Laserfiche WebLink
A 1 b 1 G I U <br />t I r <br />COMBINER BOX PANEL SIZE CALCS <br />CIRCUIT # <br />NUMBER OF <br />MODULES <br />NUMBER OF <br />MICROINVERTERS <br />NOMINAL OUTPUT <br />CURRENT <br />TOTAL <br />125 % <br />TOTAL <br />COMBINED <br />TOTAL <br />BREAKER SIZE <br />CIRCUIT 1 1 of 2 <br />1 <br />1.23A <br />= 123A <br />1.25 <br />= 1,54A- <br />- 14.04A <br />= 15A <br />CIRCUIT 1 2 of 2 <br />8 <br />2 <br />5.OA <br />- 10.00A <br />x 1.25 <br />= 12.50A <br />CIRCUIT 2 (1 of 3) <br />1 <br />1 <br />X 1.23A <br />- 1.23A <br />1.25 <br />= 1.54A <br />= 10.86A <br />= 15A <br />CIRCUIT 2 (2 of 3) <br />2 <br />1 <br />X 2.46A <br />- 2.46A <br />x 1.25 <br />= 3.08A <br />CIRCUIT 2 (3 of 3)1 <br />4 <br />1 <br />5.OA <br />- 5.00A <br />x 1.25 <br />= 6.25A <br />LOAD CALCS - TOTAL AMPS AVAILABLE <br />BUS RATING 120% TOTAL MAIN BREAKER MAX BREAKER SIZE <br />200A X 1.2 - 240 200A - 40A <br />NOTES: <br />1. 200A UTILITY METER GLOBE ONLY. (EXISTING) <br />2. 200A LOAD CENTER. (EXISTING) <br />3. 30A RATED NON -FUSED LOCKABLE AC DISCONNECT. <br />(NEW) <br />4. 125A RATED COMBINER PANEL. (NEW) <br />v ALL CONDUIT SIZES ARE MINIMUM SIZES <br />ALL WIRE SIZES ARE FOR COPPER WIRE <br />0� <br />Am <br />2 SUNTECH STP370S-B60/WNHB MODULES 2 SUNTECH STP370S-B601WNHB MODULES <br />WITH HOYMILES HM-300 MICRO WITH HOYMILES HM-600 MICRO <br />INVERTERS INVERTERS <br />(1 OF 3) (2 OF 3) <br />(2, • • • (11 (2) (11 <br />2 SUNTECH STP370S-B60/WNHB MODULES 2 SUNTECH STP370S-B601WNHB MODULES <br />WITH HOYMILES HM-300 MICRO WITH HOYMILES HM-600 MICRO <br />INVERTERS INVERTERS <br />(1 OF 3) (2 OF 3) <br />(21 • • • (1) (21 (11 <br />4 SUNTECH STP370S-B60/WNHB MODULES <br />WITH HOYMILES HM-1200 MICRO <br />INVERTERS <br />(3 OF 3) <br />(4 <br />(3) (2) <br />(1) �CIRCUIT#1 <br />4 SUNTECH STP370S-B60/WNHB MODULES <br />WITH HOYMILES HM-1200 MICRO <br />INVERTERS <br />CIRCUIT #2 <br />CONFIDENTIAL - THE INFORMATION CONTAINEI <br />IN THIS PACKET AND SUBSEQUENT CUTSHEET: <br />S O L G � N SHALL NOT BE USED FOR THE BENEFIT OF <br />ANYONE OUTSIDE SOLGEN POWER. NEITHER <br />SHALL IT BE DISCLOSED TO OTHERS OUTSIDE <br />P 0 W E R THE RECIPIENT'S ORGANIZATION, EXCEPT IN <br />CONNECTION WITH THE SALE AND USE OF THE <br />RESPECTIVE EQUIPMENT, WITHOUT WRITTEN <br />CONSENT FROM SOLGEN POWER. <br />MAX AC OPERATING CURRENT CALCS FOR HM-1200 <br /># OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATIN <br />3 X 5.OA - 15.00F <br />MAX AC OPERATING CURRENT CALCS FOR HM-600 <br /># OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATIN <br />1 X 2.46A - 2.46A <br />MAX AC OPERATING CURRENT CALCS FOR HM-300 <br /># OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATIN <br />2 X 1.23A = 2.46A <br />MAX AC OPERATING TOTAL <br />CURRENT FOR HM-1200, 600, 300 <br />HM-1200 HM-600 HM-300 <br />15.00A + 2.46A + 2.46A = 19.92A <br />BREAKER SIZE CALCS <br />MAX AC OPERATING CURRENT <br />125% <br />TOTAL <br />BREAKER SIZE <br />19.92A <br />x <br />1.25 <br />x 24.90A <br />= 25A <br />(2)12 AWG <br />(1)8 AWG EGC <br />(2)12 AWG <br />(1)8 AWG EGC <br />rL <br />I <br />UTILITY METER (E) <br />TO UTILITY <br />1 M GRID (E) <br />(2)8 AWG Z <br />(1)8 AWG EGC TE <br />IN.AIN SERVICE PANEL (E) <br />(2)8 AWG 3 <br />(1)8 AWG EGC <br />4 q q 211A <br />MAIN SERVICE <br />DISCONNECT (E) <br />(2)8 AWG <br />s (1 )a AwG EGc 25ALOAD-SIDE <br />SOLAR OCPD <br />(Opposite end of the main disconnect <br />on the busbar- NEC705.12(B)(3) SLIM DOWN BREAKERS <br />TO ALLOW FOR SOLAR <br />BREAKER CONNECTION <br />DRAWN BY: DRAWING SCALE: <br />PJV NOT TO SCA <br />SOLGEN POWER Stephen E h re s m a n DATE: DESIGN <br />5100 ELM RD, 13/07/2022 A <br />PASCO, WA 99301 I <br />P:509-931-1663 2127 Oakes Ave, Everett, WA 98201 PAGE;` <br />mm <br />mm <br />�M <br />