Laserfiche WebLink
Application# <br /> Address : 914 Hoyt Ave <br /> Dwelling Unit Electric Service & Feeder Load Calculator <br /> 220.12 General Lighting Load <br /> 3 va/ft2 of floor area, including unused space adaptable for future use. <br /> Floor Area= 3120ft2 9,360 va <br /> Basement Floor Area= 1250 ft 3,750 va <br /> 220.52(A) Small Appliance Load <br /> 1500 va for each 20 amp branch circuit required per 210.1(C)(1)in EACH kitchen, <br /> pantry, breakfast room,dining room,or similar areas. <br /> #of Small Appliance Branch Circuits= 10 "1500 va= 15,000 va <br /> 220.52(B) Laundry Load <br /> #of Laundry Branch Circuits=0"1500 va= 3,000 va <br /> Total General Lighting&Appliance Load= 31,110 va <br /> 220.42 Lighting Load Feeder Demand Factors <br /> First 3000 or less at i00% 3,000 va <br /> From 3001 to 120,000 at 35% 9,839 va <br /> Remainder over 120,000 at 25% - va <br /> Total Lighting Demand Load= 12,839 va <br /> 220.54 Electric Clothes Dryers <br /> Qty 1 Electric Dryer#1 6.72 kw 6,720 w <br /> Qt 1 Electric Dryer#21 6.72 1 kw 6,720 w <br /> 220.55 Electric Cooking-Ranges, Stove Tops and Wall Ovens <br /> Qty 2 Wall Oven Nameplate 3.65 kw <br /> Qty 0 Electric Range Nameplate - kw <br /> Qty 0 Wall Oven Nameplate - kw <br /> Electric Cooking Demand Load= 4,745 w <br /> 220.51 Fixed Electric Space Heating Loads or Air Conditioning Load: <br /> Fixed Electric Space Heat#1 kw AC#1/Geo - kva <br /> Fixed Electric Space Heat#2 kw AC#2/Geo kva <br /> Fixed Electric Space Heat#3 kw AC#3/Geo - kva <br /> Fixed Electric Space Heat#4 kw AC#4/Geo kva <br /> Fixed Electric Space Heat#5 kw AC#5/Geo - kva <br /> Total Heat&AC Load= - va <br /> 220.14 Appliance load--Dwelling Units <br /> Qty Description va(watts) Qty Description va(watts) <br /> 1 Central Furnace 1,200 0 <br /> 1 Dishwasher 1,200 0 <br /> 1 Refrigerator 1,440 0 <br /> 1 Microwave 1,580 0 <br /> 1 Range Hood 240 0 <br /> 4 Vent Fan 400 0 - <br /> 1Freezer 1,440 0 <br /> Total Connected Appliance Load= 7,500 va <br /> 220.53 Appliance load--Dwelling Units Total Appliance Demand Load= 5,625 va <br /> 220.50 Motor Loads @ 120 Volts <br /> Qty Description va(watts) Qty Description va(watts) <br /> 11 1/2hpGarbage Disposa 375 0 <br /> 2 1/2hpGar/DoorOpener 375 0 <br /> 0 0 <br /> 0 0 <br /> Total Motor Load= 1,125 va <br /> 430.24 Several Motors or a Motor(s)and Other Load(s) 25%of Largest Motor Load= 94 va <br /> Total Motor Demand Load= 1,219 va <br /> TOTAL CALCULATED DEMAND LOAD in Volt-amperes= 37,867 va <br /> TOTAL CALCULATED DEMAND LOAD in AMPS @120/240V 1ph3W= 158 amps <br /> EXISTING SERVICE SIZE 200 AMPS <br /> MINIMUM SERVICE SIZE 200 AMPS /ICE SIZE REQUESTED= 200 amps <br />