ELECTRICAL NOTES ELECTRICAL NOTES CONT. <br /> 1. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ANY/ALL ELECTRICAL WORK 22. ANY CUTTING OR PATCHING DEEMED NECESSARY FOR ELECTRICAL WORK IS THE ELECTRICAL <br /> INDICATED.ANY/ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND ANY/ALL CONTRACTORS RESPONSIBILITY AND SHALL BE INCLUDED IN THE COST FOR WORK AND <br /> APPLICABLE SPECIFICATIONS.IF ANY PROBLEMS ARE ENCOUNTERED BY COMPLYING WITH PERFORMED TO THE SATISFACTION OF THE'CONSTRUCTION MANAGER'UPON FINAL <br /> THESE REQUIREMENTS,CONTRACTOR SHALL NOTIFY'CONSTRUCTION MANAGER'AS SOON AS ACCEPTANCE. PE PSICO <br /> POSSIBLE,AFTER THE DISCOVERY OF THE PROBLEMS,AND SHALL NOT PROCEED WITH THAT <br /> PORTION OF WORK,UNTIL THE'CONSTRUCTION MANAGER'HAS DIRECTED THE CORRECTIVE 23. THE ELECTRICAL CONTRACTOR SHALL LABEL ALL PANELS WITH ONLY TYPEWRITTEN J TSN <br /> ACTIONS TO BE TAKEN. DIRECTORIES. o.o L Vm <br /> 2. THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FAMILIARIZE THEMSELVES WITH 24. DISCONNECT SWITCHES SHALL BE H.P.RATED HEAVY-DUTY,QUICK-MAKE AND QUICK-BREAK <br /> ANY/ALL CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATION INSTALLATION AND MAKE ENCLOSURES,AS REQUIRED BY EXPOSURE TYPE. <br /> PROVISIONS AS TO THE COST THEREOF.THE CONDITION OF EXISTING ELECTRICAL EQUIP.,LIGHT CORPORATE WORLD HEADQUARTERS <br /> FIXTURES,ETC.,THAT ARE PART OF THE FINAL SYSTEM,SHALL BE VERIFIED BY THE 25. ALL CONNECTIONS EXCEPT THE EV CHARGE CABLE TERMINATION IN THE CHARGE POST SHALL 700 ANDERSON HILL ROAD <br /> CONTRACTOR,PRIOR TO THE SUBMITTAL OF HIS BID.FAILURE TO COMPLY WITH THIS BE MADE WITH A PROTECTIVE COATING OF AN ANTI-OXIDE COMPOUND SUCH AS"NOALOX"BY PURCHASE NY 10577 <br /> PARAGRAPH WILL IN NO WAY RELIEVE CONTRACTOR OF PERFORMING ALL WORK NECESSARY IDEAL INDUSTRIAL INC.,COAT ALL WIRE SURFACES BEFORE CONNECTING.EXPOSED ALUMINUM <br /> FOR A COMPLETE AND WORKING SYSTEM. &COPPER SURFACES,INCLUDING GROUND BARS,SHALL BE TREATED-NO SUBSTITUTIONS. <br /> 3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC AND 26. ALL EXTERIOR AND INTERIOR ABOVE GROUND CONDUIT SHALL BE RIGID UNLESS SPECIFIED <br /> ALL CODES AND LOCAL ORDINANCES OF THE LOCAL POWER COMPANIES HAVING JURISDICTION OTHERWISE.ALL BURIED CONDUITS SHALL BE SCH 40 PVC UNLESS SPECIFIED OTHERWISE. <br /> AND SHALL INCLUDE BUT NOT BE LIMITED TO: <br /> 27. RACEWAYS:CONDUIT SHALL BE SCHEDULE 40 PVC,MEETING OR EXCEEDING NEMA TC2-2013. <br /> A.UL-UNDERWRITERS LABORATORIES THE CONTRACTOR SHALL PLUG AND CAP EACH END OF SPARE AND EMPTY CONDUITS AND <br /> B.NEC-NATIONAL ELECTRICAL CODE PROVIDE TWO SEPARATE PULL STRINGS-200 LBS TEST POLYETHYLENE CORD.ALL CONDUIT <br /> C.NEMA-NATIONAL ELECTRICAL MANUFACTURERS ASSOC. BENDS SHALL NOT BE LESS THAN SHOWN IN TABLE 2 CHAPTER 9 OF THE NEC.RGS CONDUITS <br /> D.OSHA-OCCUPATIONAL SAFETY AND HEALTH ACT WHEN SPECIFIED,SHALL MEET UL-6 FOR GALVANIZED STEEL.ALL FITTINGS SHALL BE SUITABLE <br /> E.SBC-STANDARD BUILDING CODE FOR USE WITH THREADED RIGID CONDUIT.COAT ALL THREADS WITH'BRITE ZINC'OR'GOLD <br /> F.NFPA-NATIONAL FIRE PROTECTION ASSOCIATION GALV'. <br /> pp <br /> 4 NT,BUT CONFIRM WIITTH'CONSTRUCTION MANAGER,ANY SIZES AND & <br /> EXACT 28. SUPPORT OF ALL ELECTRICAL WORK SHALL BE AS REQUIRED BY NEC. <br /> LOCATIONS OF ALL EQUIPMENT, BLACK VEATCH <br /> LOCATIONS WHEN NEEDED. 29. CONNECTORS FOR POWER CONDUCTORS:CONTRACTOR SHALL USE PRESSURE TYPE <br /> INSULATED TWIST-ON CONNECTORS FOR NO.10 AWG AND SMALLER.USE SOLDERLESS 11401 LAMAR AVENUE <br /> 5. EXISTING SERVICES:THE CONTRACTOR SHALL NOT INTERRUPT EXISTING SERVICES WITHOUT MECHANICAL TERMINAL LUGS FOR NO.8 AWG AND LARGER. OVERLAND PARK,KS 66211 <br /> WRITTEN PERMISSION OF THE OWNER. (913)458-2000 <br /> 30. THE CONTRACTOR SHALL PLACE TWO LENGTHS OF WARNING TAPE AT A DEPTH OF 12"BELOW <br /> 6. THE CONTRACTOR SHALL PAY FOR ANY/ALL PERMITS,FEES,INSPECTIONS AND TESTING.THE GROUND AND DIRECTLY ABOVE ELECTRICAL SERVICE CONDUITS.CAUTION TAPE TO READ <br /> CONTRACTOR IS TO OBTAIN PERMITS AND APPROVED SUBMITTALS PRIOR TO THE WORK "CAUTION BURIED ELECTRIC". <br /> BEGINNING OR ORDERING THE EQUIPMENT. <br /> 31. WHEN DIRECTIONAL BORING IS REQUIRED,CONTRACTOR SHALL INSTALL A LOOSE TONING WIRE <br /> 7. THE TERM"PROVIDE"USED IN CONSTRUCTION DOCUMENTS AND SPECIFICATIONS,INDICATES WITHIN INSTALLED CONDUIT TO ALLOW FOR IDENTIFICATION OF UNDERGROUND CONDUITS. PROJECT NO: 413739 <br /> THAT THE CONTRACTOR SHALL FURNISH AND INSTALL. DRAWN BY: JKR <br /> 32. ALL BOLTS SHALL BE STAINLESS STEEL. <br /> 8. THE CONTRACTOR SHALL CONFIRM WITH LOCAL UTILITY COMPANY ANY/ALL REQUIREMENTS CHECKED BY: NMB <br /> SUCH AS THE:LUG SIZE RESTRICTIONS,CONDUIT ENTRY,SIZE OF TRANSFORMERS,SCHEDULED 33. ALL MATERIALS AND EQUIPMENT SUPPLIED AND INSTALLED BY THE CONTRACTOR SHOULD BE <br /> DOWNTIME FOR THE OWNERS'CONFIRMATION,ETC.ANY/ALL CONFLICTS SHALL BE BROUGHT TO NEW AND UNUSED. <br /> THE ATTENTION OF THE CONSTRUCTION MANAGER,PRIOR TO BEGINNING ANY WORK. <br /> 9. CONDUCTORS:CONTRACTOR SHALL USE 98%CONDUCTIVITY COPPER OR ALUMINUM WITH TYPE GROUNDING NOTES <br /> (THWN-2)INSULATION,600 VOLT,COLOR CODED UNLESS SPECIFIED DIFFERENTLY ON DRAWINGS. <br /> 1. ALL HARDWARE SHALL BE STAINLESS STEEL 3/8"DIAMETER OR LARGER.ALL HARDWARE 18-8 <br /> 10. ALL WIRING INSTALLATIONS SHALL BE COMPLIANT WITH NEC ARTICLE 310.10 AND TO FOLLOW STAINLESS STEEL INCLUDING LOCK WASHERS,COAT ALL SURFACES WITH AN ANTI-OXIDANT <br /> MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. COMPOUND BEFORE MATING. <br /> 11. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS,CAST ALLOY WITH THREADED 2. FOR GROUND BOND TO STEEL ONLY:INSERT A CADMIUM FLAT WASHER BETWEEN LUG AND STEEL, 0 12/01/22 ISSUED FOR CONSTRUCTION <br /> HUBS IN WET/DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS. REV DATE DESCRIPTION <br /> COAT ALL SURFACES WITH AN ANTI-OXIDANT COMPOUND BEFORE MATING. <br /> 12. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF THE CONSTRUCTION. <br /> CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL 3. ENSURE THE WIRE INSULATION TERMINATION IS WITHIN 1/8"OF THE BARREL(NO SHINERS). yZ.HEjjR <br /> SYSTEM AND PROVIDE ALL REQUIREMENTS FOR THE EQUIPMENT TO BE PLACED IN PROPER <br /> WORKING ORDER.CONTRACTOR IS TO PROVIDE ALL ELECTRICAL EQUIPMENT UNLESS 4. ALL BELOW GRADE BONDS TO BE EXOTHERMIC WELDS OR IRREVERSIBLE COMPRESSION TYPE WASgI q <br /> OTHERWISE DIRECTED. CONNECTIONS LISTED FOR USE IN THE APPLICATION WHICH THEY ARE INSTALLED. S r.h <br /> x <br /> 13. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS, _ <br /> WORKMANLIKE MANNER.THE COMPLETED SYSTEM SHALL BE FULLY OPERATIONAL AND SUBJECT <br /> TO REGULATORY INSPECTION AND APPROVAL BY CONSTRUCTION MANAGER. <br /> a <br /> 14. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE �� �� 48406 ti9 �Q <br /> PROGRESS OF CONSTRUCTION. �� GISTER 11 <br /> SSjONAL EACs <br /> 15. CONTRACTOR SHALL GUARANTEE ANY/ALL MATERIALS AND WORK FREE FROM DEFECTS FOR A <br /> PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE. <br /> 12/1/2022 <br /> 16. THE CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ANY ADDITIONAL CHARGE <br /> AND SHALL INCLUDE THE REPLACEMENT OR THE REPAIR OF ANY OTHER PHASE OF THE IT ISA VIOLATION OF LAW FORANY PERSON,UNLESS <br /> INSTALLATION,WHICH MAY HAVE BEEN DAMAGED THEREIN. LICENSED PROF-I.NALENGINEDIRECTION <br /> R TOALTERrHIS <br /> DOCUMENT. <br /> 17. ADEQUATE AND REQUIRED LIABILITY INSURANCE SHALL BE PROVIDED FOR PROTECTION <br /> AGAINST PUBLIC LOSS AND ANY/ALL PROPERTY DAMAGE FOR THE DURATION OF WORK. <br /> 18. PROVIDE AND INSTALL CONDUIT,CONDUCTORS,PULL WIRES,BOXES,COVER PLATES AND WA-PEP01 <br /> DEVICES FOR ALL OUTLETS AS INDICATED. EVERETT <br /> 1808 MERRILL CREEK PKWY, <br /> 19. TRENCHING AND BACKFILL:THE CONTRACTOR SHALL PROVIDE FOR ALL UNDERGROUND EVERETT,WA 98203 <br /> INSTALLED CONDUIT AND/OR CABLES INCLUDING EXCAVATION AND BACKFILLING AND <br /> COMPACTION.REFER TO GENERAL SITE WORK NOTES. <br /> 20. MATERIALS,PRODUCTS AND EQUIPMENT,INCLUDING ALL COMPONENTS THEREOF,SHALL BE SHEET TITLE <br /> NEW AND SHALL APPEAR ON THE LIST OF U.L.APPROVED ITEMS AND SHALL MEET OR EXCEED <br /> THE REQUIREMENTS OF THE NEC,NEMA AND IEEE. GENERAL NOTES 3 <br /> 21. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OR MANUFACTURES CATALOG INFORMATION OF <br /> ANY/ALL LIGHTING FIXTURES,SWITCHES AND ALL OTHER ELECTRICAL ITEMS FOR APPROVAL BY <br /> THE CONSTRUCTION MANAGER PRIOR TO INSTALLATION. SHEET NUMBER <br /> GN-3 <br />