Laserfiche WebLink
u <br />I� <br />■ <br />COMBINER BOX PANEL SIZE CALCS <br />CIRCUIT # <br />NUMBER OF <br />MODULES <br />NUMBER OF <br />MICROINVERTERS <br />NOMINAL OUTPUT <br />CURRENT <br />TOTAL <br />125 % <br />TOTAL <br />COMBINED <br />TOTAL <br />BREAKER SIZE <br />CIRCUIT 1 (1 of 2) <br />4 <br />2 <br />X 2.46A <br />= 4.92A <br />x 1.25 <br />= 6.15A <br />= 12.40A <br />= 15A <br />CIRCUIT 1 (2 of 2) <br />4 <br />1 <br />5.OA <br />- 5.00A <br />x 1.25 <br />= 6.25A <br />CIRCUIT 2 (1 of 3) <br />1 <br />1 <br />X 1.23A <br />- 123A <br />1.25 <br />= 1.54A <br />= 10.86A <br />= 15A <br />CIRCUT 2 (2 of 3) <br />I <br />2 <br />1 <br />X 2.46A <br />- 2.46A <br />x 1.25 <br />- 3.08A <br />CIRCUT 2 (3 of 3) <br />4 <br />1 <br />5.OA <br />- 5.00A <br />xj 1.25 <br />= 6.25A <br />LOAD CALCS - TOTAL AMPS AVAILABLE <br />[BUS RATING 120% TOTAL MAIN BREAKER MAX BREAKER SIZE <br />200A X 1.2 = 240 200A = 40A <br />NOTES: <br />1. 200A UTILITY METER GLOBE ONLY. (EXISTING) <br />2. 200A LOAD CENTER. (EXISTING) <br />3. 30A RATED NON -FUSED LOCKABLE AC DISCONNECT. <br />(NEW) <br />v 4. 125A RATED COMBINER PANEL. (NEW) <br />ALL CONDUIT SIZES ARE MINIMUM SIZES <br />ALL WIRE SIZES ARE FOR COPPER WIRE <br />4 ZNSHINE ZXM6-NH120-360M MODULES 4 ZNSHINE ZXM6-NH120-360M MODULES <br />WITH HOYMILES HM-600 MICRO WITH HOYMILES HM-1200 MICRO <br />,) INVERTERS INVERTERS <br />(1 OF 2) (2 OF 2) <br />(4) (21 (1-) (4) (31 (21 <br />1 ZNSHINE ZXM6-NH120-360M MODULE 2 ZNSHINE ZXM6-NH120-360M MODULES 4 ZNSHINE ZXM6-NH120-360M MODULES <br />WITH HOYMILES HM-300 MICRO WITH HOYMILES HM-600 MICRO WITH HOYMILES HM-1200 MICRO <br />INVERTER INVERTERS INVERTERS <br />(1 OF 3) (2 OF 3) (3 OF 3) <br />7 <br />(1-) (2) (1-) (4) (31 (2) <br />Am <br />(1 <br />CIRCUIT #1 <br />(11 <br />—' CIRCUIT #2 <br />CONFIDENTIAL - THE INFORMATION CONTAINEI <br />IN THIS PACKET AND SUBSEQUENT CUTSHEET: <br />LG E. N <br />O SHALL NOT BE USED FOR THE BENEFIT OF <br />ANYONE OUTSIDE SOLGEN POWER. NEITHER <br />SHALL IT BE DISCLOSED TO OTHERS OUTSIDE <br />P 0 W E R THE RECIPIENT'S ORGANIZATION, EXCEPT IN <br />CONNECTION WITH THE SALE AND USE OF THE <br />RESPECTIVE EQUIPMENT, WITHOUT WRITTEN <br />CONSENT FROM SOLGEN POWER. <br />(2)12 AWG <br />(1)8 AWG EGC <br />(2)12 AWG <br />(1)8 AWG EGC <br />SOLGEN POWER <br />5100 ELM RD, <br />PASCO, WA 99301 <br />P: 509-931-1663 <br />t I r I <br />MAX AC OPERATING CURRENT CALCS FOR HM-1200 <br />#OFMICROINVERTERS1 MAX OUTPUT CURRENT MAX AC nPFRATII <br /># OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT <br />3 X 2.46A = 7.38A <br />MAX AC OPERATING CURRENT CALCS FOR HM-300 <br /># OF MICROINVERTERS MAX OUTPLIT CURRENT MAX AC C)PFRATINt; CI IRRFNT <br />rL <br />■ <br />MAX AC OPERATING TOTAL <br />CURRENT FOR HM-1200, 600, 300 <br />HM-1200 HM-600 HM-300 <br />10.00A + 7.38A + 1.23A = 18.61A <br />BREAKER SIZE CALCS <br />MAX AC OPERATING CURRENT <br />125 % <br />TOTAL <br />BREAKER SIZE <br />18.61A <br />x <br />1.25 <br />x 23.26A <br />= 25A <br />(2)8 AWG <br />(1)8 AWG EGC <br />4 <br />3 <br />(2)8 AWG <br />(1 )8 AWG EGC <br />`sw <br />Michael Lee <br />UTILITY METER (E) <br />1 <br />(RATIO <br />UTILITY <br />GRID (IT <br />(8AWG F2 (11 )8 AWG EGC <br />200A <br />MAIN SERVICE <br />DISCONNECT (E) <br />25A LOAD -SIDE - <br />SOLAR OCPD <br />(Opposite end of the main disconnect <br />on the busbar - NEC 705.12(B)(3) <br />EXISTING <br />WIRE 2--MAIN SERVICE PANEL (E) <br />L <br />DRAWN BY: DRAWING SCALE: <br />M M NOT TO SCA <br />DESIGN <br />DATE: <br />1 /27/2023 <br />3507 Oakes Ave, Everett, WA 98201 <br />MM <br />MM <br />MO <br />MM <br />