Laserfiche WebLink
M - VERTICAL AHUS <br />GENERAL NOTES: <br />1. ALL UNITS TO HAVE EC MOTORS <br />SPECIFIC NOTES: <br />1. PROVIDE WITH FACTORY INSTALLED INTEGRAL DISCONNECT SWITCH <br />2, SCCR OF 5KA <br />3. PROVIDE WITH 0-10VDC SPEED CONTROL <br />4. PROVIDE CUSTOM MIXING BOX PER DETAILS ON SHEET M-500 <br />5. PROVIDE WITH FILTER BOX WITH 2" PLEATEC MERV 13 FILTERS <br />DESCRIPTION <br />PHYSICAL DIMENSIONS <br />SUPPLY FAN <br />HEATING COIL <br />ELECTRICAL <br />EQUIPMENT <br />CLASSIFICATION <br />EQUIPMENT ID <br />LOCATION <br />AREA/SYSTEM <br />SERVED <br />MANUFACTURER <br />MODEL <br />EQUIPMENT <br />TYPE <br />HEIGHTx WIDTHX <br />DEPTH <br />(IN) <br />OPERATING <br />WEIGHT <br />(LBS) <br />CAPACITY <br />(MBH) <br />AIRFLOW <br />(CFM) <br />OUTDOOR AIR <br />FLOW <br />(CFM) <br />TOTAL STATIC <br />PRESSURE <br />(IN. WC) <br />EXTERNAL STATIC <br />PRESSURE <br />(IN. WG) <br />SPEEDCONTROL <br />MOTORTYPE <br />DRIVE TYPE <br />FAN SPEED <br />(RPM) <br />BRAKE <br />HORSEPOWER <br />(BHP) <br />MOTOR <br />HORSEPOWER <br />(HP) <br />ENTERING AIR <br />TEMPERATURE <br />(°F) <br />LEAVING AIR <br />TEMPERATURE <br />(°p) <br />FLUID FLOW <br />(GPM) <br />EWF <br />(°F) <br />LWF <br />(°F) <br />FLUID PRESSURE <br />DROP <br />F WG) <br />CAPACITY <br />(BTUH) <br />VOLTAGE <br />M <br />PHASE <br />(0) <br />DISCONNECT <br />PROVIDED BY <br />FULL LOAD <br />AMPS <br />(A) <br />MOCP <br />MINIMUM CIRCUIT <br />AMPACITY <br />(A) <br />SPECIFIC <br />NOTES <br />AHU <br />B1 <br />ROOM B-22 <br />BUILDING B <br />MAGIC AIRE <br />NOB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />B2 <br />ROOM B-23 <br />BUILDING B <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />tot <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3,4 5 <br />AHU <br />52-1 <br />ROOM B-101 <br />BUILDING B <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />5m <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1A33 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />B2-2 <br />ROOM B-105 <br />BUILDING B <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />C11 <br />ROOM C-03 <br />BUILDING C <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />60 <br />1200 <br />500 <br />1.657 <br />0.51 <br />CONSTANT <br />ECM <br />DIRECT <br />1141 <br />1.125 <br />3/4 <br />56 <br />106 <br />5.2 <br />140 <br />115 <br />1.605 <br />63839 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />C2 <br />ROOM C-04 <br />BUILDING C <br />MAGICAIRE <br />NDB-16 <br />FCU <br />58 x 25 x 24 <br />300 <br />70 <br />1800 <br />500 <br />1.917 <br />0.8 <br />CONSTANT <br />ECM <br />DIRECT <br />2925 <br />0.997 <br />1.5 <br />60 <br />99 <br />4.5 <br />140 <br />106 <br />0.905 <br />77025 <br />208 <br />1 <br />MANUFACTURER <br />6.9 <br />15 <br />8.6 <br />1, 2,3 4, 5 <br />AHU <br />Di <br />ROOM D-30 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2 <br />ROOM D-28 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />11D0 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D3 <br />ROOM D-26 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />111)0 <br />5m <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />T4 <br />56 <br />t01 <br />3.2 <br />140 <br />106 <br />0.694 <br />50 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D4 <br />ROOM D-24 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D5 <br />ROOM D-22 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />IDS <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D6 <br />ROOM D-16 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D7 <br />ROOM D-07 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />11 W <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1,133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2,3 4, 5 <br />AHU <br />D8 <br />ROOM D-05 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D9 <br />ROOM D-03 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D10 <br />ROOM D-01 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />11 W <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54399 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D11 <br />ROOM D-18 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2,3 4, 5 <br />AHU <br />D12 <br />ROOM D-20 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />IDS <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D13 <br />ROOM D-12 <br />BUILDING D <br />MAGICAIRE <br />NDB-16 <br />FCU <br />58 x 25 x 24 <br />300 <br />70 <br />1470 <br />4W <br />1.606 <br />0.8 <br />CONSTANT <br />ECM <br />DIRECT <br />2547 <br />0.672 <br />1.5 <br />60 <br />108 <br />5.0 <br />140 <br />110 <br />1.077 <br />74237 <br />208 <br />1 <br />MANUFACTURER <br />6.9 <br />15 <br />8.6 <br />1, 2, 3, 4, 5 <br />AHU <br />D14 <br />ROOM D-35 <br />BUILDING <br />MAGICAIRE <br />NDB-16 <br />FCU <br />58x25x24 <br />300 <br />70 <br />1470 <br />500 <br />1.606 <br />0.8 <br />CONSTANT <br />ECM <br />DIRECT <br />2547 <br />0.672 <br />1.5 <br />58 <br />106 <br />5.0 <br />140 <br />110 <br />1.077 <br />74237 <br />208 <br />1 <br />MANUFACTURER <br />6.9 <br />15 <br />8.6 <br />1.2, 3,4,5 <br />AHU <br />D2-1 <br />ROOM D-130 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />1. <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-2 <br />ROOM D-128 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />IDS <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-3 <br />ROOM D-126 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1,133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0,694 <br />W92 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-4 <br />ROOM D-124 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />Soo <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-5 <br />ROOM D-122 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-6 <br />ROOM D-116 <br />BUILDING D <br />MAGIC AIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-7 <br />ROOM D-107 <br />BUILDING D <br />MAGIC AIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />IWO <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1,133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0,694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-8 <br />ROOM D-105 <br />BUILDING D <br />MAGIC AIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />IDS <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />32-9 <br />ROOM D-103 <br />BUILDING D <br />MAGIC AIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-10 <br />ROOM D-101 <br />BUILDING D <br />MAGIC AIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />1100 <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-11 <br />ROOM D-118 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />40 <br />1100 <br />250 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />314 <br />61 <br />98 <br />3.2 <br />140 <br />IDS <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-12 <br />ROOM D-120 <br />BUILDING D <br />MAGICAIRE <br />NDB-12 <br />FCU <br />51 x 22 x 24 <br />191 <br />50 <br />110D <br />500 <br />1.629 <br />0.63 <br />CONSTANT <br />ECM <br />DIRECT <br />1160 <br />1.133 <br />3/4 <br />56 <br />101 <br />3.2 <br />140 <br />106 <br />0.694 <br />54392 <br />208 <br />1 <br />MANUFACTURER <br />6.8 <br />15 <br />8.5 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-13 <br />ROOM D-112 <br />BUILDING D <br />MAGICAIRE <br />NDB-16 <br />FCU <br />58 x 25 x 24 <br />300 <br />70 <br />1470 <br />400 <br />1.606 <br />0.8 <br />CONSTANT <br />ECM <br />DIRECT <br />2547 <br />0.672 <br />1.5 <br />60 <br />108 <br />5.0 <br />140 <br />110 <br />1.077 <br />74237 <br />208 <br />1 <br />MANUFACTURER <br />6.9 <br />15 <br />8.6 <br />1, 2, 3, 4, 5 <br />AHU <br />D2-14 <br />ROOM D-135 <br />BUILDING D <br />MAGICAIRE <br />NDB-16 <br />FCU <br />58 x 25 x 24 <br />300 <br />70 <br />1470 <br />500 <br />1.606 <br />0.8 <br />CONSTANT <br />ECN <br />DIRECT <br />2547 <br />0.672 <br />1.5 <br />58 <br />106 <br />5.0 <br />140 <br />110 <br />1.077 <br />74237 <br />208 <br />1 <br />MANUFACTURER <br />6.9 <br />15 <br />8.6 <br />1, 2, 3, 4, 5 <br />M - EXHAUST FAN SCHEDULE <br />GENERAL NOTES: <br />SPECIFIC NOTES: <br />1. PROVIDE WITH STANDARD ONE YEAR WARRANTY. <br />1. EXISTING STARTER TO BE REUSED OR REPLACED BY ELECTRICAL AS NEEDED. <br />2. MANUFACTURER'S CERTIFICATE OF SEISMIC COMPLIANCE INCLUDED PER IBC 1708.4. <br />2. FAN SPRING ISOLATION REQUIRED. <br />3. DOCUMENTED FACTORY TESTING OF ALL UNITSAT DESIGN LOAD CONDITIONS. <br />3. MANUFACTURER'S CERTIFCATE OF SEISMIC COMPLIANCE INCLUDED PER IBC 1708.4. <br />DESCRIPTION <br />PHYSICAL DIMENSIONS <br />PERFORMANCE <br />ELECTRICAL <br />ACOUSTICAL <br />OPERATING <br />EXTERNAL STATIC <br />FAN BRAKE <br />MINIMUM CIRCUIT <br />MAXIMUM <br />SPECIFIC <br />EQUIPMENT <br />EQUIPMENT ID <br />LOCATION <br />AREAISYSTEM SERVED <br />MANUFACTURER <br />MODEL <br />TYPE <br />MOTOR TYPE <br />DRIVE TYPE <br />CONTROL TYPE <br />LENGTH <br />WIDTH <br />HEIGHT <br />WEIGHT <br />AIRFLOW <br />PRESSURE <br />FAN SPEED <br />HORSEPOWER <br />FAN HORSEPOWER <br />VOLTAGE <br />PHASE <br />MOTOR SPEED <br />FLA <br />gMpACITY <br />OVERCURRENT <br />SCCR <br />SOUND POWER <br />NOTES <br />CLASSIFICATION <br />(IN) <br />(IN) <br />(IN) <br />(LBS) <br />(CFM) <br />(IN. W.C.) <br />(RPM) <br />(BHP) <br />(HP) <br />(V) <br />(0) <br />(RPM) <br />(AMPS) <br />(MCA) <br />PROTECTION <br />(MOP) <br />(kA) <br />(DB) <br />EF <br />B1 <br />BUILDING B <br />NURSE'S OFFICE <br />GREENHECK <br />SQ-80-VG <br />CENTRIFUGAL INLINE <br />VARI-GREEN EC <br />DIRECT <br />CONTINUOUS <br />15 <br />1 15 <br />19 <br />44 <br />210 <br />0.319 <br />1331 <br />0.03 <br />1/10 <br />115 <br />1 <br />1725 <br />1.38 <br />2 <br />15 <br />5 <br />51 <br />1,3 <br />EF <br />B2 <br />BUILDING B <br />RESTROOMS & JANITOR <br />GREENHECK <br />SQ-95-VG <br />CENTRIFUGAL INLINE <br />VARI-GREEN EC <br />DIRECT <br />CONTINUOUS <br />15 <br />15 <br />19 <br />51 <br />560 <br />0.436 <br />1579 <br />0.1 <br />1/6 <br />115 <br />1 <br />1725 <br />2.3 <br />3 <br />15 <br />5 <br />57 <br />1,3 <br />EF <br />Ci <br />BUILDING C <br />RESTROOMS & JANITOR <br />GREENHECK <br />SO-80-VG <br />CENTRIFUGAL INLINE <br />VARI-GREEN EC <br />DIRECT <br />CONTINUOUS <br />26 <br />26 <br />29 <br />44 <br />300 <br />0.215 <br />1394 <br />0.03 <br />1/10 <br />115 <br />1 <br />1725 <br />1.38 <br />2 <br />15 <br />5 <br />52 <br />1,3 <br />EF <br />DI <br />BUILDINGD <br />RESTROOMS & JANITOR <br />GREENHECK <br />SQ-160-VG <br />CENTRIFUGAL INLINE <br />VARI-GREEN EC <br />DIRECT <br />CONTINUOUS <br />15 <br />15 <br />19 <br />174 <br />20DO <br />0.48 <br />936 <br />0.31 <br />2 <br />208 <br />3 <br />1725 <br />&5 <br />8 <br />15 <br />5 <br />56 <br />1, 2, 3 <br />RE <br />31 <br />BUILDING B <br />OFFICE & COMMON AREAS <br />I GREENHECK <br />SQ-160-VG <br />CENTRIFUGAL INLINE <br />VARI-GREEN EC <br />I DIRECT <br />I INTERLOCKED WITH AHU-4 <br />26 <br />26 <br />29 <br />174 <br />3910 <br />0.994 <br />1611 <br />1 1.5 <br />1 2 <br />208 <br />T 3 <br />1725 <br />1 6.5 <br />8 <br />15 <br />5 <br />73 <br />1, 2, 3 <br />M - HOT WATER COIL SCHEDULE <br />GENERAL NOTES: <br />SPECIFIC NOTES: <br />DESCRIPTION <br />PHYSICAL DIMENSIONS <br />HEATING COIL <br />EQUIPMENT <br />CLASSIFICATION <br />EQUIPMENT ID <br />LOCATION <br />AREAI SYSTEM SERVED <br />MANUFACTURER <br />MODEL <br />TYPE <br />LENGTH <br />(IN) <br />WIDTH <br />(IN) <br />OPERATING <br />WEIGHT <br />(LBS) <br />CAPACITY <br />(MBH) <br />SUPPLYAIR <br />FLOW <br />(CFM) <br />CA AIR FLOW <br />(CFM) <br />FACE VELOCITY <br />(FPM) <br />EAT <br />(°F DB) <br />LAT <br />(°F DB) <br />MAX AIR PRESSURE <br />DROP <br />(IN. W.C.) <br />FLUID <br />VELOCITY <br />(FPS) <br />EWT <br />(°F) <br />LWT <br />(°F) <br />FLUID FLOW <br />(GPM) <br />MAX FLUID PRESSURE <br />DROP <br />(FT W.C.) <br />COIL ROWS <br />0) <br />COIL FPI <br />SPECIFIC <br />NOTES <br />HC <br />B1 <br />BUILDING B <br />I.M.C. <br />RAE CORP <br />58W24x36-7-3 F-Z-R <br />INDOOR HORIZONTAL <br />32 <br />16 <br />8 <br />117 <br />3,670 <br />642 <br />612 <br />62 <br />91 <br />0.18 <br />2.55 <br />140 <br />106 <br />7.00 <br />6.13 <br />3 <br />7 <br />HC <br />B2 <br />BUILDING B <br />WORK ROOM & JANITOR <br />RAE CORP <br />58W1544&3-W-E-R <br />INDOOR HORIZONTAL <br />16 <br />8 <br />8 <br />20 <br />550 <br />96 <br />587 <br />62 <br />96 <br />0.25 <br />1.49 <br />140 <br />110 <br />1.36 <br />1.52 <br />3 <br />8 <br />HC <br />B3 <br />BUILDING B <br />OFFICE & RESTROOMS <br />RAE CORP <br />58W12x10-73W-E-R <br />INDOOR HORIZONTAL <br />10 <br />8 <br />12 <br />14 <br />355 <br />62 <br />426 <br />62 <br />98 <br />0.14 <br />1.09 <br />140 <br />112 <br />1.00 <br />0.73 <br />3 <br />7 <br />HC <br />B4 <br />BUILDING B <br />ADMINISTRATION <br />RAE CORP <br />58W24xl6-9-3-W-J-R <br />INDOOR HORIZONTAL <br />26 <br />12 <br />8 <br />68 <br />1,905 <br />324 <br />714 <br />62 <br />95 <br />0.39 <br />2.19 <br />140 <br />105 <br />4.00 <br />3.62 <br />3 <br />9 <br />HC <br />B5 <br />BUILDING B <br />CONFERENCE <br />RAE CORP <br />5BW12x8-7-3-W-E-R <br />INDOOR HORIZONTAL <br />8 <br />6 <br />12 <br />11 <br />215 <br />37 <br />323 <br />62 <br />107 <br />0.09 <br />1.64 <br />140 <br />126 <br />1.50 <br />1.40 <br />3 <br />7 <br />HC <br />B6 <br />BUILDING B <br />CONFERENCE <br />RAE CORP <br />S8W12x8-7-3-W-E-R <br />INDOOR HORIZONTAL <br />8 <br />6 <br />12 <br />10 <br />230 <br />39 <br />345 <br />62 <br />101 <br />0.10 <br />0.93 <br />140 <br />117 <br />0.85 <br />0.51 <br />3 <br />7 <br />HC <br />B7 <br />BUILDING B <br />PRINCIPAL <br />RAE CORP <br />5BW15x8-8-3-W-E-R <br />INDOOR HORIZONTAL <br />14 <br />8 <br />11 <br />17 <br />445 <br />76 <br />534 <br />62 <br />96 <br />0.22 <br />1.22 <br />140 <br />110 <br />1.12 <br />1.03 <br />3 <br />8 <br />HC <br />B8 <br />BUILDING B <br />CONFERENCE <br />RAE CORP <br />58W15x848 3-W-E-R <br />INDOOR HORIZONTAL <br />14 <br />8 <br />12 <br />17 <br />445 <br />76 <br />534 <br />62 <br />96 <br />0.22 <br />140 <br />110 <br />1.12 <br />1.03 <br />3 <br />8 <br />HC <br />B9 <br />BUILDING B <br />SUPPLY <br />RAE CORP <br />58W12x10.8-3-W-E-R <br />INDOOR HORIZONTAL <br />12 <br />10 <br />12 <br />17 <br />470 <br />80 <br />564 <br />62 <br />96 <br />0.24 <br />140 <br />110 <br />1.16 <br />0.96 <br />3 <br />8 <br />HC <br />B10 <br />BUILDING B <br />WORK ROOM & RESTROOMS <br />RAE CORP <br />58W15x9-8-3-W-E-R <br />INDOOR HORIZONTAL <br />12 <br />10 <br />25 <br />20 <br />550 <br />94 <br />587 <br />62 <br />96 <br />0.25 <br />]2!.08!jj <br />140 <br />110 <br />1.36 <br />1.52 <br />3 <br />8 <br />HC <br />311 <br />BUILDING B <br />HEALTH <br />RAE CORP <br />158W15x8.8-3-W-E-R <br />INDOOR HORIZONTAL <br />14 <br />8 <br />89 <br />19 <br />445 <br />90 <br />534 <br />62 <br />101 <br />0.22 <br />140 <br />120 <br />1.90 <br />2.63 <br />1 3 <br />8 <br />M - CONTROL VALVE SCHEDULE <br />GENERAL NOTES: <br />SPECIFIC NOTES: <br />1. REDUCE VALVE SIZE AS NEEDED TO ACCOMODATE FLOW AND PRESSURE REQUIREMENTS. <br />DESCRIPTION <br />PHYSICAL DIMENSIONS <br />VALVE <br />SPRING <br />PERFORMANCE <br />EQUIPMENT <br />CLASSIFICATION <br />UNIT SERVED <br />QUANTITY <br />PIPE SIZE <br />(IN) <br />VALVE TYPE <br />VALVE FUNCTION <br />BODY RATING <br />TRIM <br />VALVE DESIGN <br />SPRING RETURN TYPE <br />TYPE <br />FLOW <br />(GPM) <br />CV <br />MODULATING/ <br />OPEN -CLOSE <br />SPECIFIC <br />NOTES <br />CV <br />BLDG B & D- CLASSROOM AHUS <br />22 <br />314 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />3.20 <br />5.84 <br />MODULATING <br />1 <br />CV <br />BLDG B&D-AHU-D4,-D8,-D11,-B2-1 <br />4 <br />3/4 <br />CCV <br />3-WAY <br />NON ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />3.20 <br />5.84 <br />MODULATING <br />1 <br />CV <br />BLDG D-COMMON SPACE AHU-D13 <br />1 <br />718 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />5.20 <br />6.20 <br />MODULATING <br />1 <br />CV <br />BLDG D-COMMON SPACE AHU-1)I4, 132-13, -D2-14 <br />3 <br />7/8 <br />CCV <br />8-WAY <br />NON ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />5.20 <br />6.20 <br />MODULATING <br />2 <br />CV <br />BLDG C-CLASSROOM C 03 AHU <br />1 <br />314 <br />CCV <br />3-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />4.50 <br />7.19 <br />MODULATING <br />2 <br />CV <br />BLDG C -CLASSROOM C 04 AHU <br />1 <br />7/8 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />5.00 <br />7.32 <br />MODULATING <br />1 <br />CV <br />BLDG B - HC-B1 <br />1 <br />1-1/4 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />5.75 <br />4.30 <br />MODULATING <br />1 <br />CV <br />BLDG B - HC-B2 & BC-B10 <br />2 <br />314 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />1.36 <br />1.68 <br />MODULATING <br />1 <br />CV <br />BLDG B- HC-B3 <br />1 <br />3/4 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />1.00 <br />1.78 <br />MODULATING <br />1 <br />CV <br />BLDG B- HC-B4 <br />1 <br />1 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />4.00 <br />3.19 <br />MODULATING <br />1 <br />CV <br />BLDG B - HC-B5 <br />1 <br />3/4 <br />CCV <br />SWAY <br />NONANSISTAINLESS <br />STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />1.50 <br />1.93 <br />MODULATING <br />1 <br />CV <br />BLDG B- HG136 <br />1 <br />314 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />0.85 <br />1.81 <br />MODULATING <br />1 <br />CV <br />BLDG B -HC-B7 & HG-B8 <br />1 <br />314 <br />CCV <br />2-WAY <br />NON ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />1.12 <br />1.68 <br />MODULATING <br />1 <br />CV <br />BLDG B - HC-B9 <br />1 <br />34 <br />CCV <br />2-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />1.36 <br />1.80 <br />MODULATING <br />1 <br />CV <br />BLDG B-HC-B11 <br />1 <br />314 <br />CCV <br />3-WAY <br />NON -ANSI <br />STAINLESS STEEL <br />BELIMO <br />SPRING RETURN <br />NORMALLY OPEN <br />1 1.90 <br />1.78 <br />MODULATING <br />1 <br />M - CEILING SUPPLY DIFFUSER SCHEDULE <br />GENERAL NOTES: <br />SPECIFIC NOTES: <br />DESCRIPTION <br />PHYSICAL DIMENSIONS <br />PERFORMANCE <br />ACOUSTICAL <br />MAX AIR PRESSURE <br />SPECIFIC <br />EQUIPMENT <br />EQUIPMENT <br />QUANTITY <br />MANUFACTURER <br />MODEL <br />TYPE <br />MATERIAL <br />NECK SIZE <br />FAMILY SIZE <br />MAX AIR FLOW <br />DROP <br />MAX THROW <br />MOUNTING <br />FINISH <br />NO <br />NOTES <br />CLASSIFICATION <br />ID <br />(IN) <br />(IN) <br />(CFM) <br />(IN. W.C.) <br />(FT <br />GIRD <br />CD-1 <br />84 <br />TITUS <br />MCDI <br />MODULARCORE <br />STEEL <br />10 <br />24x24 <br />367 <br />0.05 <br />10.12-17 <br />T-BAR <br />STANDARD <br />18 <br />ai0 try <br />fe Of Your Building <br />McKINSTRY Co, LLC <br />SEATTLE: <br />5005 3RD AVENUE S <br />PO BOX 24567 <br />SEATTLE, WA 98124 <br />1-800-669-6223 <br />www.mckinstrv.com <br />PROJECT <br />MUKILTEO SD <br />PHASE 10 HVAC <br />IMPROVEMENTS <br />- HORIZON ES <br />222 W CASINO RD <br />EVERETT, WA 98204 <br />CONSULTANTS: <br />ISSUE <br />PERMIT SET <br />05/06/2022 <br />REGISTRATION: <br />�R oF�WAI yT�� <br />52771 Q <br />P01 �4'GISTS <br />G <br />`rS10NAL <br />ISSUES <br />SR ENGINEER: <br />L. HESS <br />DRAWN BY: <br />M. SAFONOV N. HOBURG A. PASSAS <br />QC BY: <br />L. HESS <br />JOB NO: <br />205557,004 <br />ISSUED ON: <br />0510612022 <br />SHEET TITLE: <br />MECHANICAL <br />SCHEDULES <br />SHEET NUMBER: <br />M-060 <br />