO COMMENCING ANY WORK,
<br />V. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT THE MECHANICAL
<br />EQUIPMENT COMPONENTS ARE INSTALLED AT LOCATIONS AND ELEVATIONS WHICH MAKE
<br />THEM READILY AND SAFELY ACCESSIBLE FOR ROUTINE MAINTENANCE WITHOUT REQUIRING
<br />ANY EXTRAORDINARY MEASURES.
<br />W. THE TENANT RESERVES THE RIGHT TO CHECK CONSTRUCTION COMPLIANCE WITH PLANS
<br />AND SPECIFICATIONS. SHOULD THE TENANT FIND CORRECTIVE WORK NECESSARY, HE WILL
<br />NOTIFY GENERAL CONTRACTOR OF SUCH WORK IN WRITING AND EXPECT COMPLIANCE
<br />PERFORMED WITH DUE DILIGENCE. IF ANY CORRECTIVE WORK IS DEEMED TO BE NECESSARY,
<br />THE COST OF REINSPECT IONS WILL BE BORNE BY THE GENERAL CONTRACTOR. IF WORK IS
<br />REQUIRED BY TENANT IN ORDER TO IMPROVE, CHANGE OR CORRECT AIR CONDITIONING
<br />OPERATIONAL CONDITIONS DUE TO: PART MALFUNCTION, WARRANTY OR OTHER INABILITY
<br />TO PROVIDE THE COMFORT CONDITIONS REQUIRED BY THE STORE, GENERAL CONTRACTOR
<br />SHALL BE DIRECTED BY TENANT TO ADDRESS THIS WORK IN A TIMELY MANNER. IF IT
<br />BECOMES EVIDENT THAT THE GENERAL CONTRACTOR CAN NOT ACCOMPLISH THE TASK,
<br />THEN AFTER 72 HOURS OF WRITTEN NOTICE, THE TENANT MAY AT HIS DISCRETION TAKE
<br />OVER SUCH WORK AND BACK CHARGE THE GENERAL CONTRACTOR FOR ANY CORRECTIVE
<br />WORK THAT WAS REQUIRED DUE TO LACK OF PERFORMANCE, WORKMANSHIP AND/OR
<br />ADHERENCE TO PLANS AND SPECIFICATIONS.
<br />0
<br />� d-
<br />o �
<br />00
<br />mom L)O
<br />4-
<br />0 0
<br />b
<br />U
<br />O 0-
<br />R O
<br />�D __j
<br />�a
<br />QC
<br />UJI
<br />d
<br />Revisions:
<br />Mark Date
<br />A
<br />A
<br />d
<br />�ll� I�1LT?�f���„Vl'�+Ji�