STRUCTURAL STEEL CONT. <br />12. A440, A103 GRADE B7, OR F1554 GRADE 105 THREADED ROD SHALL BE USED <br />WHERE THRU BOLT LENGTH DOES NOT ALLOW FOR STANDARD A325 BOLTS. PROVIDE <br />ASTM A563 NUTS WITH MATCHED WASHERS AT BOTH ENDS. <br />13. USE DOUBLE NUTS OR SINGLE NUT AND PEENED THREADS AT BOLTED CONNECTIONS <br />WITH LONG SLOT HOLES. <br />14, HOLE SIZES IN STEEL MEMBERS CONNECTED TO CONCRETE OR MASONRY SHALL BE <br />1/16" LARGER THAN THE BOLT DIAMETER. USE OF LARGER HOLES WOULD REQUIRES <br />THE USE OF WELDED PLATE WASHERS AND REQUIRES PRIOR APPROVAL BY THE <br />EOR. HARDENED OR COMMON PLATE WASHERS ARE REQUIREDBELOW ALL :NUTS WHERE <br />OVERSIZED OR SLOTTED HOLES ARE USED AND SHALL BE SIZED TO COVER THE ENTIRE <br />HOLE OR SLOT. MAXIMUM HOLE SIZES AND MINIMUM WASHER SIZES FOR COLUMN BASE <br />PLATES SHALL BE IN ACCORDANCE WITH TABLE 14-2 OF THE AISC STEEL CONSTRUCTION <br />MANUAL, 14TH EDITION. <br />15. WHERE SPECIFIED, GALVANIZED STEEL SHALL CONFORM TO ASTM A123 WITH MINIMUM <br />COATING THICKNESS GRADE 60, VENT HOLES ARE THE RESPONSIBILITY OF THE <br />CONTRACTOR AND SHALL BE INDICATED ON THE SHOP DRAWINGS. ALL STEEL MEMBERS <br />AND FASTENERS EXPOSED TO THE EXTERIOR SHALL BE HOT —DIPPED GALVANIZED. <br />16. REPAIR ALL DAMAGE TO GALVANIZED COATINGS BY EITHER THE HOT —STICK OR <br />HIGH —ZINC PAINT METHODS IN ACCORDANCE WITH ASTM A780. <br />17, FABRICATOR SHALL REVIEW PROJECT PLANS AND SPECIFICATIONS TO DETERMINE <br />PAINTING AND GALVANIZING REQUIREMENTS. MEMBERS EMBEDDED IN CONCRETE OR TO <br />RECEIVE SPRAY -ON FIREPROOFING SHALL NOT BE PAINTED. DO NOT PAINT AREAS OF <br />PIECES TO BE FIELD WELDED, OR REMOVE PAINT IN FIELD PRIOR TO WELDING. <br />18. CONTRACTOR SHALL COMPLY WITH OSHA REGULATION 20 CFR PART 1026, SUBPART <br />R — STEEL ERECTION, PUBLISHED JANUARY 18, 2001. MISCELLANEOUS PLATES FOR <br />GUYING CABLE ATTACHMENTS, TEMPORARY JOIST BRACING, ETC. SHALL BE ADDED AS <br />REQUIRED, ALL SUCH ATTACHMENTS SHALL BE SUBMITTED TO THE FOR FOR REVIEW PRIOR <br />TO FABRICATION. CONTRACTOR SHALL EVALUATE COLUMNS AND PROVIDE ADEQUATE BASE <br />PLATE SHIMS, GUYS, OR TEMPORARY BRACING AS REQUIRED PER SECTION 1926.755. <br />UNITS <br />UNLESS OTHERWISE NOTED: LINEAR DIMENSIONAL UNITS ARE FEET (A) AND INCHES (s). <br />WELDS UNITS ARE INCHES, WITHOUT THE (") DESIGNATOR. ANGLES ARE IN DEGREES. <br />DIMENSIONS: <br />CONTRACTOR SHALL FIELD VERIFY ALL EXISTING DIMENSIONS AND CONFIGURATIONS. <br />WHERE CONTRACTOR FINDS DIFFERENCES BETWEEN DIMENSIONS OR CONFIGURATIONS <br />SHOWN ON THE DRAWINGS AND THE AS —BUILT CONDITION, THE CONTRACTOR SHALL <br />SUBMIT DETAILED INFORMATION REGARDING THE DIFFERENCES TO BOETNG FOR REVIEW <br />AND APPROVAL OR MODIFICATION, DETAILS ARE SUBJECT TO CHANGE BY BOETNG IF <br />FIELD VERIFICATION SHOWS SUBSTANTIVE DIFFERENCES FROM THE DRAWINGS. <br />SAFETY: <br />THE CONTRACTOR IS RESPONSIBLE FOR THE SAFE REMOVAL AND INSTALLATION OF ALL <br />ITEMS NOTED ON THE DRAWINGS AND IN THE SPECIFICATIONS. SPECIAL CARE SHALL BE <br />TAKEN TO PREVENT HARM TO ANY REMAINING BUILDING COMPONENTS AND SYSTEMS <br />DURING REMOVAL AND INSTALLATION. THIS INCLUDES PREVENTING DAMAGE AND FIRES <br />FROM EQUIPMENT USED FOR CUTTING, GRINDING OR HEATING. ALL SUCH WORK SHALL <br />BE COORDINATED WITH BOETNG FIRE PROTECTION SERVICES. <br />EXISTING FINISHED, INSULATION AND OTHER RELATED MATERIAL MAY CONTAIN HAZARDOUS <br />MATERIALS. CONTRACTOR SHALL SURVEY ALL ITEMS TO BE REMOVED OR MODIFIED AND <br />SHALL TAKE APPROPRIATE STEPS TO SAFELY WORK WITH AND AROUND SUCH MATERIALS, <br />REMOVAL OR ALTERATION (INCLUDING CUTTING, WELDING OR HEATING) OR ANY <br />HAZARDOUS MATERIALS SHALL BE COMPLETED IN A SAFE MANNER IN ACCORDANCE WITH <br />ALL APPLICABLE LAWS AND REGULATIONS, <br />WHEN CONNECTING MATERIALS BY WELDING, CONTRACTOR SHALL REMOVE ALL FINISHES, <br />INCLUDING ANY GALVANIZING, DOWN TO BARE STEEL, FOR AT LEAST 2¢8 FROM THE WELD <br />ZONE. IF THE FINISH TO BE REMOVED CONTAINS HAZARDOUS MATERIALS, THE REMOVAL <br />PROCESS SHALL BE DONE SAFELY AND IN ACCORDANCE WITH ALL APPLICABLE LAWS <br />AND REGULATIONS. <br />COORDINATION: <br />THE CONTRACTOR SHALL COORDINATE HIS FORK WITH THE WORK OF ALL OTHER <br />TRADES. <br />DRAWING INTERPRETATION: <br />THE DRAWINGS SHOW BOTH NEW AND EXISTING CONDITIONS. NEW WORK IS CALLED OUT <br />(ANNOTATED) WITHOUT ANY SPECIAL DESIGNATION, EXISTING MATERIAL OR CONFIGURATION <br />ANNOTATIONS ARE APPENDED WITH AN (E) OR ARE CALLED OUT AS EXIST OR EXISTING. <br />SUCH EXISTING CALLOUTS ARE FOR REFERENCE AND CLARITY ONLY, AND SHALL BE <br />FIELD VERIFIED. <br />DRILLED —IN CONCRETE ANCHORS (DICA): <br />DRILLED IN CONCRETE ANCHORS, UNLESS OTHERWISE NOTED, SHALL BE OF THE SIZES <br />AND TYPES SPECIFIED ON THE DRAWINGS WITH SUFFICIENT LENGTH TO PROVIDE THE <br />MINIMUM EMBEDMENT INTO SOUND CONCRETE NOTED. ANCHORS SHALL BE ICBO <br />APPROVED AND SHALL BE INSTALLED IN STRICT ACCORDANCE WITH APPROVED ICBO <br />EVALUATION REPORT(S), <br />EPDXY ADHESIVE: <br />EPDXY ADHESIVE SHALL BE THE TYPE SPECIFIED ON THE DRAWINGS, DESIGNED FOR <br />BONDING STEEL TO HARDENED CONCRETE. <br />EPDXY MATERIALS SHALL BE MIXED, APPLIED AND CURED IN STRICT ACCORDANCE <br />WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. ALL PLACEMENT AND CURING SHALL <br />BE CONDUCTED WITH CONCRETE AND AIR TEMPERATURES ABOVE 50 DEGREES. APPLY <br />EPDXY MATERIALS ONLY TO CLEAN, DRY CONCRETE. PROVIDE POSITIVE PROTECTION <br />SO ANCHORS ARE NOT DISTURBED DURING THE CURING PERIOD. <br />HOLES FOR INSERTS SHALL BE DRILLED WITH ROTARY —IMPACT HAMMERS OR <br />EQUIVALENT IMETHODS PRODUCING A ROUGH INSIDE SURFACE. CORE DRILLING HOLES <br />FOR DOWELS SHALL NOT BE AT THE LOCATION OF A HOLE. IF REINFORCEMENT IS <br />ENCOUNTERED, THE ENGINEER OF RECORD SHALL BE CONTACTED FOR RESOLUTION. <br />HOLE DEPTHS AND DIAMETERS SHALL BE AS SHOWN ON THE DRAWINGS. <br />EXISTING STRUCTURE AND MEMBER SIZES: <br />EXISTING STRUCTURAL DIMENSIONS AND MEMBER SIZES ARE FOR REFERENCE ONLY. <br />CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD PRIOR TO FABRICATION. THE <br />CONTRACTOR SHALL VERIFY THE ACTUAL CONFIGURATION OF EXISTING CONSTRUCTION <br />AND THE CONDITION OF THE STRUCTURE BEFORE BEGINNING WORK, ANY <br />DISCREPANCIES OR UNSOUND CONDITIONS SHALL BE REPORTED TO THE ENGINEER <br />OF RECORD FOR RESOLUTION BEFORE BEGINNING WORK. <br />TEMPORARY SHORING AND BRACING IS NECESSARY IN ORDER TO PERFORM THE <br />NECESSARY STRUCTURAL ;MODIFICATIONS TO THE EXISTING STRUCTURE SHOWN ON <br />THE STRUCTURAL AND ARCHITECTURAL PLANS AND DETAILS. THE CONTRACTOR MUST <br />RETAIN A LICENSED STRUCTURAL ENGINEER WHO SHALL INVESTIGATE WHERE THIS <br />TEMPORARY SHORING/BRACING IS REQUIRED, AND SHALL DESIGN THIS TEMPORARY <br />SHORING/BRACING. <br />PROJECT DATUM: <br />ELEVATION 5 Sp-388 - 0'-0" DATUM. DIMENSIONS SHOWN ARE RELATIVE TO THIS <br />DATUM. ELEVATIONS NOTED ON THE EXISTING 45-03 DRAWINGS ARE 3 INCHES <br />HIGHER, THAN THE 45-04 ELEVATIONS SHOWN ON THE 45-04 DRAWINGS. <br />THEREFORE, 558a-6" NOTED ON THE 45-03 DRAWINGS IS EQUAL TO 555'—Y <br />RELATIVE TO THE 45-04 DATUM. <br />LATERAL FORCES DUE TO WIND, EARTHQUAKE, SOIL, OR STABILITY ARE CARRIED BY <br />THE ROOF, FLOOR DIAPHRAGMS AND HORIZONTAL BRACING TO THE BRACED FRAMES. <br />CERTAIN ELEMENTS SHOWN ONE THE STRUCTURAL DRAWINGS (SUCH AS WALLS, ROOF, <br />AND FLOOR SLABS) ARE REQUIRED FOR OVERALL OR LOCAL STABILITY OF OTHER <br />ELEMENTS (SUCH AS MEANS, COLUMNS, AND WALLS). IF, DUE TO SEQUENCING OF <br />CONSTRUCTION, THESE STABILITY ELEMENTS ARE NOT IN PLACE, THE CONTRACTOR <br />SHALL RETAIN A LICENSED STRUCTURAL_ ENGINEER WHO SHALL INVESTIGATE WHERE <br />THIS TEMPORARY SHORING/BRACING IS REQUIRED, AND SHALL DESIGN THIS <br />TEMPORARY SHORING/BRACING. <br />ANSI/AISC 360-10 TABLE N5.4-1 <br />INSPECTION TASKS PRIOR TO WELDING <br />INSPECTION ,ASKS PRIOR TO WELDING <br />� QC <br />QA <br />WELDING PROCEDURE SPECIFICATIONS (WPSS) AVAILABLE <br />P <br />P <br />MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES <br />P <br />P <br />AVAILABLE <br />MATERIAL IDENTIFICATION (TYPE/GRADE) <br />0 <br />0 <br />WELDER IDENTIFICATION SYSTEM' _ <br />0 <br />0 <br />FIT —UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY) <br />— JOINT PREPARATION <br />— DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) <br />— CLEANLINESS (CONDITION OF STEEL SURFACES) <br />P <br />0 <br />— TACKING (TACK MELD QUALITY AND LOCATION) <br />— BACKING TYPE AND FIT (IF APPLICABLE) <br />CONFIGURATION AND FINISH OF ACCESS HOLES <br />0 <br />0 <br />FIT —UP OF FILLET MELDS <br />— DIMENSIONS (ALIGNMENT, GAPS AT ROOT) <br />— CLEANLINESS (CONDITION OF STEEL SURFACES) <br />P <br />0 <br />— TACKING (TACK WELD QUALITY AND LOCATION) <br />CHECK WELDING EQUIPMENT <br />0 <br />— <br />1. THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY <br />WHICH A WELDER WHO HAS WELDED A JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, <br />IF USED, SHALL BE THE LOW —STRESS TYPES. <br />0 — OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYEI <br />PENDING THESE INSPECTIONS <br />P — PERFORM THESE TASKS FOR EACH GELDED JOINT OR MEMBER <br />sym REVISION BY APPROVED DATE SYm REVISION BY APPROVED DATE <br />C IG 45-001 STRUCTURAL VERTICAL UPGRADES 1786915 CP&A — 10,08.19 <br />DEFERRED SUBMITTAL 1786915 CP ,A/HSK — 07.10.20 <br />ANSI/AISC 360-10 TABLE N5.4-2 <br />INSPECTION TASKS DURING WELDING <br />INSPECTION TASKS DURING WELDING <br />QC <br />QA <br />USE OF QUALIFIED WELDERS <br />0 <br />0 <br />CONTROL AND HANDLING OF WELDING CONSUMABLES <br />— PACKAGING <br />0 <br />0 <br />— EXPOSURE CONTROL <br />NO WELDING OVER CRACKED TACK WELDS <br />0 <br />0 <br />ENVIRONMENTAL CONDITIONS <br />— FIND SPEED WITHIN LIMITS <br />0 <br />0 <br />— PRECIPITATION AND TEMPERATURE <br />WPS FOLLOWED <br />— SETTINGS ON WELDING EQUIPMENT <br />— TRAVEL SPEED <br />0 <br />0 <br />— SELECTED WELDING MATERIALS <br />— I p r A <br />— PREHEAT APPLIED <br />— INTERPASS TEMPERATURE MAINTAINED (MIN /MAX) <br />P <br />0 <br />— PROPER POSITION (FA V, H, OH) <br />0 <br />0 <br />MELDING TECHNIQUES <br />— INTERPASS AND FINAL CLEANING <br />0 <br />O <br />— EACH PASS WITHIN PROFILE LIMITATIONS <br />— EACH PASS MEETS QUALITY REQUIREMENTS j <br />I <br />0 — OBSERVE THESE ITEMS ON A RANDOk1 BASIS, OPERATIONS NEED NOT BE <br />DELAYED PENDING THESE INSPECTIONS <br />P — PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER <br />ANSI/AISC 360-10 TABLE N5.4-3 <br />INSPECTION TASKS AFTER WELDING <br />INSPECTION TASKS AFTER WELDING <br />QC <br />QA <br />WELDS CLEANED <br />P <br />0 <br />SIZE, LENGTH AND LOCATION OF WELDS <br />P <br />P <br />WELDS MEET VISUAL ACCEPTANCE CRITERIA <br />— CRACK PROHIBITION <br />— WELD/BASE—METAL FUSION <br />— CRATER CROSS SECTION <br />P <br />P <br />— WELD PROFILES <br />— WELD SIZE <br />— UNDERCUT <br />— POROSITY <br />ARC STRIKES <br />P <br />P <br />k—AREA <br />P <br />P <br />BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) <br />P <br />P <br />REPAIR ACTIVITES <br />P <br />P <br />DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT <br />P <br />P <br />OR MEMBER <br />1. WHEN WELDING OF DOUBLER PLATES; CONTINUITY PLATES OR <br />STIFFENERS <br />HAS <br />BEEN PERFORMED IN THE k—AREA, VISUALLY INSPECT THE WEB <br />L—AREA FOR <br />CRACKS <br />WITHIN 3 IN. (75MM) OF THE MELD. <br />0 — OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE <br />DELAYED PENDING THESE INSPECTIONS <br />P — PERFORM THESE TASKS FOR EACH 'GELDED JOINT OR MEMBER <br />ANSI/RISC 360-10 TABLE N5.6-1 <br />INSPECTION TASKS PRIOR TO BOLTING <br />INSPECTION TASKS PRIOR TO BOLTING <br />QC <br />QA <br />MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER <br />0 <br />P <br />MATERIALS <br />FASTENERS LARKED IN ACCORDANCE WITH ASTM <br />0 <br />0 <br />REQUIREMENTS <br />PROPER FASTENERS SELECTED FOR THE JOINT DETAIL <br />(GRADED TYPE, BOLT LENGTH IF THREADS ARE TO BE <br />0 <br />0 <br />EXCLUDED FROM SHEAR PLANE) <br />PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL <br />0 <br />0 <br />CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING <br />SURFACE CONDITION AND HOLE PREPARATION, IF SPECIFIED, <br />0 <br />0 <br />MEET APPLICABLE REQUIREMENTS <br />PRE —INSTALLATION VERIFICATION TESTING BY INSTALLATION <br />PERSONNEL OBSERVED AND DOCUMENTED FOR FASTENER <br />P <br />0 <br />ASSEMBLIES AND METHODS USED <br />PROPER STORAGE PROVIDED FOR BOLTS, NUTS, DASHERS <br />0 <br />0 <br />AND OTHER FASTENER COMPONENTS <br />ANSI/AISC 360-10 TABLE N5.6-2 <br />INSPECTION TASKS DURING BOLTING <br />INSPECTION TASKS DURING BOLTING <br />QC <br />QA <br />FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN <br />ALL HOLES AND WASHERS (IF REQUIRED) ARE POSITIONED <br />0 <br />0 <br />AS REQUIRED <br />JOINT BROUGHT TO THE SNUG —TIGHT CONDITION PRIOR TO <br />0 <br />0 <br />THE PRETENSIONING OPERATION <br />FASTENER COMPONENT NOT TURNED BY THE WRENCH <br />O <br />0 <br />PREVENTED FROM ROTATING <br />FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE <br />RCSC SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM <br />0 <br />0 <br />THE MOST RIGID POINT TOWARD THE FREE EDGES <br />ANSI/RISC 360-10 TABLE N5.6-3 <br />INSPECTION TASKS AFTER BOLTING <br />INSPECTION TASKS AVER BOLTING QC QA <br />DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED P P <br />CONNECTIONS <br />TABLE 1705.3 REQUIRED SPECIAL <br />INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION <br />TYPE CONTINUOUS PERIODIC INSPECTION REFERENCED IBC REFERENCE <br />SPECIAL INSPECTION STANDARD <br />1. ADHESIVE ANCHORS USED TO TRANSFER <br />SHEAR. NOTE THAT EVEN THOUGH ANCHORS ACI 31 S: 1.0 <br />ARE NOT USED TO TRANSMIT TENSION, — X ACI 316 17.5.2.2 <br />INSTALLERS SHALL BE CERTIFIED PER ACI ACI 31 S: 17.523 <br />REQUIREMENT. <br />wl. <br />1) !� I Ai>EPTAEILI1�` I- <br />o THIS DESIGN AND/OR <br />aAl f SPECIFICATION IS APPROVED I — <br />'T 6' <br />APPROVE BY_ DEPT'. 1��T � i — <br />e 7i <br />91 <br />o!A� <br />DEFERRED SUBM7TAL <br />