DISTRIBUTION SYSTEM. <br />DISTRIBUTION PANELBOARD 480Y/277V <br />POWER PANEL, 208Y/120V <br />I� <br />SPECIAL PANEL AS NOTED <br />8TW <br />GROUND ROD, "TW" INDICATES TEST WELL <br />(4)#1,G,1 -1 /2"C <br />HOME RUN -PANEL- CIRCUIT (EXAMPLE 2V57) CROSS MARKS <br />2V57- 4BMA10/2,4,6 <br />PNL-CKT <br />INDICATE QUANTITY OF CONDUCTORS (SIZE NOTED) LONGER SLASH <br />INDICATES NEUTRAL WIRE (IF REQUIRED). IF UNMARKED INSTALL 3#12 AWG <br />IN 3/4 " CONDUIT. REVERSED SLASH INDICATES GROUND WIRE. <br />CONDUIT EXPOSED (RIGID METAL) <br />CONDUIT EMBEDDED IN CONCRETE OR BELOW GRADE <br />FLEXIBLE METAL OR LIQUIDTIGHT FLEX METAL CONDUIT AS NOTED <br />CONDUIT TURNING UP <br />CONDUIT TURNING DOWN <br />G <br />GROUND WIRE (SIZE AS NOTED) <br />G <br />GROUND WIRE WITH EXOTHERMIC WELD CONNECTION <br />E <br />EMERGENCY CIRCUIT <br />L <br />EXPOSED LIGHTNING PROTECTION CONDUCTOR <br />® <br />JUNCTION BOX, SPECIAL (SIZE NOTED, "WP"-WEATHERPROOF) <br />® <br />PULL BOX (SIZE NOTED, "WP"-WEATHERPROOF) <br />FTB <br />FIELD TERMINAL BOX <br />F _11-01 I <br />REMOTE 1/0 RACK <br />_PM-1 <br />POWER MONITOR DEVICE <br />❑T <br />TRANSFORMER (CAPACITY, PHASE & VOLTAGE AS NOTED) <br />NON -FUSED DISCONNECT SWITCH (ENCLOSED BREAKER OR MOLDED <br />XX/Y NN <br />CASE SWITCH WHERE FAULT CURRENT EXCEEDS 10KA) <br />FF EXP <br />XX - SWITCH RATING <br />Y - NUMBER OF POLES <br />FF - FUSE RATING <br />NN - ENCLOSURE TYPE <br />EXP - EXPLOSION PROOF (CLASS I / DIV I UNLESS NOTED OTHERWISE) <br />Ep <br />ENCLOSED CIRCUIT BREAKER <br />ZA <br />STARTER <br />(M) <br />MOTOR (SIZE AS NOTED) <br />GENERATOR, ALTERNATING CURRENT (VOLTAGE, KVA, <br />PHASES, FREQUENCY AS NOTED) <br />I <br />RECEPTACLE 20 AMP DUPLEX, 2 POLE, 3 WIRE <br />h9E20 <br />CLASS I, DIVISION I EXPLOSION PROOF GFCI 125V, 20A, 2P, 3W <br />EXP <br />INTERLOCKING RECEPTACLE. CROUSE HINDS CPS152 (RECEPTACLE) <br />AND GFS-1 (GFI MODULE) OR APPROVED ALTERNATE. <br />ABOVE COUNTER RECEPTACLE 20 AMP DUPLEX, 2 POLE, 3 WIRE <br />SIG <br />ISOLATED GROUND RECEPTACLE, 20AMP. DUPLEX. 2 POLE. 3 WIRE <br />If*-GF' GROUND FAULT INTERRUPT RECEPTACLE, 20AMP, DUPLEX, 2 POLE, 3WIRE <br />WP <br />WP INDICATES WEATHERPROOF <br />RECEPTACLE 20AMP 4-PLEX, 2 POLE, 3 WIRE <br />RECEPTACLE, NEMA CONFIGURATION AS INDICATED, <br />L6-2OR <br />RECEPTACLE, 48OV/3PH, 20A SINGLE, 3P, 4W LOCKING TYPE NEMA L6-20 <br />GROUNDING <br />j <br />RECEPTACLE, 208V/1 PH, 30A SINGLE, 2P, 3W LOCKING TYPE NEMA L6-30 <br />GROUNDING <br />® <br />JUNCTION BOX, FIELD SIZED PER NEC, <br />0FSD <br />JUNCTION BOX, 120V CONNECTION FOR FIRE -SMOKE DAMPER <br />0MOD <br />JUNCTION BOX, 120V CONNECTION FOR MOTOR -OPERATED DAMPER <br />(� <br />CONNECTION TO EQUIPMENT AS INDICATED. <br />MECHANICAL EQUIPMENT TAG. <br />$M <br />MOTOR RATED SWITCH <br />POKE THRU DEVICE - REFER TO DETAIL 3 ON SHEET E508-02-46 <br />PT_X <br />PT-1 - 6" POWER/DATA/AV POKE THRU DEVICE <br />PT-2 - 8" POWER/DATA/AV POKE THRU DEVICE <br />SYM <br />REVISION <br />BY <br />APPROVED <br />A <br />777X CWC NEW BUILDING - <br />RECORD WBS 2548317 <br />JMG <br />DFC <br />DATE SYM <br />01/03/17 <br />MillMllml <br />W_21�0' <br />LF LOW VOLTAGE CIRCUIT BREAKER. <br />AMP FRAME/AMP TRIP. <br />25 SYNCHRONISM - RELAY <br />27 <br />UNDER VOLTAGE RELAY <br />50 51 <br />INSTANTANEOUSITIME OVERCURRENT <br />RELAY <br />511 N <br />INSTANTANEOUS/TIME NEUTRAL <br />OVERCUR� NT RELAY <br />Sx'- <br />POWER FACTOR CORRECTION CAPACITORS <br />,— <br />(FUSED) <br />�.+.� <br />�Y> <br />CONTROL POWER TRANSFORMER <br />POTENTIAL TRANSFORMER <br />IT <br />MR <br />CURRENT TRANSFORMER. MR INDICATES <br />MULTI -RATIO <br />pM <br />ALI_EN-BRADLEY POWER MONITOR 5000 <br />ANALOG AMMETER <br />AS <br />AMMETER SWITCH <br />VS <br />VOLTMETER SWITCH <br />ANALOG VOLTMETER <br />SYSTEM GROUND <br />MOTOR STARTER (COMBINATION) <br />® <br />MOTOR STARTER (MANUAL) <br />S� <br />SOLENOID VALVE <br />®® <br />REMOTE CONTROL STATION (TYPE AS NOTED) <br />Fol <br />EMERGENCY POWER SHUTDOWN <br />PTF <br />3-COMPARTMENT POWER POLE WIRE MOLD 30TP-4 <br />2-COMPARTMENT POWER POLE WIRE MOLD 30TP-3 <br />SB <br />SWITCH BYPASS DEVICE <br />CB <br />MANUAL CONTROLLER <br />TB <br />TEST BLOCK <br />LOW VOLTAGE CIRCUIT BREAKER, <br />DRAWOUT TYPE <br />ELECTRICALLY OPERATED <br />UNIT SUBSTATION TRANSFORMER <br />49 <br />OVERLOAD RELAY <br />86 <br />LOCKOUT RELAY <br />G1 G2 <br />KIRK KEY INTERLOCKS. SEE BOEING <br />27 <br />STANDARDS <br />UNDERVOLTAGE RELAY <br />46 <br />REVERSE PHASE CURRENT RELAY <br />47 <br />PHASE SEQUENCE VOLTAGE RELAY <br />25 <br />SYNCHRONIZING DEVICE <br />I <br />I <br />LIGHTNING ARRESTER <br />PRIMARY MEDIUM VOLTAGE FUSED <br />SWITCH <br />MEDIUM VOLTAGE CABLE TERMINATION <br />GF <br />GROUND FAULT MONITOR <br />SIB® <br />SURGE PROTECTIVE DEVICE <br />SG <br />STATIC GROUND RECEPTACLE <br />REVISION <br />BY I APPROVED I DATE <br />LIGHTING FIXTURES: UPPER CASE ALPHA -NUMERIC CHARACTER INDICATES FIXTURE TYPE. <br />LOWER CASE ALPHANUMERIC CHARACTER INDICATES CIRCUIT NUMBER AND PHASE FED FROM. <br />UPPER CASE ALPHANUMERIC CHARACTER IN PARENTHESIS INDICATES RELAY NUMBER. <br />LOWER CASE LETTER INDICATES SWITCH LEG. <br />%L" INDICATES NIGHT LIGHT OPERATION (CIRCUIT NOT SWITCHED). <br />0 <br />STRUCTURE MOUNTED LED HIGH BAY FIXTURE. EACH FIXTURE SHALL INCLUDE <br />A QUICK DISCONNECT AND IN -LINE FUSE. <br />STRUCTURE MOUNTED LED HIGH BAY FIXTURE (EMERGENCY). EACH FIXTURE <br />SHALL INCLUDE A QUICK DISCONNECT AND IN -LINE FUSE. <br />—� <br />INDUSTRIAL FLUORESCENT/LED LIGHTING FIXTURE. <br />INDUSTRIAL FLUORESCENT/LED LIGHTING FIXTURE (EMERGENCY) <br />J <br />WALL/RECESSED/SURFACE MOUNTED FLUORESCENT LIGHTING FIXTURE. <br />WALL/RECESSED/SURFACE MOUNTED FLUORESCENT LIGHTING FIXTURE (EMERGENCY) <br />RECESSED MOUNTED LED LIGHTING FIXTURE <br />RECESSED MOUNTED LED LI,GH I FIXTURE (EMERGENCY) <br />EXTERIOR WALL PACK (EMERGENCY) <br />WALL OR CEILING EXIT SIGN. FIXTURE SHALL BE WIRED AHEAD OF LOCAL SWITCHES. ARROW <br />AS SHOWN DENOTES DIRECTION OF EGRESS, SOLID QUADRANT INDICATES FACE. <br />LIGHTING L";*ONTROLS <br />LIGHTING <br />CONTROL SWITCHES AND OCCUPANCY SENSORS: ADDITIONAL LOWER CASE <br />LETTER INDICATES <br />SWITCH LEG, <br />SINGLE POLE TOGGLE WALL SWITCH <br />3 <br />THREE-WAY TOGGLE WALL SWITCH <br />OS <br />LINE -VOLTAGE OCCUPANCY SENSOR WALL SWITCH <br />WP <br />SINGLE POLE TOGGLE WALL SWITCH, WEATHERPROOF <br />XX L.V <br />LOW -VOLTAGE, 2-BUTTON ON/OFF WALL SWITCH. SWITCH TO TIE <br />INTO GE LIGHTSWEEP LIGHTING CONTROL PANEL(S) SERVING <br />RESPECTIVE AREA. REFER TO GE LIGHTING LIGHTSWEEP CONTROL <br />DRAWINGS FOR MORE INFORMATION <br />WHERE SHOWN)FIRST DIGIT REPRESENTS FLOOR (U - 2ND FLOOR, V - 3RD FLOOR) <br />SECOND DIGIT SPECIFIES LIGHTING CONTROL ZONE, SEE CONTROL ZONE PLANS 2E8 <br />AND 3E8 FOR ADDITIONAL INFORMATION. <br />OC <br />CEILING MOUNTED, LOW -VOLTAGE, DUAL TECHNOLOGY OCCUPANCY SENSOR WITH POWER PACK <br />LCP <br />POWER PACK: HUBBELL #UVPP OR APPROVED EQUAL (FOR EACH OCCUPANCY SENSOR) <br />ROOMS: HUBBELL #OMNI-DT-500/100 OR APPROVED EQUAL (500/1000 SO. FEET) <br />CORRIDORS/TUNNELS: HUBBELL #OMNI-DT-2000 OR APPROVED EQUAL (2,000 SQ. FEET) <br />SUBSCRIPT INDICATES LOW VOLTAGE OCCUPANCY SENSOR WIRED BACK TO GE LIGHTING CONTROL PANEL <br />INDICATED. <br />BUILDING MOUNTED PHOTOCELL, <br />ZONE X 8HB <br />LOW -VOLTAGE, 2-BUTTON HIGH BAY LIGHTING WALL SWITCH WITH <br />DESIGNATED ZONE. SWITCH TO TIE INTO GE LIGHTSWEEP LIGHTING <br />CONTROL PANEL(S) SERVING RESPECTIVE ZONES. BUTTONS SHALL <br />INCLUDE:'OVERRIDE' AND'UNASSIGNED'. REFER TO GE LIGHTING <br />LIGHTSWEEP CONTROL DRAWINGS FOR MORE INFORMATION. <br />T <br />120 MINUTE TIMER WALL SWITCH <br />D <br />SINGLE -POLE DIMMER WALL SWITCH <br />ALUMINUM LADDER TYPE CABLE TRAY. SIZE & HEIGHT AS NOTED ON DRAWINGS. <br />12" CABLE RUNWAY. <br />CE COMMUNICATIONS ENCLOSURE. <br />K� # 2-PORT MODULAR STAINLESS STEEL FACEPLATE WITH (1) CAT 5e CABLE FROM "CE" OR "CR" INDICATED AND <br />(1) RJ-45 CONNECTOR FOR DATA OUTLET, PROVIDE BLANK COVER FOR UNUSED PORT. SUBSCRIPT <br />INDICATES NUMBER OF ACTIVE JACKS IF GREATER THAN 1. <br />E STAINLESS STEEL FACEPLATE WITH MOUNTING STUD SCREWS, (1) CAT 5e UTP CABLE FROM 110 PUNCH - <br />DOWN BLOCKS INDICATED AND (1) RJ-45 CONNECTOR FOR ANALOG EMERGENCY PHONE OUTLET. MOUNT <br />OUTLET AT 48" AFF, UON. COORDINATE EXACT LOCATION WITH OWNERS FIRE SAFETY REPRESENTATIVE <br />PRIOR TO ROUGH -IN. <br />CCTV OUTLET FOR INTERIOR CAMERA: SURFACE MOUNTED BOX INSTALLED ABOVE CEILING ON TILE BRIDGE <br />WITH 1-PORT MODULAR FACEPLATE WITH (1) CAT 5e UTP CABLE AND (1) RJ-45 CONNECTOR. ROUT CAT5e <br />CABLE BACK TO "CE" OR "CR" INDICATED. CAMERA PROVIDED BY OTHERS, <br />2-PORT MODULAR STAINLESS STEEL FACEPLATE WITH (1) CAT 5e UTP CABLE FROM "CE" OR "CR" INDICATED <br />AND (1) CAT 5e CABLE FROM 110 PUNCHDOWN BLOCKS INDICATED AND (2) RJ-45 CONNECTORS, <br />PB PULLBOX. SIZE AND TYPE AS NOTED ON DRAWINGS. <br />r_ NOW PAINTED FIRE RETARDANT PLYWOOD BACKBOARD. <br />11101110 STYLE PUNCHDOWN BLOCKS. <br />CCVT CCTV ENCLOSURE FOR EXTERIOR CAMERA. <br />AMS AMS PANEL. <br />BR BADGE READER, <br />BR PREPPED DOOR AND BADGE READER <br />P <br />IS SUBSTATION POWER MONITOR NETWORK POINT OF CONNECTION. COORDINATE WITH OWNER FOR EXACT <br />LOCATION WITHIN SUBSTATION. <br />( CEILING MOUNTED VOICE/DATA OUTLET WITH (1) CAT 5e CABLE AND (1) RJ-45 CONNECTOR TO "CE" OR "CR" <br />/ INDICATED. LOCATE ADJACENT TO PROJECTOR POWER RECEPTACLE. <br />© 2-PORT MODULAR OUTLET WITH (1) CAT 5e CABLE FROM "CE" OR "CR" INDICATED AND (1) RJ-45 CONNECTOR <br />FOR DATA OUTLET. OUTLET IS MOUNTED WITHIN MULTI -PURPOSE POKE-THRU/ FLOORBOX. REFER TO <br />208/120V POWER DRAWINGS FOR POKE THRU/ FLOORBOX LOCATIONS. PROVIDE BLANK COVER FOR <br />UNUSED PORT. SUBSCRIPT INDICATES NUMBER OF ACTIVE JACKS IF GREATER THAN 1. <br />[DM DOOR MONITORING SYSTEM. <br />VENTILATION SYSTEM EMERGENCY SHUTOFF SWITCH. <br />0 - k + m17 <br />THIS DESIGN AND/OR CHEC <br />SPECIFICATION IS APPROVED RFW <br />ENGII <br />APPROVED BY DEPT. DATE DFC <br />NJ SUB -METERING NODE <br />PHASE <br />A -PHASE (LEFT BUS IN PNQ <br />-* 1 _ BUS IN •NQ <br />- <br />NEUTRAL <br />EQUIPMENT GROUND <br />!SOLATED GROUND <br />XE 4 V58-3A M A2 -1 - D <br />SUBTITLE <br />12/05/14 <br />12105/14 <br />TITLE <br />12/05/14 <br />480Y/277 VAC POWER CABLES <br />BROWN <br />ORANGE <br />YELLOW <br />GRAY <br />GREEN <br />GRN/YEL* <br />* GREEN WITH YELLOW <br />TRACER <br />BLACK <br />RED <br />BLUE <br />WHITE <br />GREEN <br />GRN/YEL* <br />**TI BUILDOUT ONLY - PROVIDE <br />NUETRAL WITH COLOR TRACER TO <br />MATCH PHASE <br />SUFFIX "D" INDICATES DISTRIBUTION PANEL <br />SUFFIX %1, -2, ETC." USED TO INDICATE MULTIPLE PANELS AT SAME LOCATION WITH SAME VOLTAGE AND FED FROM SAME VAULT <br />NEAREST COLUMN INTERSECTION <br />LOCATION OF PANEL WHEN NOT ON FIRST FLOOR: <br />TN1 = TUNNEL LEVEL 1 <br />TN2 = TUNNEL LEVEL 2 <br />P = AUTOCLAVE PIT <br />M = MEZZANINE <br />U = LEVEL 2 <br />V m LEVEL 3 <br />C = CATWALK <br />RF = ROOF <br />VAULT <br />VOLTAGE: <br />4 = 48OV, 3PH, 3W <br />3 = 480Y/277V, 3PH, 4W <br />2 = 208Y/120V, 3PH, 4W OR 120/24OV,1 PH, 3W <br />PREFIX: <br />(BLANK) = NORMAL POWER PANEL <br />"I" = ISOLATED GND PANEL <br />"Z" = 400 HZ PANEL <br />"XE" = EMERGENCY PANEL <br />"XL" = LEGALLY REQUIRED STANDBY PANEL <br />"XS" = OPTIONAL STANDBY PANEL <br />"XU" = UPS SYSTEM <br />t <br />DATE 02.13,20 <br />CURRENT REVISION SYMBOL <br />WN0317 <br />SHEET <br />EO <br />,JOB NO. <br />EVERETT, VVA DWG N0. 40-053mE0 <br />DATE <br />K*I, loia <br />01/03/17 <br />ELECTRICAL MASTER <br />