NUMBER
<br />FROM
<br />TO
<br />SIZE
<br />POWER
<br />CONTROL
<br />SIGNAL
<br />COMMENTS
<br />C-001
<br />CONTROL PANEL
<br />PUMP 1 STARTER
<br />3/4"
<br />4414, 1#14G
<br />C-002
<br />CONTROL PANEL
<br />PUMP 2 STARTER
<br />3/4"
<br />4414, 1#14G
<br />C-003
<br />CONTROL PANEL
<br />STILLING BASIN SAMPLER 2
<br />1"
<br />2414, 1#14G
<br />C-004
<br />CONTROL PANEL
<br />(F) SDMH 1-4 SAMPLER
<br />1"
<br />VIA J -P3, JB-P4
<br />C-005
<br />CONTROL PANEL
<br />SDMH 1-3 SAMPLER
<br />1"
<br />2414, 1#14G
<br />VIA JB-P3, JB-P4
<br />C-006
<br />CONTROL PANEL
<br />(F) FSMH 2-2 SAMPLER
<br />1"
<br />2414, 1#14G
<br />VIA J -P3, JD=P4
<br />C-007
<br />CONTROL PANEL
<br />(E) STILLING BASIN SAMPLER
<br />1"
<br />2414, 1#14G
<br />P-001
<br />EXISTING PANEL XS4VO2-2-(40-09)
<br />XS4VO2-2-1 (40-03)
<br />2"
<br />342, 146G
<br />VIA J -P1, JB-P2, JB-P3
<br />P-002
<br />STUB UP NEAR XS4VO2-2-(40-09)
<br />JB-P3
<br />2"
<br />SPARE
<br />VIA JB-P1, JD-P2
<br />P-003
<br />STUB UP NEAR XS4VO2-2-(40-09)
<br />JB-P3
<br />2"
<br />SPARE
<br />VIA JB-P1, J -P2
<br />P-004
<br />XS4VO2-2-1 (40-03)
<br />XFMR
<br />1"
<br />343, 1-#1OG
<br />P-005
<br />XS2VO2-2-1 (40-03)
<br />CONTROL PANEL
<br />111
<br />2412, 1-#12G
<br />P=006
<br />XS2VO2-2-1 (40-03)
<br />FSMH 2-2 SAMPLER
<br />1"
<br />2410, 1-#10G
<br />VIA J -P3
<br />P-007
<br />XS VO2-2-1 (40-03)
<br />UPSTREAM VALVE DISC SW
<br />1"
<br />3412, 1- 12G
<br />P-003
<br />UPSTREAM VALVE DISC SW
<br />UPSTREAM VALVE
<br />1"
<br />3412, 1-#12G
<br />P-009
<br />XFMR
<br />XS2VO2.2-1 (40-03)
<br />211
<br />446, 1-#3G
<br />P-010
<br />XS4VO2-2-1 (40-06)
<br />SITE LIGHTING
<br />1"
<br />2412, 1- 12G
<br />VIA J -P3
<br />P-011
<br />XS2VO2-2-1 (0-03)
<br />RECEPTACLES
<br />1"
<br />2412, 1-#12G
<br />VIA J - 3
<br />P-012
<br />XS2VO2-2-1 (0-03)
<br />FIT F-1
<br />1"
<br />2412, 1-#12G
<br />VIA -P3
<br />P-013
<br />XS2VO2-2-1 (40-03)
<br />(F) SDMH 1-4 SAMPLER
<br />1""
<br />VIA JB-P3, JB-P4
<br />P-014
<br />XS2VO2-2-1 (40-06)
<br />SDMH 1-3 SAMPLER
<br />1"'
<br />2410, 1410G
<br />VIA JB-P3, J -P4
<br />P-015
<br />XS2VO2-2-1 (40-03)
<br />STILLING BASIN SAMPLER 2
<br />1"
<br />2410, 1-#10G
<br />VIA J -P3
<br />P-016
<br />XS2VO2-2-1 (40-06)
<br />FIT F-2
<br />1"
<br />2412, 1-412G
<br />VIA JB-P3
<br />P-017
<br />XS4VO2-2.1 (40-06)
<br />EX-DBRISER-GATE DISC SW
<br />1°'
<br />3412, 1-#12G
<br />VIA J -P3
<br />P-013
<br />EX-D RISER -GATE DISC SW
<br />EX-D RISER -GATE
<br />1"
<br />3412, 1412G
<br />P-019
<br />XS4VO2-2-1 (40-03)
<br />PUMP 1 STARTER
<br />3/4"
<br />3412, 1412G
<br />P-020
<br />XS4VO2-2-1 (40-06)
<br />PUMP 2 STARTER
<br />3/4"
<br />3412, 1-#12G
<br />P-021
<br />PUMP 1 STARTER
<br />PUMP 1
<br />3/4"
<br />3412, 1-#12G
<br />P-022
<br />PUMP 2 STARTER
<br />PUMP 2
<br />3/4"
<br />3412, 1-#12G
<br />P-023
<br />JB-P3
<br />JD-P4
<br />1"
<br />SPARE
<br />P-024
<br />JB=P3
<br />JB=P4
<br />1"
<br />SPARE
<br />P-025
<br />XS2VO2-2-1 (40-03)
<br />JB-P3
<br />1"
<br />SPARE
<br />P-026
<br />XS2VO2-2-1 (40-06)
<br />J -P3
<br />1"
<br />SPARE
<br />P-027
<br />XS4VO2-2-1 (40-06)
<br />HEATER DISCONNECT SWITCH
<br />3/4"
<br />3412, 1-#12G
<br />P-023
<br />HEATER DISCONNECT SWITCH
<br />HEATER
<br />3/4"
<br />3412, 1-#12
<br />P-029
<br />XS2VO2-2-1 (40-06)
<br />EXHAUST FAN DISCONNECT SWITCH
<br />3/4"
<br />2412, 1412G
<br />P-030
<br />EXHAUST FAN DISCONNECT SWITCH
<br />EXHAUST FAN
<br />3/4"
<br />2412, 1412G
<br />P-031
<br />XS2VO2-2-1 (40-06)
<br />40-03 BUILDING LIGHTING
<br />3/4"
<br />2412, 1-#12
<br />P-032
<br />XS2V02-2A (40-03)
<br />40-03 BUILDING RECEPTACLES
<br />3/4'
<br />2412, 1412G
<br />S-001
<br />(E) HONEYWELL PANEL
<br />CONTROL PANEL
<br />1"
<br />1/C#16(SH), NETWORK CABLE
<br />VIA JB-S1, JD=S2, JB=S 9 COORDINATE WITH HONEYWELL FOR NETWORK CABLE TYPE
<br />S-002
<br />STUB UP NEAR (E) HONEYWELL PANEL
<br />JB-S3
<br />1"
<br />2/C#16(SH)
<br />S-003
<br />STUB UP NEAR (E) HONEYWELL PANEL
<br />JB=S3
<br />1"
<br />2/C#1 (SH)
<br />S-004
<br />EX-D RISER=GATE
<br />CONTROL PANEL
<br />1"
<br />2-2/C 16(SH)
<br />S-005
<br />UPSTREAM VALVE
<br />CONTROL PANEL
<br />1"
<br />2-2/C#16(SH)
<br />S-006
<br />FIT F-1
<br />CONTROL PANEL
<br />1"
<br />2/C#16(SH)
<br />VIA J -S3
<br />S-007
<br />(F) SDMH 1-4 SAMPLER
<br />CONTROL PANEL
<br />1"
<br />VIA J -S3, J -S4
<br />S-003
<br />SDMH 1-3 SAMPLER
<br />CONTROL PANEL
<br />1"
<br />2/C#16(SH)
<br />VIA J -S3, JB-S4
<br />S-009
<br />LT L-3
<br />CONTROL PANEL
<br />1"
<br />2/C16(SH)
<br />VIA J-S3, JB-S4
<br />S-010
<br />STILLING BASIN SAMPLER 2
<br />CONTROL PANEL
<br />1"
<br />2/C#16(SH)
<br />S-011
<br />LT L-2
<br />CONTROL PANEL
<br />1"
<br />2/C16(SH)
<br />VIA JB-S3, JD=S4
<br />S-012
<br />FIT F-2
<br />CONTROL PANEL
<br />1"
<br />2/C#1(SH)
<br />S-013
<br />LT L-1
<br />CONTROL PANEL
<br />1"
<br />2/C#16(SH)
<br />S-014
<br />(E) SAMPLER
<br />CONTROL PANEL
<br />1"
<br />2/C 16(SH)
<br />S-015
<br />(E) GV-1
<br />CONTROL PANEL
<br />1"
<br />2-2/C#16(SH)
<br />S-016
<br />CONTROL PANEL
<br />(F) FSMH 2-2 SAMPLER
<br />1°°
<br />2/C#16(SH)
<br />VIA J - 3
<br />S-017
<br />(E) LT-4
<br />CONTROL PANEL
<br />11°
<br />2/C16(SH)
<br />S-013
<br />LT-5
<br />CONTROL PANEL
<br />1"
<br />2/C 16(SH)
<br />VIA J -S3, JP-S4
<br />S-019
<br />LT-6
<br />CONTROL PANEL
<br />1"
<br />2/C#16(SH)
<br />VIA J -S3, J -S4
<br />S-020
<br />CONTROL PANEL
<br />J-S3
<br />1"
<br />SPARE
<br />S-021
<br />CONTROL PANEL
<br />JB-S3
<br />1"
<br />SPARE
<br />S-022
<br />JB=S3
<br />JB=S4
<br />1"
<br />SPARE
<br />S-023
<br />JB=S3
<br />J -S4
<br />1 °°
<br />SPARE
<br />S-024
<br />CONTROL PANEL
<br />(E) LT
<br />sym
<br />I REVISION
<br />ICY
<br />APPROVED
<br />DATE
<br />sYm
<br />®®
<br />DOEING EVERT SITE STORMWATER UPGRADE
<br />25065486
<br />KJ
<br />ZOD
<br />0105e21
<br />REMSION
<br />13Y
<br />APPRMD
<br />DATE
<br />ACCEPTABILITY
<br />Meiia
<br />03.05.21
<br />�� ffnnE
<br />THIS DESIGNAND/OR
<br />SPECIFICATION IS APPROVED
<br />CHECKED
<br />J. Mohr
<br />03.05.21
<br />PROVED BY
<br />DEPT.
<br />DATE
<br />UNCREER-
<br />Z. Devlin
<br />03.05.41
<br />ME
<br />ZAPPROVED-
<br />HECK D
<br />. 21
<br />ELECTRICAL