DISTRIBUTION SYSTEM.
<br />DISTRIBUTION PANELBOARD 480Y/277V
<br />POWER PANEL, 208Y/120V
<br />I�
<br />SPECIAL PANEL AS NOTED
<br />8TW
<br />GROUND ROD, "TW" INDICATES TEST WELL
<br />(4)#1,G,1 -1 /2"C
<br />HOME RUN -PANEL- CIRCUIT (EXAMPLE 2V57) CROSS MARKS
<br />2V57- 4BMA10/2,4,6
<br />PNL-CKT
<br />INDICATE QUANTITY OF CONDUCTORS (SIZE NOTED) LONGER SLASH
<br />INDICATES NEUTRAL WIRE (IF REQUIRED). IF UNMARKED INSTALL 3#12 AWG
<br />IN 3/4 " CONDUIT. REVERSED SLASH INDICATES GROUND WIRE.
<br />CONDUIT EXPOSED (RIGID METAL)
<br />CONDUIT EMBEDDED IN CONCRETE OR BELOW GRADE
<br />FLEXIBLE METAL OR LIQUIDTIGHT FLEX METAL CONDUIT AS NOTED
<br />CONDUIT TURNING UP
<br />CONDUIT TURNING DOWN
<br />G
<br />GROUND WIRE (SIZE AS NOTED)
<br />G
<br />GROUND WIRE WITH EXOTHERMIC WELD CONNECTION
<br />E
<br />EMERGENCY CIRCUIT
<br />L
<br />EXPOSED LIGHTNING PROTECTION CONDUCTOR
<br />®
<br />JUNCTION BOX, SPECIAL (SIZE NOTED, "WP"-WEATHERPROOF)
<br />®
<br />PULL BOX (SIZE NOTED, "WP"-WEATHERPROOF)
<br />FTB
<br />FIELD TERMINAL BOX
<br />F _11-01 I
<br />REMOTE 1/0 RACK
<br />_PM-1
<br />POWER MONITOR DEVICE
<br />❑T
<br />TRANSFORMER (CAPACITY, PHASE & VOLTAGE AS NOTED)
<br />NON -FUSED DISCONNECT SWITCH (ENCLOSED BREAKER OR MOLDED
<br />XX/Y NN
<br />CASE SWITCH WHERE FAULT CURRENT EXCEEDS 10KA)
<br />FF EXP
<br />XX - SWITCH RATING
<br />Y - NUMBER OF POLES
<br />FF - FUSE RATING
<br />NN - ENCLOSURE TYPE
<br />EXP - EXPLOSION PROOF (CLASS I / DIV I UNLESS NOTED OTHERWISE)
<br />Ep
<br />ENCLOSED CIRCUIT BREAKER
<br />ZA
<br />STARTER
<br />(M)
<br />MOTOR (SIZE AS NOTED)
<br />GENERATOR, ALTERNATING CURRENT (VOLTAGE, KVA,
<br />PHASES, FREQUENCY AS NOTED)
<br />I
<br />RECEPTACLE 20 AMP DUPLEX, 2 POLE, 3 WIRE
<br />h9E20
<br />CLASS I, DIVISION I EXPLOSION PROOF GFCI 125V, 20A, 2P, 3W
<br />EXP
<br />INTERLOCKING RECEPTACLE. CROUSE HINDS CPS152 (RECEPTACLE)
<br />AND GFS-1 (GFI MODULE) OR APPROVED ALTERNATE.
<br />ABOVE COUNTER RECEPTACLE 20 AMP DUPLEX, 2 POLE, 3 WIRE
<br />SIG
<br />ISOLATED GROUND RECEPTACLE, 20AMP. DUPLEX. 2 POLE. 3 WIRE
<br />If*-GF' GROUND FAULT INTERRUPT RECEPTACLE, 20AMP, DUPLEX, 2 POLE, 3WIRE
<br />WP
<br />WP INDICATES WEATHERPROOF
<br />RECEPTACLE 20AMP 4-PLEX, 2 POLE, 3 WIRE
<br />RECEPTACLE, NEMA CONFIGURATION AS INDICATED,
<br />L6-2OR
<br />RECEPTACLE, 48OV/3PH, 20A SINGLE, 3P, 4W LOCKING TYPE NEMA L6-20
<br />GROUNDING
<br />j
<br />RECEPTACLE, 208V/1 PH, 30A SINGLE, 2P, 3W LOCKING TYPE NEMA L6-30
<br />GROUNDING
<br />®
<br />JUNCTION BOX, FIELD SIZED PER NEC,
<br />0FSD
<br />JUNCTION BOX, 120V CONNECTION FOR FIRE -SMOKE DAMPER
<br />0MOD
<br />JUNCTION BOX, 120V CONNECTION FOR MOTOR -OPERATED DAMPER
<br />(�
<br />CONNECTION TO EQUIPMENT AS INDICATED.
<br />MECHANICAL EQUIPMENT TAG.
<br />$M
<br />MOTOR RATED SWITCH
<br />POKE THRU DEVICE - REFER TO DETAIL 3 ON SHEET E508-02-46
<br />PT_X
<br />PT-1 - 6" POWER/DATA/AV POKE THRU DEVICE
<br />PT-2 - 8" POWER/DATA/AV POKE THRU DEVICE
<br />SYM
<br />REVISION
<br />BY
<br />APPROVED
<br />A
<br />777X CWC NEW BUILDING -
<br />RECORD WBS 2548317
<br />JMG
<br />DFC
<br />DATE SYM
<br />01/03/17
<br />MillMllml
<br />W_21�0'
<br />LF LOW VOLTAGE CIRCUIT BREAKER.
<br />AMP FRAME/AMP TRIP.
<br />25 SYNCHRONISM - RELAY
<br />27
<br />UNDER VOLTAGE RELAY
<br />50 51
<br />INSTANTANEOUSITIME OVERCURRENT
<br />RELAY
<br />511 N
<br />INSTANTANEOUS/TIME NEUTRAL
<br />OVERCUR� NT RELAY
<br />Sx'-
<br />POWER FACTOR CORRECTION CAPACITORS
<br />,—
<br />(FUSED)
<br />�.+.�
<br />�Y>
<br />CONTROL POWER TRANSFORMER
<br />POTENTIAL TRANSFORMER
<br />IT
<br />MR
<br />CURRENT TRANSFORMER. MR INDICATES
<br />MULTI -RATIO
<br />pM
<br />ALI_EN-BRADLEY POWER MONITOR 5000
<br />ANALOG AMMETER
<br />AS
<br />AMMETER SWITCH
<br />VS
<br />VOLTMETER SWITCH
<br />ANALOG VOLTMETER
<br />SYSTEM GROUND
<br />MOTOR STARTER (COMBINATION)
<br />®
<br />MOTOR STARTER (MANUAL)
<br />S�
<br />SOLENOID VALVE
<br />®®
<br />REMOTE CONTROL STATION (TYPE AS NOTED)
<br />Fol
<br />EMERGENCY POWER SHUTDOWN
<br />PTF
<br />3-COMPARTMENT POWER POLE WIRE MOLD 30TP-4
<br />2-COMPARTMENT POWER POLE WIRE MOLD 30TP-3
<br />SB
<br />SWITCH BYPASS DEVICE
<br />CB
<br />MANUAL CONTROLLER
<br />TB
<br />TEST BLOCK
<br />LOW VOLTAGE CIRCUIT BREAKER,
<br />DRAWOUT TYPE
<br />ELECTRICALLY OPERATED
<br />UNIT SUBSTATION TRANSFORMER
<br />49
<br />OVERLOAD RELAY
<br />86
<br />LOCKOUT RELAY
<br />G1 G2
<br />KIRK KEY INTERLOCKS. SEE BOEING
<br />27
<br />STANDARDS
<br />UNDERVOLTAGE RELAY
<br />46
<br />REVERSE PHASE CURRENT RELAY
<br />47
<br />PHASE SEQUENCE VOLTAGE RELAY
<br />25
<br />SYNCHRONIZING DEVICE
<br />I
<br />I
<br />LIGHTNING ARRESTER
<br />PRIMARY MEDIUM VOLTAGE FUSED
<br />SWITCH
<br />MEDIUM VOLTAGE CABLE TERMINATION
<br />GF
<br />GROUND FAULT MONITOR
<br />SIB®
<br />SURGE PROTECTIVE DEVICE
<br />SG
<br />STATIC GROUND RECEPTACLE
<br />REVISION
<br />BY I APPROVED I DATE
<br />LIGHTING FIXTURES: UPPER CASE ALPHA -NUMERIC CHARACTER INDICATES FIXTURE TYPE.
<br />LOWER CASE ALPHANUMERIC CHARACTER INDICATES CIRCUIT NUMBER AND PHASE FED FROM.
<br />UPPER CASE ALPHANUMERIC CHARACTER IN PARENTHESIS INDICATES RELAY NUMBER.
<br />LOWER CASE LETTER INDICATES SWITCH LEG.
<br />%L" INDICATES NIGHT LIGHT OPERATION (CIRCUIT NOT SWITCHED).
<br />0
<br />STRUCTURE MOUNTED LED HIGH BAY FIXTURE. EACH FIXTURE SHALL INCLUDE
<br />A QUICK DISCONNECT AND IN -LINE FUSE.
<br />STRUCTURE MOUNTED LED HIGH BAY FIXTURE (EMERGENCY). EACH FIXTURE
<br />SHALL INCLUDE A QUICK DISCONNECT AND IN -LINE FUSE.
<br />—�
<br />INDUSTRIAL FLUORESCENT/LED LIGHTING FIXTURE.
<br />INDUSTRIAL FLUORESCENT/LED LIGHTING FIXTURE (EMERGENCY)
<br />J
<br />WALL/RECESSED/SURFACE MOUNTED FLUORESCENT LIGHTING FIXTURE.
<br />WALL/RECESSED/SURFACE MOUNTED FLUORESCENT LIGHTING FIXTURE (EMERGENCY)
<br />RECESSED MOUNTED LED LIGHTING FIXTURE
<br />RECESSED MOUNTED LED LI,GH I FIXTURE (EMERGENCY)
<br />EXTERIOR WALL PACK (EMERGENCY)
<br />WALL OR CEILING EXIT SIGN. FIXTURE SHALL BE WIRED AHEAD OF LOCAL SWITCHES. ARROW
<br />AS SHOWN DENOTES DIRECTION OF EGRESS, SOLID QUADRANT INDICATES FACE.
<br />LIGHTING L";*ONTROLS
<br />LIGHTING
<br />CONTROL SWITCHES AND OCCUPANCY SENSORS: ADDITIONAL LOWER CASE
<br />LETTER INDICATES
<br />SWITCH LEG,
<br />SINGLE POLE TOGGLE WALL SWITCH
<br />3
<br />THREE-WAY TOGGLE WALL SWITCH
<br />OS
<br />LINE -VOLTAGE OCCUPANCY SENSOR WALL SWITCH
<br />WP
<br />SINGLE POLE TOGGLE WALL SWITCH, WEATHERPROOF
<br />XX L.V
<br />LOW -VOLTAGE, 2-BUTTON ON/OFF WALL SWITCH. SWITCH TO TIE
<br />INTO GE LIGHTSWEEP LIGHTING CONTROL PANEL(S) SERVING
<br />RESPECTIVE AREA. REFER TO GE LIGHTING LIGHTSWEEP CONTROL
<br />DRAWINGS FOR MORE INFORMATION
<br />WHERE SHOWN)FIRST DIGIT REPRESENTS FLOOR (U - 2ND FLOOR, V - 3RD FLOOR)
<br />SECOND DIGIT SPECIFIES LIGHTING CONTROL ZONE, SEE CONTROL ZONE PLANS 2E8
<br />AND 3E8 FOR ADDITIONAL INFORMATION.
<br />OC
<br />CEILING MOUNTED, LOW -VOLTAGE, DUAL TECHNOLOGY OCCUPANCY SENSOR WITH POWER PACK
<br />LCP
<br />POWER PACK: HUBBELL #UVPP OR APPROVED EQUAL (FOR EACH OCCUPANCY SENSOR)
<br />ROOMS: HUBBELL #OMNI-DT-500/100 OR APPROVED EQUAL (500/1000 SO. FEET)
<br />CORRIDORS/TUNNELS: HUBBELL #OMNI-DT-2000 OR APPROVED EQUAL (2,000 SQ. FEET)
<br />SUBSCRIPT INDICATES LOW VOLTAGE OCCUPANCY SENSOR WIRED BACK TO GE LIGHTING CONTROL PANEL
<br />INDICATED.
<br />BUILDING MOUNTED PHOTOCELL,
<br />ZONE X 8HB
<br />LOW -VOLTAGE, 2-BUTTON HIGH BAY LIGHTING WALL SWITCH WITH
<br />DESIGNATED ZONE. SWITCH TO TIE INTO GE LIGHTSWEEP LIGHTING
<br />CONTROL PANEL(S) SERVING RESPECTIVE ZONES. BUTTONS SHALL
<br />INCLUDE:'OVERRIDE' AND'UNASSIGNED'. REFER TO GE LIGHTING
<br />LIGHTSWEEP CONTROL DRAWINGS FOR MORE INFORMATION.
<br />T
<br />120 MINUTE TIMER WALL SWITCH
<br />D
<br />SINGLE -POLE DIMMER WALL SWITCH
<br />ALUMINUM LADDER TYPE CABLE TRAY. SIZE & HEIGHT AS NOTED ON DRAWINGS.
<br />12" CABLE RUNWAY.
<br />CE COMMUNICATIONS ENCLOSURE.
<br />K� # 2-PORT MODULAR STAINLESS STEEL FACEPLATE WITH (1) CAT 5e CABLE FROM "CE" OR "CR" INDICATED AND
<br />(1) RJ-45 CONNECTOR FOR DATA OUTLET, PROVIDE BLANK COVER FOR UNUSED PORT. SUBSCRIPT
<br />INDICATES NUMBER OF ACTIVE JACKS IF GREATER THAN 1.
<br />E STAINLESS STEEL FACEPLATE WITH MOUNTING STUD SCREWS, (1) CAT 5e UTP CABLE FROM 110 PUNCH -
<br />DOWN BLOCKS INDICATED AND (1) RJ-45 CONNECTOR FOR ANALOG EMERGENCY PHONE OUTLET. MOUNT
<br />OUTLET AT 48" AFF, UON. COORDINATE EXACT LOCATION WITH OWNERS FIRE SAFETY REPRESENTATIVE
<br />PRIOR TO ROUGH -IN.
<br />CCTV OUTLET FOR INTERIOR CAMERA: SURFACE MOUNTED BOX INSTALLED ABOVE CEILING ON TILE BRIDGE
<br />WITH 1-PORT MODULAR FACEPLATE WITH (1) CAT 5e UTP CABLE AND (1) RJ-45 CONNECTOR. ROUT CAT5e
<br />CABLE BACK TO "CE" OR "CR" INDICATED. CAMERA PROVIDED BY OTHERS,
<br />2-PORT MODULAR STAINLESS STEEL FACEPLATE WITH (1) CAT 5e UTP CABLE FROM "CE" OR "CR" INDICATED
<br />AND (1) CAT 5e CABLE FROM 110 PUNCHDOWN BLOCKS INDICATED AND (2) RJ-45 CONNECTORS,
<br />PB PULLBOX. SIZE AND TYPE AS NOTED ON DRAWINGS.
<br />r_ NOW PAINTED FIRE RETARDANT PLYWOOD BACKBOARD.
<br />11101110 STYLE PUNCHDOWN BLOCKS.
<br />CCVT CCTV ENCLOSURE FOR EXTERIOR CAMERA.
<br />AMS AMS PANEL.
<br />BR BADGE READER,
<br />BR PREPPED DOOR AND BADGE READER
<br />P
<br />IS SUBSTATION POWER MONITOR NETWORK POINT OF CONNECTION. COORDINATE WITH OWNER FOR EXACT
<br />LOCATION WITHIN SUBSTATION.
<br />( CEILING MOUNTED VOICE/DATA OUTLET WITH (1) CAT 5e CABLE AND (1) RJ-45 CONNECTOR TO "CE" OR "CR"
<br />/ INDICATED. LOCATE ADJACENT TO PROJECTOR POWER RECEPTACLE.
<br />© 2-PORT MODULAR OUTLET WITH (1) CAT 5e CABLE FROM "CE" OR "CR" INDICATED AND (1) RJ-45 CONNECTOR
<br />FOR DATA OUTLET. OUTLET IS MOUNTED WITHIN MULTI -PURPOSE POKE-THRU/ FLOORBOX. REFER TO
<br />208/120V POWER DRAWINGS FOR POKE THRU/ FLOORBOX LOCATIONS. PROVIDE BLANK COVER FOR
<br />UNUSED PORT. SUBSCRIPT INDICATES NUMBER OF ACTIVE JACKS IF GREATER THAN 1.
<br />[DM DOOR MONITORING SYSTEM.
<br />VENTILATION SYSTEM EMERGENCY SHUTOFF SWITCH.
<br />0 - k + m17
<br />THIS DESIGN AND/OR CHEC
<br />SPECIFICATION IS APPROVED RFW
<br />ENGII
<br />APPROVED BY DEPT. DATE DFC
<br />NJ SUB -METERING NODE
<br />PHASE
<br />A -PHASE (LEFT BUS IN PNQ
<br />-* 1 _ BUS IN •NQ
<br />-
<br />NEUTRAL
<br />EQUIPMENT GROUND
<br />!SOLATED GROUND
<br />XE 4 V58-3A M A2 -1 - D
<br />SUBTITLE
<br />12/05/14
<br />12105/14
<br />TITLE
<br />12/05/14
<br />480Y/277 VAC POWER CABLES
<br />BROWN
<br />ORANGE
<br />YELLOW
<br />GRAY
<br />GREEN
<br />GRN/YEL*
<br />* GREEN WITH YELLOW
<br />TRACER
<br />BLACK
<br />RED
<br />BLUE
<br />WHITE
<br />GREEN
<br />GRN/YEL*
<br />**TI BUILDOUT ONLY - PROVIDE
<br />NUETRAL WITH COLOR TRACER TO
<br />MATCH PHASE
<br />SUFFIX "D" INDICATES DISTRIBUTION PANEL
<br />SUFFIX %1, -2, ETC." USED TO INDICATE MULTIPLE PANELS AT SAME LOCATION WITH SAME VOLTAGE AND FED FROM SAME VAULT
<br />NEAREST COLUMN INTERSECTION
<br />LOCATION OF PANEL WHEN NOT ON FIRST FLOOR:
<br />TN1 = TUNNEL LEVEL 1
<br />TN2 = TUNNEL LEVEL 2
<br />P = AUTOCLAVE PIT
<br />M = MEZZANINE
<br />U = LEVEL 2
<br />V m LEVEL 3
<br />C = CATWALK
<br />RF = ROOF
<br />VAULT
<br />VOLTAGE:
<br />4 = 48OV, 3PH, 3W
<br />3 = 480Y/277V, 3PH, 4W
<br />2 = 208Y/120V, 3PH, 4W OR 120/24OV,1 PH, 3W
<br />PREFIX:
<br />(BLANK) = NORMAL POWER PANEL
<br />"I" = ISOLATED GND PANEL
<br />"Z" = 400 HZ PANEL
<br />"XE" = EMERGENCY PANEL
<br />"XL" = LEGALLY REQUIRED STANDBY PANEL
<br />"XS" = OPTIONAL STANDBY PANEL
<br />"XU" = UPS SYSTEM
<br />t
<br />DATE 02.13,20
<br />CURRENT REVISION SYMBOL
<br />WN0317
<br />SHEET
<br />EO
<br />,JOB NO.
<br />EVERETT, VVA DWG N0. 40-053mE0
<br />DATE
<br />K*I, loia
<br />01/03/17
<br />ELECTRICAL MASTER