ELECTRICAL SYMBOLS LEGEND
<br />SYMBOL
<br />(N)
<br />NEW CIRCUIT
<br />(E)
<br />EXISTING CIRCUIT TO REMAIN
<br />(D)
<br />EXISTING CIRCUIT TO DEMOLISH
<br />(R)
<br />RELOCATED CIRCUIT TO INTERCEPT AND EXTEND
<br />HOMERUN
<br />PANEL BOARD
<br />SIMPLEX RECEPTACLE
<br />DUPLEX RECEPTACLE
<br />QUADRUPLEX RECEPTACLE
<br />C
<br />CEILING RECEPTACLE
<br />P
<br />PENDANT RECEPTACLE
<br />GFCI
<br />GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE
<br />IG
<br />ISOLATED GROUND RECEPTACLE
<br />WP
<br />WEATHERPROOF RECEPTACLE
<br />+1811
<br />RECEPTACLE WITH MOUNTING HEIGHT
<br />FLOOR RECEPTACLE
<br />SPECIAL PURPOSE RECEPTACLE, MATCH TO "NEMN PATTERN OF EQUIPMENT
<br />DIRECT CONNECTION
<br />PLUG MOLD STRIP
<br />DISCONNECT
<br />J
<br />JUNCTION BOX
<br />J
<br />FLOOR JUNCTION BOX
<br />PP
<br />TWO SECTION DATAJPOWER POLE
<br />SINGLE POLE SWITCH
<br />S2
<br />TWO POLE SWITCH
<br />SD
<br />DIMMER SWITCH
<br />SM
<br />MOTOR RATED SWITCH
<br />Sz
<br />DATA RECEPTACLE WITH 3/4" CONDUIT, COORDINATE EXACT REQUIREMENTS WITH NETWORK SERVICES
<br />OS
<br />OCCUPANCY SENSOR, CEILING MOUNT
<br />F
<br />MANUAL PULL STATION
<br />S
<br />SMOKE DETECTOR
<br />H
<br />FIRE ALARM HORN
<br />S
<br />FIRE ALARM STROBE {# a CANDELA)
<br />94FIRE
<br />ALARM HORN STROBE (# = CANDELA)
<br />123
<br />ARCHITECTURAL ROOM NO.
<br />AC
<br />ABOVE COUNTER
<br />DC
<br />DROP CORD
<br />SOLID HEAVY LINE INDICATES RACEWAY AND OR CONDUCTORS ABOVE FINISHED FLOOR.
<br />DASHED HEAVY LINE INDICATES RACEWAY AND OR CONDUCTORS BELOW FINISHED FLOOR.
<br />EF
<br />MECHANICAL EQUIPMENT NUMBER
<br />Es®
<br />DETAIL NUMBER CALLOUT
<br />3 E E
<br />OTE
<br />#2
<br />DEVICE PLACEMENT
<br />48"
<br />MAX
<br />ALL OPERABLE
<br />PARTS MUST BE
<br />WITHIN
<br />SPECIFIED
<br />RANGES
<br />15'° MIN
<br />FIN. FLR.
<br />ELECTRICAL
<br />GENERAL MOTES:
<br />1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS, INCLUDING ANY ACCOMPANYING SPECIFICATIONS, ARE BASED ON
<br />BEST AVAILABLE INFORMATION AND ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE
<br />BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, REVIEW ALL RELEVANT DOCUMENTATION, AND BECOME
<br />FAMILIAR WITH THE SCOPE OF WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION, OR CONFLICT EXIST IN THE
<br />PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING THEIR BID
<br />PRICE SO THAT A PRE -BID ADDENDUM CAN BE ISSUED, OTHERWISE, THE CONTRACTOR SHALL SUPPLY THE PROPER
<br />MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS INCLUSIVE OF THEIR ORIGINAL BID. UPON
<br />COMPLETION OF EACH ELECTRICAL SYSTEM, THE CONTRACTOR SHALL TEST AND CONFIRM ITS PROPER OPERATION. ANY
<br />INCOMPLETE SYSTEM SHALL BE MADE COMPLETE AND OPERABLE PRIOR TO PROJECT CLOSEOUT.
<br />2. THE PLANS FOR OTHER TRADES, SUCH AS ARCHITECTURAL, MECHANICAL, PLUMBING, AND REFRIGERATION, ARE
<br />CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE
<br />CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO
<br />COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES OR IF EQUIPMENT DIMENSIONS ARE GREATER THAN
<br />SPECIFIED OR DIMENSIONED ON THE ELECTRICAL PLANS.
<br />3. THE CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS, AND LABOR REQUIRED FOR THE ELECTRICAL CONNECTIONS
<br />OF ALL EQUIPMENT SHOWN ON THE PLANS FOR OTHER TRADES, SUCH AS ARCHITECTURAL, MECHANICAL, PLUMBING,
<br />AND REFRIGERATION.
<br />4. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH THE MOST RECENT LOCAL, STATE, AND NATIONAL
<br />CODES. IF AT ANY TIME DURING OR AFTER CONSTRUCTION SOMETHING IS FOUND TO BE INSTALLED IN VIOLATION OF
<br />THESE CODES, IT SHALL BE CORRECTED BY THE CONTRACTOR.
<br />5. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED
<br />TESTING AGENCY THAT IS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION AND BE PROPERLY INSTALLED FOR
<br />THE CONDITIONS AND SPACE THAT IT IS BEING INSTALLED WITHIN.
<br />6. THE CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT
<br />SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE CONTRACTOR SHALL GROUND THE ELECTRICAL
<br />SYSTEM IN ACCORDANCE WITH THE MOST RECENT LOCAL, STATE, AND NATIONAL CODES.
<br />7. ALL CONDUIT SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO ROOF JOISTS. CONDUIT LAYOUTS SHOWN ON THE
<br />PLANS ARE DIAGRAMMATIC, NOT INDICATING THE EXACT ROUTING REQUIRED. THE CONTRACTOR SHALL ROUTE THE
<br />CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING,
<br />EQUIPMENT, BUILDING STRUCTURE, AND OTHER POTENTIAL OBSTRUCTIONS.
<br />8. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH -IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAtRE,
<br />ETC. A DISTANCE OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.
<br />9. THE CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY=STANDARD
<br />METHODS AND PRACTICES. TO ENSURE ALL DEVICES ARE RIGIDLY FIXED, THE CONTRACTOR SHALL SECURE ALL DEVICE
<br />BOXES WITH BRACKETS, HANGERS, ETC, DESIGNED FOR THE APPLICATION.
<br />10. UNLESS OTHERWISE NOTED, THE MINIMUM SIZE CONDUIT SHALL BE 3/4-INCH. FOR DRY INTERIOR LOCATIONS THAT ARE
<br />NOT SUBJECT TO PHYSICAL DAMAGE, THE CONDUIT SHALL BE EMT WITH STEEL SET SCREW FITTINGS. FOR INTERIOR
<br />LOCATIONS SUBJECT TO PHYSICAL DAMAGE AND EXTERIOR LOCATIONS, EXCEPT FOR THE SERVICE ENTRANCE, THE
<br />CONDUIT SHALL BE GALVANIZED RIGID STEEL CONDUIT (GRC). FOR DAMP INTERIOR LOCATIONS THAT ARE NOT SUBJECT
<br />TO PHYSICAL DAMAGE, THE CONDUIT SHALL BE EMT WITH COMPRESSION GLAND TYPE FITTINGS. FOR WET INTERIOR
<br />LOCATIONS THAT ARE NOT SUBJECT TO PHYSICAL DAMAGE, THE CONDUIT SHALL BE SCHEDULE 40 PVC. FOR WET
<br />INTERIOR LOCATIONS THAT ARE SUBJECT TO PHYSICAL DAMAGE, THE CONDUIT SHALL BE GRC. UNDERGROUND CONDUIT
<br />SHALL BE SCHEDULE 40 PVC WITH GRC ELBOWS AND RISERS THAT ARE WRAPPED IN CORROSION -RESISTANT MATERIALS
<br />WHERE INDIRECT CONTACT WITH SOIL OR CONCRETE.
<br />11. FLEXIBLE CONDUIT AND MC CABLE SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO
<br />MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR LIQUID -TIGHT FLEXIBLE CONDUIT
<br />SHALL NOT BE GREATER THAN 72 INCHES.
<br />12. THE CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH A 200LB RATED NYLON PULL CORD.
<br />13. WHERE WIRE SIZE IS NOT SHOWN ON THE PLANS FOR 20A, 120V BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF TWO
<br />#12 THHN, COPPER CONDUCTORS, AND ONE #12 THHN, COPPER GROUND IN 314-INCH CONDUIT. REFER TO EQUIPMENT
<br />SCHEDULES, FEEDER SCHEDULES, AND NOTES ON THE PLANS FOR WIRE AND CONDUIT SIZING FOR ALL OTHER BRANCH
<br />AND FEEDER CIRCUITS. THE CONTRACTOR VERIFY ACTUAL INSTALLATION CONDITIONS AND MAINTAIN A MAXIMUM
<br />VOLTAGE DROP OF 3-PERCENT FOR BRANCH CIRCUITS AND 2-PERCENT FOR FEEDER CIRCUITS.
<br />% UNLESS OTHERWISE NOTED, CONDUCTORS SHALL BE 600VAG RATED, TYPE THHN/THWN-2, COPPER. CONDUCTORS UP TO
<br />#10 MAY BE SOLID OR STRANDED, AND CONDUCTORS #8 OR LARGER SHALL BE STRANDED. TERMINATION OF STRANDED
<br />CONDUCTORS MUST BE MADE USING UL LISTED DEVICES DESIGNED FOR THE APPLICATION.
<br />15. AFTER THE INSTALLATION IS COMPLETE, THE CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM, INCLUDING
<br />REMOVING ALL FINGERPRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, AND UNNECESSARY LABELS OR STICKERS FROM
<br />FIXTURES AND EQUIPMENT. ADDITIONALLY, THE CONTRACTOR SHALL REMOVE ALL ACCUMULATED RUBBISH AND DEBRIS
<br />FROM THE PREMISES.
<br />16. ALL PENETRATIONS THROUGH FIRE -RATED ASSEMBLIES SHALL BE SEALED WITH A FIRE -RATED SEALANT, SUCH AS 3M
<br />FIRESTOP FIRE -BARRIER CAULK, PUTTY, WRAP STRIPS, AND COMPOSITE SHEETS, OR DOW CORNING 3-6548 SILICONE RTV
<br />FOAM.
<br />17. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF WALL -MOUNTED DEVICES WITH CABINETRY AND OTHER WALL
<br />OBSTRUCTIONS AND CEILING -MOUNTED DEVICES WITH CEILING OBSTRUCTIONS. ANY DEVICES THAT NEED TO BE
<br />RELOCATED SHALL BE COORDINATED WITH THE FRED MEYER RELAY MANAGER, KROGER PROJECT MANAGER; AND FINAL
<br />FIXTURE PLAN BEFORE ROUGH -IN.
<br />18. DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. EXACT DEVICE LOCATIONS SHALL BE AS INDICATED
<br />ON THE ARCHITECTURAL PLANS OR AS DIMENSIONED. IF NOT SHOWN ON THE ARCHITECTURAL PLANS OR DIMENSIONED
<br />ON THE ELECTRICAL PLANS, VERIFY THE EXACT LOCATION WITH THE ARCHITECT PRIOR TO ROUGH -IN.
<br />19. NO SCREWS ARE TO RUN INTO THE ROOF DECK UNDER ANY CIRCUMSTANCES.
<br />REMODEL NOTES:
<br />20. THE CONTRACTOR SHALL PROVIDE NEW, UPDATED PANEL DIRECTORIES FOR ALL PANELS IN WHICH CIRCUITS ARE
<br />ADDED, RELOCATED, OR REMOVED. UNUSED CIRCUITS SHALL BE MARKED SPARE.
<br />21, THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTING TO AREAS AS REQUIRED BASED ON THE PHASING
<br />PLAN WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.
<br />22, THE CONTRACTOR SHALL MAINTAIN POWER TO ALL DOWNSTREAM EQUIPMENT WHEN ANY EXISTING EQUIPMENT IS
<br />REMOVED.
<br />23. THE CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE EXISTING POWER PANELS FROM
<br />WHICH NEW CIRCUITS ARE BEING FED. ADDITIONALLY, THE CONTRACTOR SHALL VERIFY EXISTING BRANCH CIRCUIT
<br />BREAKERS AND PROVIDE NEW BRANCH CIRCUIT BREAKERS AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.
<br />24. THE CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELECOM ROOM FROM WHICH NEW
<br />TELEPHONE/DATA OUTLETS WILL BE FED. ADDITIONALLY, THE CONTRACTOR SHALL VERIFY EXISTING PATCH PANEL
<br />SPACES AND PROVIDE NEW PATCH PANELS AS NECESSARY TO LAND/TERMINATE NEW TELECOM CABLING.
<br />25, AS REQUIRED, EXISTING FLOOR DUCT JUNCTION BOXES AND RECEPTACLES SHALL BE RELEVELED AND REPAIRED TO
<br />MATCH THE FINISHED FLOOR WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.
<br />NEW CIRCUIT UNMARKED CONDUITS
<br />CONTAIN 2CONDUGTORS.
<br />10
<br />PANEL HOMERUN 3/4"
<br />LIGHTING OR MINIMUM RACEWAY
<br />POWER OUTLETS UNLESS NOTED THREE POLE
<br />OTHERWISE BREAKER
<br />EA-1(3,5)
<br />NO, OF CONDUCTORS 4-12-3/4"C.
<br />SIZE OF CONDUCTORS
<br />SIZE OF RACEWAY
<br />ISOLATED GROUND CIRCUITRY
<br />C-1,3,5
<br />6-10CU-1"C
<br />3-10CU ISOLATED GND
<br />1-10CU EQUIPMENT GND
<br />THREE SINGLE POLE CIRCUITS
<br />A-1,3,5
<br />6-10CU-3/4"C
<br />1®10CU EQUIPMENT GND
<br />LIGHTING NOTES:
<br />26. ANY FLUORESCENT LIGHT FIXTURES WITH EXISTING T12 OR T8 TYPE LAMPS WITHIN THE STORE SHALL BE REPORTED TO
<br />THE KROGER PROJECT MANAGER BY THE ELECTRICAL CONTRACTOR FOR COORDINATION OF REPLACEMENT.
<br />27. EXISTING LED LIGHT FIXTURES SHALL REMAIN. INSPECT FOR PROPER OPERATION. CLEAN AND REFURBISH AS REQUIRED.
<br />COORDINATE IF A NEW FIXTURE IS NEEDED WITH KROGER PROJECT MANAGER.
<br />28. THE EXISTING VESTIBULE AND EXTERIOR WALL PACK LIGHT FIXTURES SHALL BE INSPECTED FOR OPERATION, CLEAN AND
<br />REFURBISH AS REQUIRED. ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL LIKE TYPE LAMPS FOR EXISTING
<br />FIXTURES THAT ARE NOT OPERATING.
<br />29. THE QUEVISION SENSING DEVICE LOCATIONS SHALL HAVE PRIORITY OVER THE INTERIOR LIGHTING PATTERN. WHERE
<br />INTERFERENCE OCCURS, THE CONTRACTOR SHOULD ADJUST THE LIGHTING PATTERN AS NEEDED TO ACCOMMODATE
<br />THE REQUIREMENTS OF THE QUEVISION SENSING DEVICES. CONTRACTOR TO COORDINATE ALL ADJUSTMENTS WITH THE
<br />QUEVISION INSTALLATION REPRESENTATIVE AND THE KROGER PROJECT MANAGER.
<br />30. ALL BATTERY -POWERED OR CONTINUOUS BURN LUMINAIRES SHOWN ON THE PLANS, SUCH AS EXIT LIGHTS, NIGHT
<br />LIGHTS, OR EMERGENCY LIGHTS, SHALL BE CONNECTED TO THE UNSWITCHED LEG OF THE LIGHTING CIRCUIT FEEDING
<br />THAT AREA.
<br />31. LUMINAIRES INSTALLED IN THE MECHANICAL ROOMS SHALL BE PLACED SO THAT ALL EQUIPMENT IS ADEQUATELY
<br />ILLUMINATED AFTER THE MECHANICAL EQUIPMENT IS IN PLACE.
<br />32. ALL LUMINAIRES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE, NOT THE CEILING GRID OR OTHER
<br />NONSTRUCTURAL MEMBERS.
<br />33. TO ACHIEVE AND MAINTAIN A CONSISTENT LIGHT QUALITY, FOR ALL SUPPLIED AND INSTALLED LAMP TYPES, LAMPS
<br />SHALL BE OF THE SAME MANUFACTURER, COLOR TEMPERATURE, COLOR RENDERING INDEX, LAMP EFFICACY, LUMEN
<br />OUTPUT, AND STARTING CHARACTERISTICS.
<br />34. LUMINAIRES INSTALLED IN DAMP OR WET LOCATIONS SHALL BE UL LISTED FOR INSTALLATION IN THE ENVIRONMENT,
<br />CAR€ SHOULD BE TAKEN TO ENSURE THAT DIFFUSERS AND LENSES ARE APPROPRIATE FOR THEIR INSTALLED USE, AND
<br />PREMATURE DISCOLORATION WILL NOT RESULT DUE TO EXPOSURE TO UV LIGHT, CHEMICALS, OR OTHER CONDITIONS.
<br />POWER NOTES;
<br />35. ALL ELECTRICAL CONDUITS IN THE SALES AREA DESCENDING FROM ROOF FRAMING TO EITHER LOW WALLS OR
<br />EQUIPMENT SHOULD BE COORDINATED AND GROUPED WITH OTHER MECHANICAL PIPES.
<br />36. INSTALL JUNCTION BOX AND CIRCUIT TO POWER TWO QUEVISION HANGING FLAT -SCREEN MONITORS, CONFIRM THE
<br />EXACT LOCATION OF THE MONITORS WITH QUEVISION INSTALLER OR KROGER PM BEFORE INSTALLING JUNCTION BOX.
<br />QUEVISION INSTALLER TO INSTALL THE 120-VOLT CONVENIENCE OUTLET ON HANGING MONITOR POLE/BRACKET AND
<br />MAKE THE FINAL CONNECTION AT THE JUNCTION BOX.
<br />37. LOCATE ALL OVERHEAD ELECTRICAL DROPS TO SHELVING AT THE CENTER OFF THE SHELVING RUN. RUN CONDUIT
<br />VERTICALLY FROM A JUNCTION BOX AT THE ROOF FRAMING TO THE TOP OF THE SHELVING UNIT. SECURE CONDUIT TO
<br />THE TOP OF THE SHELVING AND PAINT TO MATCH COLUMNS.
<br />38. UNLESS OTHERWISE NOTED, MOUNT ALL DISCONNECTS AT 5-0" ABOVE FLOOR FINISH TO THE DISCONNECT HANDLE.
<br />39. THE CONTRACTOR SHALL COORDINATE THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS
<br />WITH THE FRED MEYER RELAY MANAGER, KROGER PROJECT MANAGER, AND FINAL FIXTURE PLAN BEFORE ROUGH -IN.
<br />UNLESS OTHERWISE DIRECTED, THE CONTRACTOR SHALL MAKE THE FINAL CONNECTION FOR ALL EQUIPMENT. THE
<br />CONTRACTOR SHALL OBTAIN WIRING DIAGRAMS FROM THE EQUIPMENT SUPPLIER FOR ALL EQUIPMENT BEFORE ANY
<br />ROUGH -IN. ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE CONTRACTOR WITHOUT A WIRING DIAGRAM SHALL
<br />BE CORRECTED AT THE CONTRACTOR'S EXPENSE. THE CONTRACTOR SHALL PROVIDE COPIES OF WIRING DIAGRAMS
<br />WITHIN EACH PIECE OF EQUIPMENT AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.
<br />40. THE CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE
<br />MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS. REFER TO THE MECHANICAL PLANS FOR
<br />THE LOCATION OF THERMOSTATS.
<br />41. THE CONTRACTOR SHALL PROVIDE A 20-AMP, 120-VOLT RECEPTACLE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
<br />SERVICING OF ALL HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT PER NEC ARTICLE 210.63. THE
<br />RECEPTACLE SHALL HAVE GFCI PROTECTION, AND BE INSTALLED IN A CAST METAL BOX WITHIN 25 FEET OF THE
<br />EQUIPMENT IT SERVES.
<br />42. ALL SINGLE-PHASE RECEPTACLES 50-AMPS OR LESS AND THREEaPHASE RECEPTACLE5100-AMPS OR LESS THAT ARE
<br />INSTALLED WITHIN 6-FEET OF A SINK SHALL HAVE GROUND -FAULT CIRCUIT -INTERRUPTER PROTECTION FOR PERSONNEL
<br />PER NEC ARTICLE 210.8(B)(2).
<br />ROOF NOTES:
<br />43. THE CONTRACTOR SHALL INSTALL A ROOF JACK (BOOT) FOR ALL CONDUIT PENETRATIONS THROUGH THE ROOF, ALL
<br />ROOF PENETRATION SEALS SHALL BE IN ACCORDANCE WITH THE ROOF WARRANTY AND BE COMPLETELY SEALED WITH
<br />ROOF ADHESIVE. THE CONTRACTOR SHALL USE PROPER CLAMPING METHODS TO SEAL BOOT AROUND THE CONDUIT.
<br />KITCHEN NOTES:
<br />44. THE ONLY SURFACE -MOUNTED CONDUIT PERMITTED IN THE DELI AND BAKERY PREP ROOMS SHALL BE ON THEIR COOLER
<br />AND FREEZER WALLS AND CEILINGS.
<br />45. NO SURFACE MOUNTED CONDUIT IS ALLOWED IN MEAT AND PRODUCE PREP ROOMS.
<br />46. FOR ALL APPLIANCES WITHOUT A CORD -AND -PLUG CONNECTION, THE CONTRACTOR SHALL VERIFY THE APPLIANCE
<br />INCLUDES A UNIT SWITCH COMPLYING WITH NEC ARTICLE 422.34 AND HAS OTHER MEANS FOR DISCONNECTION PER NEC
<br />ARTICLE 422.34(A) THROUGH (D). IF THE APPLIANCE HAS NO UNIT SWITCH, THE CONTRACTOR SHALL PROVIDE A
<br />LOCKABLE MEANS OF DISCONNECT COMPLYING WITH NEC ARTICLE 110.25.
<br />47. ALL SINGLE-PHASE KITCHEN RECEPTACLES 50-AMPS OR LESS AND THREE-PHASE KITCHEN RECEPTACLES 100-AMPS OR
<br />LESS SHALL HAVE GROUND -FAULT CIRCUIT -INTERRUPTER PROTECTION FOR PERSONNEL PER NEC ARTICLE 210.8(B)(2).
<br />REFRIGERATION NOTES:
<br />48. ALL ELECTRICAL CONDUITS TO REFRIGERATED CASES SHALL BE COORDINATED AND GROUPED WITH REFRIGERATION
<br />PIPING PIPES.
<br />49. THE CONTRACTOR SHALL COORDINATE THE EXACT LOCATIONS OF ALL REFRIGERATION EQUIPMENT AND ELECTRICAL
<br />CONNECTIONS WITH THE FRED MEYER RELAY MANAGER, KROGER PROJECT MANAGER, FINAL FIXTURE PLAN, AND THE
<br />REFRIGERATION CONTRACTOR BEFORE ROUGH -IN. UNLESS OTHERWISE DIRECTED, THE CONTRACTOR SHALL MAKE THE
<br />FINAL CONNECTION FOR ALL EQUIPMENT. THE CONTRACTOR SHALL OBTAIN WIRING DIAGRAMS FROM THE EQUIPMENT
<br />SUPPLIER FOR ALL EQUIPMENT BEFORE ANY ROUGH -IN. ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE
<br />CONTRACTOR WITHOUT A WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. THE CONTRACTOR
<br />SHALL PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE OF EQUIPMENT AND ADDITIONAL COPIES WITH THE
<br />OPERATION AND MAINTENANCE MANUALS.
<br />50. THE CONTRACTOR SHALL PROVIDE WEATHERPROOF BOXES,
<br />51. THE CONTRACTOR SHALL PROVIDE EMPTY CONDUITS AS REQUIRED FOR ALL REFRIGERATION CONTROLS WIRING AND
<br />COORDINATE ALL REFRIGERATION CONTROLS WORK WITH THE EMS CONTRACTOR AND PLANS. THE EMS CONTRACTOR
<br />PROVIDES WIRING AND MAKES THE FINAL CONNECTIONS FOR ALL REFRIGERATION CONTROLS.
<br />ArchitectureInteriors
<br />PlanningEngineering
<br />Portland, OR
<br />503.224.9560
<br />!Vancouver, WA
<br />360.695.7879
<br />Seattle, WA
<br />206.749.9993
<br />www.mcknze.com
<br />MACKENZIE
<br />DESIGN DRIVEN ICLIENT FOCUSED
<br />Client
<br />FRED MEYER
<br />PORTLAND, OR 97202
<br />Jc6m eafM sY�ga
<br />Project
<br />FRED MEYER #458
<br />MILL CREEK
<br />12906 TLL-
<br />T HWY
<br />EVERETT, WA 98208
<br />Mechanical/Electrical
<br />Engineering Consultants Incorporated
<br />303 Federal Way Boise, ID 83705
<br />Pho�ie:308.376.9$20:FtLY.2t}�.376.4322
<br />NVIIV- .eciboise,coin
<br />® MACKENZIE
<br />2020 ALL RIGHTS RESERVED
<br />THESE DRAWINGS ARE THE PROPERTY OF
<br />MACKENZIE AND ARE NOT TO BE USED
<br />OR REPRODUCED IN ANY MANNER,
<br />WITHOUT PRIOR WRITTEN PERMISSION
<br />Revision Schedule
<br />Revision Delta I Issue Date
<br />E1.2.2
<br />SPECIALTY LIGHTING PLAN - PRODUCE, HSW AND DETAILS
<br />E1.3.1
<br />POWER PLAN - AREA 1
<br />DRAWN BY: ZES
<br />E1.3.2
<br />POWER PLAN - AREA 2
<br />E1.3.3
<br />POWER PLAN - AREA 3
<br />CHECKED BY: KSL
<br />E 1.3.4
<br />POWER PLAN - AREA 4
<br />E1.3.5
<br />POWER PLAN - AREA 5
<br />E1.3.6
<br />POWER PLAN - AREA 6
<br />SHEET
<br />E1.3.7
<br />POWER PLAN - AREA 7
<br />E1.3.8
<br />POWER PLAN -AREA 8 AND DETAILS
<br />E1.3.1.1
<br />REFRIGERATION POWER PLAN
<br />E1.3.1.2
<br />REFRIGERATION DEFROST PLAN
<br />EOw 1
<br />E1.5
<br />ELECTRICAL DIMENSION PLANS
<br />E4.1
<br />ENLARGED POWER PLAN - BAKERY, DELI AND EQUIPMENT SCHEDULE
<br />E5.1
<br />ELECTRICAL STANDARD DETAILS
<br />E6.2.1.1
<br />PANEL SCHEDULES
<br />E6.2,1.2
<br />PANEL SCHEDULES
<br />F1.2
<br />FIRE ALARM PLAN
<br />JOB NO
<br />
|