GENERAL STRUCTURAL NOTES <br />CODES AND REFERENCES: <br />ADHESIVE DOWELS: <br />SHOP DRAWING1. <br />2016 EDITION OF THE INTERNATIONAL BUILDING CODE (IBC), WITH STATE OF WASHINGTON AND CITY OF <br />ALL ADHESIVE DOWELS SHALL HAVE CURRENT ICC APPROVAL FOR MATERIAL INTO WHICH INSTALLATION <br />SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL ITEMS. <br />EVERETT AMENDMENTS AND SUPPLEMENTED WITH ASCE 7-10. <br />TAKES PLACE, SUCH AS HILTI HY200-R (ICC ESR-3167) OR APPROVED EQUIVALENT. <br />THE CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL. ITEMS NOT IN <br />ALL CODE REFERENCES HEREAFTER SHALL CORRESPOND TO THE FOLLOWING EDITIONS, U.N.O.: <br />PRECAST CONCRETE: <br />ACCORDANCE WITH CONTRACT DOCUMENTS SHALL BE FLAGGED UPON CONTRACTOR'S REVIEW. <br />MATERIAL CODE EDITION <br />REINFORCING SHOWN IN DETAIL IS FOR IN -PLACE CONDITION. CONTRACTOR SHALL BE RESPONSIBLE <br />VERIFY ALL DIMENSIONS WITH OWNER. <br />FOR PICK UP POINT INSERTS AND LOCATIONS, SPECIAL PICK UP REINFORCING AND STRONG BACKS, <br />CONCRETE BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE <br />AND ALL PICK UP AND PLACING OPERATIONS. <br />MANUFACTURER OR FABRICATOR SHALL CLOUD ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS FROM <br />AND COMMENTARY, ACI 318-14. <br />DRYPACK: <br />CONTRACT DOCUMENTS. ANY OF THE AFOREMENTIONED WHICH ARE NOT CLOUDED OR FLAGGED BY <br />CONCRETE (PRECAST) 7TH EDITION OF PCI DESIGN HANDBOOK: PRECAST AND <br />SUBMITTING PARTIES, SHALL NOT BE CONSIDERED APPROVED AFTER ENGINEER'S REVIEW, U.N.O. <br />PRESTRESSED CONCRETE. <br />CONCRETE REINFORCING CRSI REINFORCING BAR DETAILING, 2015. <br />DRYPACK SHALL BE 5,000 PSI NON -SHRINK GROUT, FIVE STAR OR EQUIVALENT. INSTALL DRYPACK <br />THE ENGINEER HAS THE RIGHT TO APPROVE OR DISAPPROVE ANY CHANGES TO CONTRACT DOCUMENTS <br />STRUCTURAL STEEL 14TH EDITION OF STEEL CONSTRUCTION MANUAL (RISC <br />UNDER BEARING PLATES BEFORE FRAMING MEMBER 1S INSTALLED. <br />AT ANY TIME BEFORE OR AFTER SHOP DRAWING REVIEW. <br />SCM) INCLUDING THE SPECIFICATION FOR STRUCTURAL <br />CHEMICAL- RESISTANT COATING: <br />STEEL BUILDINGS AISC 360-10. <br />THE SHOP DRAWINGS DO NOT REPLACE THE CONTRACT DOCUMENTS. ITEMS OMITTED OR SHOWN <br />STRUCTURAL STEEL WELDING STRUCTURAL WELDING CODE -STEEL, AWS D1.1-15. <br />SPI POLYSHIELD HT 10OF OR OWNER APPROVED ALTERNATE SHALL BE USED AT TRENCH SURFACES. <br />INCORRECTLY AND ARE NOT FLAGGED BY THE STRUCTURAL ENGINEER SHALL NOT BE CONSIDERED <br />STAINLESS STRUCTURAL STEEL WELDING STRUCTURAL WELDING CODE -STEEL, AWS D1.6-17. <br />PREPARE EXISTING AND NEW CONCRETE AND STEEL SURFACES ACCORDING TO MANUFACTURERS <br />CHANGES TO CONTRACT DOCUMENTS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE ITEMS ARE <br />RECOMMENDATIONS. APPLY PRIMER AND COATINGS PER MANUFACTURER'S RECOMMENDATIONS. <br />. <br />CONSTRUCTED TO CONTRACT DOCUMENTS. <br />L a <br />HYDROPHILIC WATERSTOPS: <br />THE ADEQUACY OF ENGINEERING DESIGNS AND LAYOUT PERFORMED BY OTHERS RESTS WITH THE <br />RISK CATEGORY = 11. <br />DESIGNING OR SUBMITTING AUTHORITY. <br />HYDROPHILIC WATERSTOPS SHALL BE INSTALLED AT ALL BELOW -GRADE CONCRETE TRENCH JOINTS OR <br />REVIEWING IS INTENDED ONLY AS AN AID TO THE CONTRACTOR IN OBTAINING CORRECT SHOP DRAWINGS. <br />PAD SLAB: <br />INTERFACES. HYDROPHILIC WATERSTOPS SHALL BE 3/4" x 1" SIKA SWELLSTOP OR APPROVED <br />CONTRACTOR HAS THE RESPONSIBILITY OF THE CORRECTNESS OF ALL APPROVAL DRAWINGS. <br />EQUIVALENT. INSTALL HYDROPHILIC WATERSTOPS PER MANUFACTURER'S RECOMMENDATIONS. <br />200 PSF. <br />GENERAL <br />JOINT SEALANTS: <br />SEISMIC: <br />JOINT SEALANTS SHALL BE SIKAFLEX ®1C SL OR APPROVED EQUIVALENT POLYURETHANE JOINT <br />THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT <br />IMPORTANCE FACTOR le = 1.0. <br />SEALANT. FOAM BACKING RODS SHALL COMPLY WITH WSDOT SPECIFICATION 9-06.3. INSTALL JOINT <br />INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES <br />LATITUDE = 47.9237; LONGITUDE-122.2765. <br />SEALANT PER MANUFACTURER'S RECOMMENDATIONS. <br />NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, <br />Ss o 1.446, S1 0 0.559, SEISMIC SITE CLASS a C. <br />BUT ARE NOT LIMITED TO BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. <br />Sds o 0.964, Sd1 = 0.464, SEISMIC DESIGN CATEGORY o D. <br />STRUCTURAL STEEL: <br />THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, <br />ANALYSIS PROCEDURE USED = EQUIVALENT LATERAL FORCE PROCEDURE. <br />TECHNIQUES, SEQUENCES OR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE <br />PROGRAMS INCIDENT THERETO NOR SHALL OBSERVATION VISITS TO THE SITE INCLUDE INSPECTION OF <br />FOUNDATIONS - <br />a <br />ALL CONSTRUCTION SHALL BE PER AISC®SCM. <br />THESE ITEMS. <br />REFERENCE GEOTECHNICAL REPORT SUPPLIED BY TERRACON; JOB NO. 81115065; DATED JANUARY 17, <br />ALL STRUCTURAL STEEL SHALL BE AS FOLLOWS: <br />CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOAD SHALL <br />2012. SPREAD FOOTINGS AND MAT FOUNDATIONS SHALL BEAR ON A MINIMUM OF 6' OF ENGINEERED <br />WIDE FLANGE STEEL A.S.T.. A992, GRADE 50 FY = 50 KSI <br />NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. <br />FILL 16" MINIMUM BELOW FINISHED GRADE. ENGINEERED FILL SHALL MEET THE REQUIREMENTS OF <br />ALL OTHER STRUCTURAL STEEL SHAPES A.S.T.. A36 FY = 36 KSI <br />WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS OR MATERIALS, SUCH STANDARDS SHALL BE <br />FOUNDATION MATERIAL CLASS A, AS DEFINED IN SECTION 9m03.17 OF THE WSDOT STANDARD <br />THE LATEST EDITION AND/OR ADDENDA, U.N.O. <br />SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPAL CONSTRUCTION. DESIGN SOIL BEARING VALUE o <br />HIGH - STRENGTH BOLTS: <br />4,000 PSF; MODULUS OF SUBGRADE REACTION = 300 PSI. TRENCH WALL BACKFILL MATERIAL SHALL <br />ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING AND <br />MEET THE REQUIREMENTS OF GRAVEL BORROW, AS DEFINED IN SECTION 9-03.14(1) OF THE WSDOT <br />ALL HIGH -STRENGTH BOLTS SHALL CONFORM TO ASTM A325 AND SHALL BE INSTALLED AS <br />ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO CONSTRUCTION. <br />STANDARD SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPAL CONSTRUCTION. REFER TO <br />BEARING -TYPE CONNECTIONS WITH THREADS INCLUDED IN SHEAR PLANE (I.E. A TYPE "N" CONNECTION). <br />GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION PRIOR TO COMMENCEMENT OF EARTHWORK. <br />HIGH -STRENGTH BOLTS SHALL BE SNUG -TIGHT, TYPICAL, U.N.O. AN INDEPENDENT TESTING LABORATORY <br />OPTIONS ARE FOR CONTRACTOR'S CONVENIENCE. IF AN OPTION IS CHOSEN, CONTRACTOR SHALL BE <br />CONCRETE <br />SHALL INSPECT ALL HIGH -STRENGTH BOLTING. <br />RESPONSIBLE FOR ALL NECESSARY CHANGES AND SHALL COORDINATE ALL DETAILS. <br />WELDING: <br />NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES AND <br />MINIMUM 26-DAY STRENGTH OF CONCRETE SHALL BE 4500 PSI: <br />TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK <br />WELDERS HOLDING VALID W.A.B.O. CERTIFICATES AND HAVING CURRENT EXPERIENCE IN THE TYPE OF <br />ON THE PROJECT. <br />. . . <br />ALL CONCRETE CONSTRUCTION SHALL CONFORM TO ACI. MECHANICALLY VIBRATE ALL CONCRETE WHEN <br />WELD SHOWN ON THE DRAWINGS OR NOTES SHALL PERFORM ALL WELDING. CERTIFICATES SHALL BE <br />PLACED, EXCEPT THAT SLABS ON GRADE NEED BE VIBRATED ONLY AT TRENCHES, FLOOR DUCTS, <br />THOSE ISSUED BY AN ACCEPTED TESTING AGENCY. <br />CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS PRIOR TO START OF <br />TURNDOWNS, ETC. MAXIMUM SLUMP IS 4 1/2" FOR CONCRETE WITHOUT PLASTICIZER. IF PLASTICIZER IS <br />CONSTRUCTION. RESOLVE ANY DISCREPANCY WITH THE OWNER. <br />USED, A HIGHER FINAL SLUMP MAY BE ALLOWED UPON STRUCTURAL ENGINEER'S APPROVAL. MAXIMUM <br />ALL WELDING DONE BY E70 SERIES LOW HYDROGEN RODS, U.N.O. ALL WELDING SHALL BE PER LATEST <br />WATER/CEMENT RATIO (W/C) SHALL BE 0.45 FOR GENERAL CONCRETE. USE 1 1/2" MINUS COARSE <br />AWS STANDARDS. <br />TYPICAL DETAILS MAY NOT NECESSARILY BE CUT ON PLANS, BUT APPLY, U.N.O. <br />AGGREGATE FOR CONCRETE 6' THICK AND GREATER; USE 3/4" MINUS COARSE AGGREGATE FOR <br />THESE DRAWINGS DO NOT DISTINGUISH BETWEEN SHOP AND FIELD WELDS; THE CONTRACTOR MAY SHOP <br />WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL NOTES AND/OR <br />THINNER SECTIONS. PROVIDE AIR ENTRAINMENT (5% ± 1%) IN CONCRETE EXPOSED TO FREEZE -THAW <br />WELD OR FIELD WELD AT THEIR DISCRETION. SHOP WELDS AND FIELD WELDS SHALL BE SHOWN ON <br />SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN. <br />ACTION. <br />THE SHOP DRAWINGS SUBMITTED FOR REVIEW. ALL FULL/COMPLETE PENETRATION WELDS SHALL BE <br />FLY F�. <br />TESTED AND CERTIFIED BY AN INDEPENDENT TESTING LABORATORY. <br />ANY ENGINEERING DESIGN, PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL <br />OF A REGISTERED ENGINEER RECOGNIZED BY THE BUILDING CODE JURISDICTION OF THIS PROJECT. <br />HEADED STUDS: <br />FLY ASH, IF PERMITTED BY ENGINEER, SHALL BE LIMITED TO 16% OF CEENTITIOUS MATERIALS AND <br />SHALL HAVE A REPLACEMENT FACTOR OF 1.2 RELATIVE TO CEMENT REPLACED. NO FLY ASH ADDITIVES <br />ALL REFERENCE TO HEADED STUDS .SHALL BE AUTOMATIC MELDED HIGH -STRENGTH HEADED STUDS. <br />SPECIAL L INSPECTION - <br />SHALL BE USED IN FLATWORK OR ARCHITECTURALLY EXPOSED CONCRETE. <br />ATTACHMENT SHALL CONFORM TO ALL REQUIREMENTS OF AWS. CONFORMANCE SHALL INCLUDE, BUT NOT <br />BE LIMITED TO, ALL QUALITY CONTROL TESTING PROVISIONS OF THE AFOREMENTIONED PUBLICATIONS. <br />SPECIAL INSPECTION IS TO BE PROVIDED FOR THE ITEMS LISTED BELOW IN ADDITION TO THE <br />REINFORCING STEEL FOR CONCRETE: <br />INSPECTIONS CONDUCTED BY THE BUILDING SAFER' DEPARTMENT. "SPECIAL STRUCTURAL INSPECTION" <br />STEEL EMBEDS AT INTERIOR OF TRENCHES: <br />SHALL NOT RELIEVE THE OWNER OR THEIR AGENT FROM REQUESTING THE CITY INSPECTIONS REQUIRED <br />USE ASTM A615, GRADE 60 (FY = 60 KSI), DEFORMED BARS FOR ALL BARS. NO TACK WELDING OF <br />BY IBC SECTION 110.3. SPECIAL INSPECTION IS REQUIRED PER SECTIONS 1704 AND 1705 FOR THE <br />REINFORCING BARS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE WITH THE STRUCTURAL ENGINEER. <br />ALL STEEL EMBED PLATES AT INTERIOR OF TRENCHES SHALL BE STAINLESS STEEL (SS) ASTM A240 <br />FOLLOWING: <br />ACI 318 SHALL APPLY. SUPPORT OF FOUNDATION REINFORCING MUST PROVIDE ISOLATION FROM <br />TYPE 304L, UNLESS NOTED OTHERWISE. <br />MOISTURE AND CORROSION. <br />1. CONCRETE (PER IBC TABLE 1705.3): <br />PROTECTIVE COATINGS FOR MILD STEEL TRENCH EMBEDS: <br />A) DURING THE TAKING OF TEST SPECIMENS. <br />REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS. ALL OARS SHALL BE PER ACI SP®66. <br />B) DURING THE PLACEMENT OF ALL REINFORCED CONCRETE, U.N.O. <br />DOWEL ALL VERTICAL REINFORCING TO FOUNDATION WITH STANDARD 90-DEGREE HOOKS, U.N.O. <br />ALL MILD STEEL EMBEDS AT TRENCH LIDS AND WALLS SHALL RECEIVE POLYESTER POWDER COATING <br />C VERIFICATION OF CURING TEMPERATURE AND TECHNIQUE (PERIODIC). <br />SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING CONCRETE. <br />WITH A MINIMUM THICKNESS OF 3 MILS. USE SHERWIN WILLIAMS POWDU SUPER DURABLE TGIC <br />D) NO INSPECTION IS REQUIRED FOR SLABS ON GRADE. <br />POWDER COATING OR APPROVED EQUIVALENT. APPLY PRIMER AND COATING PER MANUFACTURER'S <br />LAP SPLICES IN CONCRETE: <br />RECOMMENDATIONS. COORDINATE COLOR WITH OWNER. <br />2. PRECAST CONCRETE (IN ADDITION TO ABOVE, PER IBC TABLE 1705.3): <br />LAP SPLICES, U.N.O., SHALL BE CLASS "B" TENSION LAP SPLICES PER ACI 315. STAGGER SPLICES A <br />FIELD REPAIR: FIELD REPAIR OF DAMAGED POLYESTER POWDER COATING SHALL BE DONE IN <br />A) DURING ERECTION OF PRECAST MEMBERS (PERIODIC). <br />MINIMUM OF (1) LAP LENGTH. <br />ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. <br />3. BOLTS IN CONCRETE (PER IBC TABLE 1705.3): <br />ALL SPLICE LOCATIONS SUBJECT TO APPROVAL BY THE STRUCTURAL ENGINEER. PROVIDE BENT <br />HANDLING: AFTER SHOP FABRICATION AND COATING, STRUCTURAL STEEL MEMBERS SHALL BE HANDLED <br />A) DURING THE PLACING OF CONCRETE AROUND BOLTS. <br />CORNER BARS TO MATCH AND LAP WITH HORIZONTAL BARS AT ALL CORNERS AND INTERSECTIONS PER <br />WITH SUFFICIENT CARE TO MINIMIZE DAMAGE DURING SHIPMENT. SUFFICIENT DUNNAGE SHALL BE USED <br />TYPICAL DETAILS. <br />TO PREVENT ANY RUBBING OF STEEL TO STEEL. <br />4. REINFORCING STEEL (PERIODIC) (PER IBC TABLE 1705.3): <br />A) DURING THE PLACING OF REINFORCING STEEL FOR ALL CONCRETE REQUIRED TO HAVE <br />REINFORCING STEEL COVER: <br />PROTECTIVE COATINGS FOR STEEL: <br />SPECIAL INSPECTION NOTED ABOVE. <br />ALL REINFORCING SHALL BE CHAIRED TO ENSURE PROPER CLEARANCES. CLEAR CONCRETE COVERAGES <br />ALL STRUCTURAL AND MISCELLANEOUS MILD STEEL AND FASTENERS SHALL RECEIVE POLYAMIDE EPDXY <br />5. POST -INSTALLED ANCHORS (PER IBC TABLE 1705.3): <br />AS FOLLOWS: <br />COATING WITH ALIPHATIC ACRYLIC POLYURETHANE TOPCOAT UNLESS NOTED OTHERWISE. USE TNEMEC <br />A) CONTINUOUS INSPECTION DURING THE PLACEMENT OF ALL ADHESIVE ANCHORS INSTALLED <br />SERIES 66 HI -BUILD EPDXOLINE WITH TNEMEC ENDURA®SHIELD SERIES 73 TOPCOAT OR APPROVED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS. <br />CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH . • • • • . • • • • • . • . • • • 3" EQUAL. EPDXY -POLYURETHANE COATING SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. B) PERIODIC INSPECTION OF ALL OTHER ADHESIVE AND MECHANICAL ANCHORS. <br />EXPOSED TO EARTH OR WEATHER COORDINATE COLOR WITH OWNER. <br />6 OR LARGER . . ...... .... . ....... . 2" <br />5 OR LARGER • • . . . . . . • 1 1 /2" FIELD REPAIR: FIELD REPAIR OF DAMAGED EPDXY -POLYURETHANE COATING SHALL BE DONE IN 6. WELDING (PER AISC TIO CHAPTER N): <br />. . � . . � 1 . � � � . � � � . . 1 . ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. A) VISUAL INSPECTION OF ALL FIELD WELDS. <br />SLABS NOT EXPOSED TO EARTH OR WEATHER . . . . . . . . . . . . . . . . . . . 3/4" B) NON-DESTRUCTIVE TESTING OF ALL COMPLETE PENETRATION WELDS. <br />ALL OTHER PER ACI 316, <br />HANDLING: AFTER SHOP FABRICATION AND COATING, STRUCTURAL STEEL MEMBERS SHALL BE HANDLED <br />WITH SUFFICIENT CARE TO MINIMIZE DAMAGE DURING SHIPMENT. SUFFICIENT DUNNAGE SHALL BE USED 7. BOLTING (PER AISC 360 CHAPTER N): <br />TO PREVENT ANY RUBBING OF STEEL TO STEEL. B, DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR: <br />A) THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO BE CERTAIN IT <br />CONFORMS TO THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS. <br />B) PER IBC SECTION 1704.2.4: THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS <br />TO THE BUILDING OFFICIAL AND TO THE ENGINEER OF RECORD. ALL DISCREPANCIES SHALL <br />BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN, IF <br />UNCORRECTED TO THE DESIGN AUTHORITY AND THE BUILDING OFFICIAL. SUBMIT A FINAL <br />REPORT AS REQUIRED. <br />C) UPON COMPLETION OF THE ASSIGNED WORK, THE ENGINEER SHALL COMPLETE AND SIGN <br />THE APPROPRIATE FORMS CERTIFYING THAT, TO THE BEST OF THEIR KNOWLEDGE, THE <br />WORK IS IN CONFORMANCE WITH THE APPROVED PLANS, SPECIFIC <br />FOR ADDITIONAL INFORMATION ON SPECIAL STRUCTURAL INSPECTIONS, SEE THE SPECIAL INSPECTION <br />TABLES ON S2F-5 AND S2F®6 AND CONTACT STRUCTURAL ENGINEER PRIOR TO START OF <br />CONSTRUCTION. <br />fflwl�� Motalt <br />A.U.C. <br />AGGREGATE BASE COURSE <br />H/C <br />HOLLOW CORE <br />A.F.F. <br />ABOVE FINISHED FLOOR <br />HORIZ. <br />HORIZONTAL <br />ALT. <br />ALTERNATE <br />I.F.W. <br />INSIDE FACE OF WALL <br />A.B. <br />ANCHOR BOLT <br />I.E. <br />INVERT ELEVATION <br />BM <br />BEAM <br />K (KIP) <br />1,000 POUNDS <br />B.F.F. <br />BELOW FINISHED FLOOR <br />L.L. <br />LIVE LOADS <br />B.O.B. <br />BOTTOM OF BEAM <br />LBS () <br />POUNDS <br />B.O.D. <br />BOTTOM OF DECK <br />L.L.H. <br />LONG LEG HORIZONTAL <br />B.O.F. <br />BOTTOM OF FOOTING <br />L.L.V. <br />LONG LEG VERTICAL <br />B.O.P. <br />BOTTOM OF PLATE <br />MFR('S) <br />MANUFACTURER('S) <br />B.O.S. <br />BOTTOM OF STEEL <br />MAS. C.J. <br />MASONRY CONTROL JOINT <br />BRG <br />BEARING <br />MECH'L <br />MECHANICAL <br />C.I.P. <br />CAST -IN -PLACE <br />N/A <br />NOT APPLICABLE <br />C.L. <br />CENTERLINE <br />N.T.S. <br />NOT TO SCALE <br />C.L.B. <br />CENTERLINE OF BEAM <br />O.C. <br />ON CENTERS <br />C.L.C. <br />CENTERLINE OF COLUMN <br />O.F.W. <br />OUTSIDE FACE OF WALL <br />C.L.F. <br />CENTERLINE OF FOOTING <br />OPP. <br />OPPOSITE <br />C.L.W. <br />CENTERLINE OF WALL <br />P.C. <br />PRE -CAST CONCRETE <br />CLR <br />CLEAR <br />P.L.F. <br />POUNDS PER LINEAR FOOT <br />CONC. <br />CONCRETE <br />PREFAB <br />PRE -FABRICATED <br />CONC. C.J. <br />CONCRETE CONTROL JOINT <br />P.S.F. <br />POUNDS PER SQUARE FOOT <br />CONC. S.J. <br />CONCRETE SAWCUT JOINT <br />P.S.I. <br />POUNDS PER SQUARE INCH <br />C.M.U. <br />CONCRETE MASONRY UNIT <br />REINF. <br />REINFORCING <br />CONN. <br />CONNECTION <br />S.L.H. <br />SHORT LEG HORIZONTAL <br />CONT. <br />CONTINUOUS <br />S.L.V. <br />SHORT LEG VERTICAL <br />D.L. <br />DEAD LOAD <br />SIM. <br />SIMILAR <br />DIA; <br />DIAMETER <br />SQ. <br />SQUARE <br />DN <br />DOWN <br />STD <br />STANDARD <br />DWG(S) <br />DRAWING(S) <br />T.L, <br />TOTAL LOAD <br />E.O.S. <br />EDGE OF SLAB <br />T.O.B. <br />TOP OF BEAM <br />EL. <br />ELEVATION <br />T.O.D. <br />TOP OF DECK <br />EQ. <br />EQUAL <br />T.O.F. <br />TOP OF FOOTING <br />EQUIP. <br />EQUIPMENT <br />T.O.G. <br />TOP OF GRATING <br />EXP. <br />EXPANSION BOLT <br />T.O.L. <br />TOP OF LEDGER <br />EXP. JT. (E.J.) <br />EXPANSION JOINT <br />T.O.M. <br />TOP OF MASONRY <br />E.W. <br />EACH WAY <br />T.O.P. <br />TOP OF PLATE <br />F.F. <br />FINISHED FLOOR <br />T.O.S. <br />TOP OF STEEL <br />F.O.M. <br />FACE OF MEMBER <br />T.O.W. <br />TOP OF WALL <br />F.O.S. <br />FACE OF STEEL <br />TYP. <br />TYPICAL <br />F.O.W. <br />FACE OF WALL <br />U.N.O. <br />UNLESS NOTED OTHERWISE <br />GA. <br />GAUGE <br />VERT. <br />VERTICAL <br />GALV. <br />GALVANIZED <br />WSTP <br />WATERSTOP <br />GSN <br />GENERAL STRUCTURAL NOTES <br />W.W.R. <br />WELDED WIRE REINFORCEMENT <br />9 <br />rki <br />In <br />rol <br />MEMBERS.1 PROVIDE A COLD FORMED STEEL DECK FABRICATION FROM STEEL <br />CONFORMING TO ASTM A1008 SS OR ASTM A653, STRUCTURAL <br />QUALITY, AND SECTION A3 OF THE LATEST EDITION OF THE AISI <br />SPECIFICATION FOR THE DESIGN OF COLD —FORMED STEEL <br />STRUCTURAL - MINIMUM YIELD <br />Or 50 <br />2. STEEL DECK PROPERTIES FINISHES: <br />Rai'- DECK TYPEBASED ON VERCO MANUFACTURING. <br />FOR ENGINEER'S REVIEW. SEE SPECIFICATION. <br />-ORM DECK UNITS TO SPAN 3 OR MORE SUPPORTS WITH DECK <br />BEARING 3—INCHES ON SUPPORTING MEMBERS OR INTERIOR <br />EQUIVALENT PRODUCTS BY VULCRAFT, OR EQUAL, MAY BE SUBMITTED <br />(.`;ONSTRUCTION LIVE LOADS SHALL NOT EXCEED 20 POUNDS PER <br />WUARE FOOT UNIFORM LOAD OR 150 POUND CONCENTRATED LOAD <br />ON 1 WIDE SECTION OF DECK. <br />%iEE ARCHITECTURAL, MECHANICAL, PROCESS AND ELECTRICAL <br />YRAWINGS FOR ADDITIONAL OP'ODECK. <br />c'OR DECK APPLICATIONS <br />-` R OR ROOF DECKS (TYPE B <br />ATTACH <br />-, DECK <br />TO <br />STRUCTURAL SUPPORTS <br />iO_r <br />WELDSFOR WELDS TO STRUCTURAL MEMBERS PROVIDE ARC —SPOT <br />DWELDS OF DIAMETER PER <br />D1.3 SPECIFICATIONS. <br />6) ATTACH ALL DECK UNITS TO STRUCTURAL FRAMING WITH A <br />FASTENER LAYOUT FOR BOTH ENDS AND INTERIOR SUPPORTS <br />SHALL B,_ - FASTENERS <br />PROVIDE 1/2—INCH PUDDLE WELD AT EVERY 12 INCHES <br />WHERE THE DECK FLUTES ARE PARALLEL TO THE SUPPORTS. <br />4DECK SHALL BE FASTENED AT THE - AP BY <br />BUTTON —PUNCHING AT s INCHES ON CENTER MAXIMUM. <br />1. CEMENT SHALL BE ASTM C150 TYPE 11 FOR - <br />LL STRUCTURES. <br />CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE <br />STRENGTH (PSI) AS NOTED IN THE TABLE BELOW AND AS FURTHER <br />DEFINED _ SPECIFICATIONS <br />CONCRETE STRENGTH (PSI) <br />TYPE I STRENGTH I LOCATION <br />C 4,000 BLDG BASIC CONC — FOUNDATIONS AND SLABS <br />UON <br />G 125 CLSM/CDF — SEE SPECIFICATION SECTION 02065 <br />(MAX) <br />ACCEPTABILITY <br />THIS DESIGN AND/OR <br />SPECIFICATION IS APPROVED <br />APPROVED BY <br />