Laserfiche WebLink
August 18, 2014 <br /> Gibson Bluff <br /> L&A Job No. 14-056 <br /> Page 15 <br /> For walls with ascending backslope, an additional pressure of 0.75 pcf per degree of the <br /> backslope angle above horizon should be added to the above design pressures. To <br /> counter the above active or at-rest pressure, a passive lateral soil pressure of 300 pcf EFD <br /> may be used. This passive pressure value is applicable only to walls with a level or <br /> ascending backslope for a horizontal distance at least 1.5 times the wall height. To resist <br /> against sliding, the friction force between the footings and the subgrade soils may be <br /> calculated based on a coefficient of friction of 0.55. The above soil parameters are <br /> ultimate values based on a fully drained condition of the walls, and proper factors of <br /> safety should be applied in the design of the basement walls against sliding and <br /> overturning failures. The foundation walls should also be designed for seismic loading <br /> based on a 100-year seismic event. Based on the soil conditions in the detention vault <br /> area, we recommend the vault walls be designed for an invert triangular lateral soil <br /> pressure diagram with the pressure at the top of the triangle to be 10H psf for a 100-year <br /> seismic event, where H is the height from finish grade at or above the top of the wall to <br /> the bottom of footings in feet. A one-third increase in the above recommended allowable <br /> soil bearing pressure may be used when considering the seismic loading condition. <br /> A vertical drainage blanket, at least 12-inch-thick horizontally, consisting of clean, free- <br /> draining, pea gravel or washed gravel should be placed against the back of foundation <br /> walls to within 18 inches of the finish grade to prevent accumulation of groundwater <br /> behind and buildup of hydrostatic pressure against the walls. This drainage blanket fill <br /> should be compacted to a non-yielding state with a vibratory compactor. Structural fill <br /> should be used for the remaining wall backfill. The top 18 inches of the backfill may <br /> LIU & ASSOCIATES, INC. <br />