I� <br />■ <br />u <br />■ <br />Lai <br />■ <br />rL <br />■ <br />COMBINER BOX PANEL SIZE CALCS <br />CIRCUIT# <br />NUMBER OF <br />MODULES <br />NUMBER OF <br />MICROINVERTERS <br />NOMINAL OUTPUT <br />CURRENT <br />TOTAL <br />125% <br />TOTAL <br />COMBINED <br />TOTAL <br />BREAKER SIZE <br />CIRCUIT 1 (1 of 3) <br />1 <br />1 <br />X 1.23A <br />= 1.23A <br />1.25 <br />= 1.54A <br />= 10.86A <br />= 15A <br />CIRCUIT 1 (2 of 3) <br />2 <br />1 <br />X 2.46A <br />= 2.46A <br />x 1.25 <br />= 3.08A <br />CIRCUIT 1 (3 of 3) <br />4 <br />1 <br />5.OA <br />- 5.00A <br />x 1.25 <br />= 6.25A <br />CIRCUIT 2 (1 of 2) <br />2 <br />1 <br />X 2.46A <br />= 2.46A <br />x 1.25 <br />= 3.08A <br />- 9.33A <br />= 15A <br />CIRCUIT 2 (2 of 2) <br />4 <br />1 <br />5.OA <br />- 5.00A <br />x 1.25 <br />= 6.25A <br />LOAD CALCS - TOTAL AMPS AVAILABLE <br />BUS RATING 120 % TOTAL MAIN BREAKER MAX BREAKER SIZE <br />125A X 1.2 = 150 125A = 25A <br />NOTES: <br />v 1. 200A UTILITY METER GLOBE ONLY. (EXISTING) <br />2. 125A LOAD CENTER. (EXISTING) <br />3. 30A RATED NON -FUSED LOCKABLE AC DISCONNECT. <br />(NEW) <br />4. 125A RATED COMBINER PANEL. (NEW) <br />ALL CONDUIT SIZES ARE MINIMUM SIZES <br />ALL WIRE SIZES ARE FOR COPPER WIRE <br />1 ZNSHINE ZXM6-NH120-360M MODULE <br />WITH HOYMILES HM-300 MICRO <br />INVERTER <br />(1 OF 3) <br />7 <br />Am <br />2 ZNSHINE ZXM6-NH120-360M MOD14LIMHINE ZXM6-NH120-360M MODULES <br />WITH HOYMILES HM-600 MICRO WITH HOYMILES HM-1200 MICRO <br />INVERTERS INVERTERS <br />(2 OF 3) (3 OF 3) <br />(✓) (1 (4) (3) (2) (1 CIRCUIT #1 <br />2 ZNSHINE ZXM6-NH120-360M MODULE43ZNSHINE ZXM6-NH120-360M MODULES <br />WITH HOYMILES HM-600 MICRO WITH HOYMILES HM-1200 MICRO <br />INVERTERS INVERTERS <br />(1 OF 2) (2 OF 2) <br />(2) (J-) (4) (3) (J) CIRCUIT#2 <br />CONFIDENTIAL - THE INFORMATION CONTAINEI <br />IN THIS PACKET AND SUBSEQUENT CUTSHEET: <br />S O L G � N <br />SHALL NOT BE USED FOR THE BENEFIT OF <br />ANYONE OUTSIDE SOLGEN POWER. NEITHER <br />SHALL IT BE DISCLOSED TO OTHERS OUTSIDE <br />P O W E R THE RECIPIENT'S ORGANIZATION, EXCEPT IN <br />CONNECTION WITH THE SALE AND USE OF THE <br />RESPECTIVE EQUIPMENT, WITHOUT WRITTEN <br />CONSENT FROM SOLGEN POWER. <br />t I r I <br />MAX AC OPERATING CURRENT CALCS FOR HM-1200 <br /># OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT <br />2 X 5.OA = 10.00A <br />MAX AC OPERATING CURRENT CALCS FOR HM-600 <br /># OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT <br />2 X 2.46A = 4.92A <br />MAX AC OPERATING CURRENT CALCS FOR HM-300 <br /># OF MICROINVERTERS <br />MAX OUTPUT CURRENT MAX AC OPERATING CURRENT <br />1 X 1.23A = 1.23A <br />MAX AC OPERATING <br />CURRENT FOR HM-1200, 600, 300 <br />TOTAL <br />HM-1200 <br />HM-600 <br />HM-300 <br />= 16.15A <br />10.00A <br />+ 4.92A <br />+ 1.23A <br />BREAKER SIZE CALCS <br />MAX AC OPERATING CURRENT <br />125 % <br />TOTAL <br />BREAKER SIZE <br />16.15A <br />x <br />1.25 <br />x 20.19A <br />= 25A <br />(2)8 AWG <br />(1)8 AWG EGC / 2 <br />3 <br />UTILITY METER (E) N <br />1'� TO UTILITY <br />GRID (E) <br />4 I I 125A <br />MAIN SERVICE <br />DISCONNECT (E) <br />(2)8 AWG <br />(1)8 AWG EGC <br />(2)12 AWG <br />(1 )8 AWG EGC <br />(2)12 AWG <br />(1 )8 AWG EGC <br />25A LOAD -SIDE <br />SOLAR OCPD <br />(Opposite end of the main disconnect <br />on the busbar - NEC 705.12(B)(3) <br />EXISTING <br />WIRE <br />SERVICE PANEL (E) <br />DRAWN BY: DRAWING SCALE: <br />Edward Amato EAc NOT TOSCA <br />DATE: DESIGN <br />SOLGEN POWER <br />5100 ELM RD, 26/01 /2023 A <br />PASCO, WA 99301 I <br />P:509-931-1663 1702 Colby Ave Everett WA 98201 PA` , <br />MM <br />MO <br />�M <br />