M - VERTICAL AHUS
<br />GENERAL NOTES:
<br />1. ALL UNITS TO HAVE EC MOTORS
<br />SPECIFIC NOTES:
<br />1. PROVIDE WITH FACTORY INSTALLED INTEGRAL DISCONNECT SWITCH
<br />2, SCCR OF 5KA
<br />3. PROVIDE WITH 0-10VDC SPEED CONTROL
<br />4. PROVIDE CUSTOM MIXING BOX PER DETAILS ON SHEET M-500
<br />5. PROVIDE WITH FILTER BOX WITH 2" PLEATEC MERV 13 FILTERS
<br />DESCRIPTION
<br />PHYSICAL DIMENSIONS
<br />SUPPLY FAN
<br />HEATING COIL
<br />ELECTRICAL
<br />EQUIPMENT
<br />CLASSIFICATION
<br />EQUIPMENT ID
<br />LOCATION
<br />AREA/SYSTEM
<br />SERVED
<br />MANUFACTURER
<br />MODEL
<br />EQUIPMENT
<br />TYPE
<br />HEIGHTx WIDTHX
<br />DEPTH
<br />(IN)
<br />OPERATING
<br />WEIGHT
<br />(LBS)
<br />CAPACITY
<br />(MBH)
<br />AIRFLOW
<br />(CFM)
<br />OUTDOOR AIR
<br />FLOW
<br />(CFM)
<br />TOTAL STATIC
<br />PRESSURE
<br />(IN. WC)
<br />EXTERNAL STATIC
<br />PRESSURE
<br />(IN. WG)
<br />SPEEDCONTROL
<br />MOTORTYPE
<br />DRIVE TYPE
<br />FAN SPEED
<br />(RPM)
<br />BRAKE
<br />HORSEPOWER
<br />(BHP)
<br />MOTOR
<br />HORSEPOWER
<br />(HP)
<br />ENTERING AIR
<br />TEMPERATURE
<br />(°F)
<br />LEAVING AIR
<br />TEMPERATURE
<br />(°p)
<br />FLUID FLOW
<br />(GPM)
<br />EWF
<br />(°F)
<br />LWF
<br />(°F)
<br />FLUID PRESSURE
<br />DROP
<br />F WG)
<br />CAPACITY
<br />(BTUH)
<br />VOLTAGE
<br />M
<br />PHASE
<br />(0)
<br />DISCONNECT
<br />PROVIDED BY
<br />FULL LOAD
<br />AMPS
<br />(A)
<br />MOCP
<br />MINIMUM CIRCUIT
<br />AMPACITY
<br />(A)
<br />SPECIFIC
<br />NOTES
<br />AHU
<br />B1
<br />ROOM B-22
<br />BUILDING B
<br />MAGIC AIRE
<br />NOB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />B2
<br />ROOM B-23
<br />BUILDING B
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />tot
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3,4 5
<br />AHU
<br />52-1
<br />ROOM B-101
<br />BUILDING B
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />5m
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1A33
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />B2-2
<br />ROOM B-105
<br />BUILDING B
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />C11
<br />ROOM C-03
<br />BUILDING C
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />60
<br />1200
<br />500
<br />1.657
<br />0.51
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1141
<br />1.125
<br />3/4
<br />56
<br />106
<br />5.2
<br />140
<br />115
<br />1.605
<br />63839
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />C2
<br />ROOM C-04
<br />BUILDING C
<br />MAGICAIRE
<br />NDB-16
<br />FCU
<br />58 x 25 x 24
<br />300
<br />70
<br />1800
<br />500
<br />1.917
<br />0.8
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />2925
<br />0.997
<br />1.5
<br />60
<br />99
<br />4.5
<br />140
<br />106
<br />0.905
<br />77025
<br />208
<br />1
<br />MANUFACTURER
<br />6.9
<br />15
<br />8.6
<br />1, 2,3 4, 5
<br />AHU
<br />Di
<br />ROOM D-30
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2
<br />ROOM D-28
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />11D0
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D3
<br />ROOM D-26
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />111)0
<br />5m
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />T4
<br />56
<br />t01
<br />3.2
<br />140
<br />106
<br />0.694
<br />50
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D4
<br />ROOM D-24
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D5
<br />ROOM D-22
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />IDS
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D6
<br />ROOM D-16
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D7
<br />ROOM D-07
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />11 W
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1,133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2,3 4, 5
<br />AHU
<br />D8
<br />ROOM D-05
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D9
<br />ROOM D-03
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D10
<br />ROOM D-01
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />11 W
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54399
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D11
<br />ROOM D-18
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2,3 4, 5
<br />AHU
<br />D12
<br />ROOM D-20
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />IDS
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D13
<br />ROOM D-12
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-16
<br />FCU
<br />58 x 25 x 24
<br />300
<br />70
<br />1470
<br />4W
<br />1.606
<br />0.8
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />2547
<br />0.672
<br />1.5
<br />60
<br />108
<br />5.0
<br />140
<br />110
<br />1.077
<br />74237
<br />208
<br />1
<br />MANUFACTURER
<br />6.9
<br />15
<br />8.6
<br />1, 2, 3, 4, 5
<br />AHU
<br />D14
<br />ROOM D-35
<br />BUILDING
<br />MAGICAIRE
<br />NDB-16
<br />FCU
<br />58x25x24
<br />300
<br />70
<br />1470
<br />500
<br />1.606
<br />0.8
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />2547
<br />0.672
<br />1.5
<br />58
<br />106
<br />5.0
<br />140
<br />110
<br />1.077
<br />74237
<br />208
<br />1
<br />MANUFACTURER
<br />6.9
<br />15
<br />8.6
<br />1.2, 3,4,5
<br />AHU
<br />D2-1
<br />ROOM D-130
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />1.
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-2
<br />ROOM D-128
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />IDS
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-3
<br />ROOM D-126
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1,133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0,694
<br />W92
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-4
<br />ROOM D-124
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />Soo
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-5
<br />ROOM D-122
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-6
<br />ROOM D-116
<br />BUILDING D
<br />MAGIC AIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-7
<br />ROOM D-107
<br />BUILDING D
<br />MAGIC AIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />IWO
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1,133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0,694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-8
<br />ROOM D-105
<br />BUILDING D
<br />MAGIC AIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />IDS
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />32-9
<br />ROOM D-103
<br />BUILDING D
<br />MAGIC AIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-10
<br />ROOM D-101
<br />BUILDING D
<br />MAGIC AIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />1100
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-11
<br />ROOM D-118
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />40
<br />1100
<br />250
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />314
<br />61
<br />98
<br />3.2
<br />140
<br />IDS
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-12
<br />ROOM D-120
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-12
<br />FCU
<br />51 x 22 x 24
<br />191
<br />50
<br />110D
<br />500
<br />1.629
<br />0.63
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />1160
<br />1.133
<br />3/4
<br />56
<br />101
<br />3.2
<br />140
<br />106
<br />0.694
<br />54392
<br />208
<br />1
<br />MANUFACTURER
<br />6.8
<br />15
<br />8.5
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-13
<br />ROOM D-112
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-16
<br />FCU
<br />58 x 25 x 24
<br />300
<br />70
<br />1470
<br />400
<br />1.606
<br />0.8
<br />CONSTANT
<br />ECM
<br />DIRECT
<br />2547
<br />0.672
<br />1.5
<br />60
<br />108
<br />5.0
<br />140
<br />110
<br />1.077
<br />74237
<br />208
<br />1
<br />MANUFACTURER
<br />6.9
<br />15
<br />8.6
<br />1, 2, 3, 4, 5
<br />AHU
<br />D2-14
<br />ROOM D-135
<br />BUILDING D
<br />MAGICAIRE
<br />NDB-16
<br />FCU
<br />58 x 25 x 24
<br />300
<br />70
<br />1470
<br />500
<br />1.606
<br />0.8
<br />CONSTANT
<br />ECN
<br />DIRECT
<br />2547
<br />0.672
<br />1.5
<br />58
<br />106
<br />5.0
<br />140
<br />110
<br />1.077
<br />74237
<br />208
<br />1
<br />MANUFACTURER
<br />6.9
<br />15
<br />8.6
<br />1, 2, 3, 4, 5
<br />M - EXHAUST FAN SCHEDULE
<br />GENERAL NOTES:
<br />SPECIFIC NOTES:
<br />1. PROVIDE WITH STANDARD ONE YEAR WARRANTY.
<br />1. EXISTING STARTER TO BE REUSED OR REPLACED BY ELECTRICAL AS NEEDED.
<br />2. MANUFACTURER'S CERTIFICATE OF SEISMIC COMPLIANCE INCLUDED PER IBC 1708.4.
<br />2. FAN SPRING ISOLATION REQUIRED.
<br />3. DOCUMENTED FACTORY TESTING OF ALL UNITSAT DESIGN LOAD CONDITIONS.
<br />3. MANUFACTURER'S CERTIFCATE OF SEISMIC COMPLIANCE INCLUDED PER IBC 1708.4.
<br />DESCRIPTION
<br />PHYSICAL DIMENSIONS
<br />PERFORMANCE
<br />ELECTRICAL
<br />ACOUSTICAL
<br />OPERATING
<br />EXTERNAL STATIC
<br />FAN BRAKE
<br />MINIMUM CIRCUIT
<br />MAXIMUM
<br />SPECIFIC
<br />EQUIPMENT
<br />EQUIPMENT ID
<br />LOCATION
<br />AREAISYSTEM SERVED
<br />MANUFACTURER
<br />MODEL
<br />TYPE
<br />MOTOR TYPE
<br />DRIVE TYPE
<br />CONTROL TYPE
<br />LENGTH
<br />WIDTH
<br />HEIGHT
<br />WEIGHT
<br />AIRFLOW
<br />PRESSURE
<br />FAN SPEED
<br />HORSEPOWER
<br />FAN HORSEPOWER
<br />VOLTAGE
<br />PHASE
<br />MOTOR SPEED
<br />FLA
<br />gMpACITY
<br />OVERCURRENT
<br />SCCR
<br />SOUND POWER
<br />NOTES
<br />CLASSIFICATION
<br />(IN)
<br />(IN)
<br />(IN)
<br />(LBS)
<br />(CFM)
<br />(IN. W.C.)
<br />(RPM)
<br />(BHP)
<br />(HP)
<br />(V)
<br />(0)
<br />(RPM)
<br />(AMPS)
<br />(MCA)
<br />PROTECTION
<br />(MOP)
<br />(kA)
<br />(DB)
<br />EF
<br />B1
<br />BUILDING B
<br />NURSE'S OFFICE
<br />GREENHECK
<br />SQ-80-VG
<br />CENTRIFUGAL INLINE
<br />VARI-GREEN EC
<br />DIRECT
<br />CONTINUOUS
<br />15
<br />1 15
<br />19
<br />44
<br />210
<br />0.319
<br />1331
<br />0.03
<br />1/10
<br />115
<br />1
<br />1725
<br />1.38
<br />2
<br />15
<br />5
<br />51
<br />1,3
<br />EF
<br />B2
<br />BUILDING B
<br />RESTROOMS & JANITOR
<br />GREENHECK
<br />SQ-95-VG
<br />CENTRIFUGAL INLINE
<br />VARI-GREEN EC
<br />DIRECT
<br />CONTINUOUS
<br />15
<br />15
<br />19
<br />51
<br />560
<br />0.436
<br />1579
<br />0.1
<br />1/6
<br />115
<br />1
<br />1725
<br />2.3
<br />3
<br />15
<br />5
<br />57
<br />1,3
<br />EF
<br />Ci
<br />BUILDING C
<br />RESTROOMS & JANITOR
<br />GREENHECK
<br />SO-80-VG
<br />CENTRIFUGAL INLINE
<br />VARI-GREEN EC
<br />DIRECT
<br />CONTINUOUS
<br />26
<br />26
<br />29
<br />44
<br />300
<br />0.215
<br />1394
<br />0.03
<br />1/10
<br />115
<br />1
<br />1725
<br />1.38
<br />2
<br />15
<br />5
<br />52
<br />1,3
<br />EF
<br />DI
<br />BUILDINGD
<br />RESTROOMS & JANITOR
<br />GREENHECK
<br />SQ-160-VG
<br />CENTRIFUGAL INLINE
<br />VARI-GREEN EC
<br />DIRECT
<br />CONTINUOUS
<br />15
<br />15
<br />19
<br />174
<br />20DO
<br />0.48
<br />936
<br />0.31
<br />2
<br />208
<br />3
<br />1725
<br />&5
<br />8
<br />15
<br />5
<br />56
<br />1, 2, 3
<br />RE
<br />31
<br />BUILDING B
<br />OFFICE & COMMON AREAS
<br />I GREENHECK
<br />SQ-160-VG
<br />CENTRIFUGAL INLINE
<br />VARI-GREEN EC
<br />I DIRECT
<br />I INTERLOCKED WITH AHU-4
<br />26
<br />26
<br />29
<br />174
<br />3910
<br />0.994
<br />1611
<br />1 1.5
<br />1 2
<br />208
<br />T 3
<br />1725
<br />1 6.5
<br />8
<br />15
<br />5
<br />73
<br />1, 2, 3
<br />M - HOT WATER COIL SCHEDULE
<br />GENERAL NOTES:
<br />SPECIFIC NOTES:
<br />DESCRIPTION
<br />PHYSICAL DIMENSIONS
<br />HEATING COIL
<br />EQUIPMENT
<br />CLASSIFICATION
<br />EQUIPMENT ID
<br />LOCATION
<br />AREAI SYSTEM SERVED
<br />MANUFACTURER
<br />MODEL
<br />TYPE
<br />LENGTH
<br />(IN)
<br />WIDTH
<br />(IN)
<br />OPERATING
<br />WEIGHT
<br />(LBS)
<br />CAPACITY
<br />(MBH)
<br />SUPPLYAIR
<br />FLOW
<br />(CFM)
<br />CA AIR FLOW
<br />(CFM)
<br />FACE VELOCITY
<br />(FPM)
<br />EAT
<br />(°F DB)
<br />LAT
<br />(°F DB)
<br />MAX AIR PRESSURE
<br />DROP
<br />(IN. W.C.)
<br />FLUID
<br />VELOCITY
<br />(FPS)
<br />EWT
<br />(°F)
<br />LWT
<br />(°F)
<br />FLUID FLOW
<br />(GPM)
<br />MAX FLUID PRESSURE
<br />DROP
<br />(FT W.C.)
<br />COIL ROWS
<br />0)
<br />COIL FPI
<br />SPECIFIC
<br />NOTES
<br />HC
<br />B1
<br />BUILDING B
<br />I.M.C.
<br />RAE CORP
<br />58W24x36-7-3 F-Z-R
<br />INDOOR HORIZONTAL
<br />32
<br />16
<br />8
<br />117
<br />3,670
<br />642
<br />612
<br />62
<br />91
<br />0.18
<br />2.55
<br />140
<br />106
<br />7.00
<br />6.13
<br />3
<br />7
<br />HC
<br />B2
<br />BUILDING B
<br />WORK ROOM & JANITOR
<br />RAE CORP
<br />58W1544&3-W-E-R
<br />INDOOR HORIZONTAL
<br />16
<br />8
<br />8
<br />20
<br />550
<br />96
<br />587
<br />62
<br />96
<br />0.25
<br />1.49
<br />140
<br />110
<br />1.36
<br />1.52
<br />3
<br />8
<br />HC
<br />B3
<br />BUILDING B
<br />OFFICE & RESTROOMS
<br />RAE CORP
<br />58W12x10-73W-E-R
<br />INDOOR HORIZONTAL
<br />10
<br />8
<br />12
<br />14
<br />355
<br />62
<br />426
<br />62
<br />98
<br />0.14
<br />1.09
<br />140
<br />112
<br />1.00
<br />0.73
<br />3
<br />7
<br />HC
<br />B4
<br />BUILDING B
<br />ADMINISTRATION
<br />RAE CORP
<br />58W24xl6-9-3-W-J-R
<br />INDOOR HORIZONTAL
<br />26
<br />12
<br />8
<br />68
<br />1,905
<br />324
<br />714
<br />62
<br />95
<br />0.39
<br />2.19
<br />140
<br />105
<br />4.00
<br />3.62
<br />3
<br />9
<br />HC
<br />B5
<br />BUILDING B
<br />CONFERENCE
<br />RAE CORP
<br />5BW12x8-7-3-W-E-R
<br />INDOOR HORIZONTAL
<br />8
<br />6
<br />12
<br />11
<br />215
<br />37
<br />323
<br />62
<br />107
<br />0.09
<br />1.64
<br />140
<br />126
<br />1.50
<br />1.40
<br />3
<br />7
<br />HC
<br />B6
<br />BUILDING B
<br />CONFERENCE
<br />RAE CORP
<br />S8W12x8-7-3-W-E-R
<br />INDOOR HORIZONTAL
<br />8
<br />6
<br />12
<br />10
<br />230
<br />39
<br />345
<br />62
<br />101
<br />0.10
<br />0.93
<br />140
<br />117
<br />0.85
<br />0.51
<br />3
<br />7
<br />HC
<br />B7
<br />BUILDING B
<br />PRINCIPAL
<br />RAE CORP
<br />5BW15x8-8-3-W-E-R
<br />INDOOR HORIZONTAL
<br />14
<br />8
<br />11
<br />17
<br />445
<br />76
<br />534
<br />62
<br />96
<br />0.22
<br />1.22
<br />140
<br />110
<br />1.12
<br />1.03
<br />3
<br />8
<br />HC
<br />B8
<br />BUILDING B
<br />CONFERENCE
<br />RAE CORP
<br />58W15x848 3-W-E-R
<br />INDOOR HORIZONTAL
<br />14
<br />8
<br />12
<br />17
<br />445
<br />76
<br />534
<br />62
<br />96
<br />0.22
<br />140
<br />110
<br />1.12
<br />1.03
<br />3
<br />8
<br />HC
<br />B9
<br />BUILDING B
<br />SUPPLY
<br />RAE CORP
<br />58W12x10.8-3-W-E-R
<br />INDOOR HORIZONTAL
<br />12
<br />10
<br />12
<br />17
<br />470
<br />80
<br />564
<br />62
<br />96
<br />0.24
<br />140
<br />110
<br />1.16
<br />0.96
<br />3
<br />8
<br />HC
<br />B10
<br />BUILDING B
<br />WORK ROOM & RESTROOMS
<br />RAE CORP
<br />58W15x9-8-3-W-E-R
<br />INDOOR HORIZONTAL
<br />12
<br />10
<br />25
<br />20
<br />550
<br />94
<br />587
<br />62
<br />96
<br />0.25
<br />]2!.08!jj
<br />140
<br />110
<br />1.36
<br />1.52
<br />3
<br />8
<br />HC
<br />311
<br />BUILDING B
<br />HEALTH
<br />RAE CORP
<br />158W15x8.8-3-W-E-R
<br />INDOOR HORIZONTAL
<br />14
<br />8
<br />89
<br />19
<br />445
<br />90
<br />534
<br />62
<br />101
<br />0.22
<br />140
<br />120
<br />1.90
<br />2.63
<br />1 3
<br />8
<br />M - CONTROL VALVE SCHEDULE
<br />GENERAL NOTES:
<br />SPECIFIC NOTES:
<br />1. REDUCE VALVE SIZE AS NEEDED TO ACCOMODATE FLOW AND PRESSURE REQUIREMENTS.
<br />DESCRIPTION
<br />PHYSICAL DIMENSIONS
<br />VALVE
<br />SPRING
<br />PERFORMANCE
<br />EQUIPMENT
<br />CLASSIFICATION
<br />UNIT SERVED
<br />QUANTITY
<br />PIPE SIZE
<br />(IN)
<br />VALVE TYPE
<br />VALVE FUNCTION
<br />BODY RATING
<br />TRIM
<br />VALVE DESIGN
<br />SPRING RETURN TYPE
<br />TYPE
<br />FLOW
<br />(GPM)
<br />CV
<br />MODULATING/
<br />OPEN -CLOSE
<br />SPECIFIC
<br />NOTES
<br />CV
<br />BLDG B & D- CLASSROOM AHUS
<br />22
<br />314
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />3.20
<br />5.84
<br />MODULATING
<br />1
<br />CV
<br />BLDG B&D-AHU-D4,-D8,-D11,-B2-1
<br />4
<br />3/4
<br />CCV
<br />3-WAY
<br />NON ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />3.20
<br />5.84
<br />MODULATING
<br />1
<br />CV
<br />BLDG D-COMMON SPACE AHU-D13
<br />1
<br />718
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />5.20
<br />6.20
<br />MODULATING
<br />1
<br />CV
<br />BLDG D-COMMON SPACE AHU-1)I4, 132-13, -D2-14
<br />3
<br />7/8
<br />CCV
<br />8-WAY
<br />NON ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />5.20
<br />6.20
<br />MODULATING
<br />2
<br />CV
<br />BLDG C-CLASSROOM C 03 AHU
<br />1
<br />314
<br />CCV
<br />3-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />4.50
<br />7.19
<br />MODULATING
<br />2
<br />CV
<br />BLDG C -CLASSROOM C 04 AHU
<br />1
<br />7/8
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />5.00
<br />7.32
<br />MODULATING
<br />1
<br />CV
<br />BLDG B - HC-B1
<br />1
<br />1-1/4
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />5.75
<br />4.30
<br />MODULATING
<br />1
<br />CV
<br />BLDG B - HC-B2 & BC-B10
<br />2
<br />314
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />1.36
<br />1.68
<br />MODULATING
<br />1
<br />CV
<br />BLDG B- HC-B3
<br />1
<br />3/4
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />1.00
<br />1.78
<br />MODULATING
<br />1
<br />CV
<br />BLDG B- HC-B4
<br />1
<br />1
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />4.00
<br />3.19
<br />MODULATING
<br />1
<br />CV
<br />BLDG B - HC-B5
<br />1
<br />3/4
<br />CCV
<br />SWAY
<br />NONANSISTAINLESS
<br />STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />1.50
<br />1.93
<br />MODULATING
<br />1
<br />CV
<br />BLDG B- HG136
<br />1
<br />314
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />0.85
<br />1.81
<br />MODULATING
<br />1
<br />CV
<br />BLDG B -HC-B7 & HG-B8
<br />1
<br />314
<br />CCV
<br />2-WAY
<br />NON ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />1.12
<br />1.68
<br />MODULATING
<br />1
<br />CV
<br />BLDG B - HC-B9
<br />1
<br />34
<br />CCV
<br />2-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />1.36
<br />1.80
<br />MODULATING
<br />1
<br />CV
<br />BLDG B-HC-B11
<br />1
<br />314
<br />CCV
<br />3-WAY
<br />NON -ANSI
<br />STAINLESS STEEL
<br />BELIMO
<br />SPRING RETURN
<br />NORMALLY OPEN
<br />1 1.90
<br />1.78
<br />MODULATING
<br />1
<br />M - CEILING SUPPLY DIFFUSER SCHEDULE
<br />GENERAL NOTES:
<br />SPECIFIC NOTES:
<br />DESCRIPTION
<br />PHYSICAL DIMENSIONS
<br />PERFORMANCE
<br />ACOUSTICAL
<br />MAX AIR PRESSURE
<br />SPECIFIC
<br />EQUIPMENT
<br />EQUIPMENT
<br />QUANTITY
<br />MANUFACTURER
<br />MODEL
<br />TYPE
<br />MATERIAL
<br />NECK SIZE
<br />FAMILY SIZE
<br />MAX AIR FLOW
<br />DROP
<br />MAX THROW
<br />MOUNTING
<br />FINISH
<br />NO
<br />NOTES
<br />CLASSIFICATION
<br />ID
<br />(IN)
<br />(IN)
<br />(CFM)
<br />(IN. W.C.)
<br />(FT
<br />GIRD
<br />CD-1
<br />84
<br />TITUS
<br />MCDI
<br />MODULARCORE
<br />STEEL
<br />10
<br />24x24
<br />367
<br />0.05
<br />10.12-17
<br />T-BAR
<br />STANDARD
<br />18
<br />ai0 try
<br />fe Of Your Building
<br />McKINSTRY Co, LLC
<br />SEATTLE:
<br />5005 3RD AVENUE S
<br />PO BOX 24567
<br />SEATTLE, WA 98124
<br />1-800-669-6223
<br />www.mckinstrv.com
<br />PROJECT
<br />MUKILTEO SD
<br />PHASE 10 HVAC
<br />IMPROVEMENTS
<br />- HORIZON ES
<br />222 W CASINO RD
<br />EVERETT, WA 98204
<br />CONSULTANTS:
<br />ISSUE
<br />PERMIT SET
<br />05/06/2022
<br />REGISTRATION:
<br />�R oF�WAI yT��
<br />52771 Q
<br />P01 �4'GISTS
<br />G
<br />`rS10NAL
<br />ISSUES
<br />SR ENGINEER:
<br />L. HESS
<br />DRAWN BY:
<br />M. SAFONOV N. HOBURG A. PASSAS
<br />QC BY:
<br />L. HESS
<br />JOB NO:
<br />205557,004
<br />ISSUED ON:
<br />0510612022
<br />SHEET TITLE:
<br />MECHANICAL
<br />SCHEDULES
<br />SHEET NUMBER:
<br />M-060
<br />
|