ELECTRICAL SPECIFICATIONS GENERAL NOTES
<br /> �
<br /> .�p EXp�0il�
<br /> PART 1-GENERAL 1. THE ELECTRICAL DRAWINGS,SPECIFICATIONS AND GENERAL NOTES
<br /> DESCRIBE THE RECOMMENDED SCOPE OF WORK AND THE DOCUMENTS
<br /> 1.01 COORDINATION OF TRADES:SCHEDULE AND COORDINATE WORK WITH THAT OF OTHER DIVISIONS AND SECTIONS. SHALL BE USED FOR THE PURPOSE OF BIDDING,BUILDING DEPARTMENT
<br /> 1.02 GUARANTEE IN WRITING THE ELECTRICAL INSTALLATION,AND ALL WORK UNDER THIS SECTION,FOR A PERIOD OF ONE YEAR FROM THE DATE REVIEW,AND TO SECURE THE NECESSARY CONSTRUCTION PERMIT ONLY. A .A
<br /> OF FINAL ACCEPTANCE BY THE OWNER AGAINST ALL EVIDENCE OF IMPERFECT WORKMANSHIP OR FAILURE OR MALFUNCTION OF MATERIALS. N6 4511 111 U.
<br /> 2. BRANCH CONTROL CIRCUITING AND WIRE COUNT MAY NOT BE INDICATED ON
<br /> PART 2-PRODUCTS THESE PLANS.CONTRACTOR IS RESPONSIBLE TO COMPLETE THE BRANCH 11
<br /> CIRCUIT WIRING IN ACCORDANCE WITH PLAN NOTES AND AS PERMITTED BY
<br /> 2.01 MATERIALS AND EQUIPMENT AUTHORITY.CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS AS A PART OF ^
<br /> A. MATERIAL FURNISHED UNDER THIS CONTRACT,UNLESS OTHERWISE NOTED,SHALL BE NEW,FREE FROM DEFECTS AND SHALL RECORD DRAWING SUBMITTAL TO ARCHITECT AND AUTHORITY HAVING
<br /> CONFORM WITH THE STANDARDS OF UL JURISDICTION(ANJ). ♦'I
<br /> B. VOLTAGE.AMPERE.AND OTHER RATINGS OF EQUIPMENT SHALL BE SUITABLE FOR USE INTENDED.DISCONNECT SWITCHES SHALL ����A.® y'� G�
<br /> BE PROPERLY HORSEPOWER RATED AND SUITABLE FOR VOLTAGE,AND AMPERE RATING OF LOAD 3. ELECTRICAL INSTALLATION SHALL COMPLY WITH THE LOCALLY ADOPTED,AS
<br /> 'iv_
<br /> K��
<br /> C. THE DRAWINGS GENERALLY INDICATE THE RACEWAY SIZE,THE NUMBER,SIZE,AND INSULATION TYPE OF CONDUCTORS TO BE NATIONAL ELECTRICAL CODE ADAPTED BY THE JURISDICTION AND ANY
<br /> PROVIDED AND INSTALLED.WHERE THESE ITEMS DO NOT MEET MINIMUM APPLICABLE CODES,FOR EQUIPMENT BEING SERVED, LOCAL SUPPLIMENTS.
<br /> COMPLY AS REQUIRED AT NO ADDITIONAL COST.
<br /> 2.02 RACEWAYS 4. ALL EQUIPMENT SHOWN IS NEW,CONTRACTOR FURNISHED AND INSTALLED,
<br /> A. GALVANIZED RIGID CONDUIT(GRC);INCLUDING ELBOWS AND COUPLINGS. UNLESS OTHERWISE NOTED.IF CONTRACTOR PROPOSED TO SUBSTITUTE ®p !/� PANDA RESTAURANT GROUP INC.
<br /> B. INTERMEDIATE METAL CONDUIT(IMC);INCLUDING ELBOWS AND COUPLINGS. SPECIFIC EQUIPMENT SPECIFIED,HE SHALL SUBMIT HIS REQUEST FOR /t 1683 Walnut Grove Ave.
<br /> C. ELECTRIC METALLIC TUBING(EMT)WITH FITTINGS OF PRESSED STEEL OR MALLEABLE IRON,COMPRESSION TYPE WITH INSULATED CONSIDERATION TO THE OWNER AND ENGINEER PRIOR TO THE BID IN /� p
<br /> THROATS. WRITING.ALL SUSSTFTIONS MUST BE REVIEWED BY THE ENGINEER.SUCH ®gyp ma`s Rosemead,California
<br /> D. RIGID NON-METALLIC CONDUIT(PVC)U.L.LABELED SCHEDULE 40 P.V.C. REVIEW SHALL NOT RELIEVE THE CONTRACTOR FROM COMPLYING WITH THE lY� a (``�� 91770
<br /> 2.03 DEVICE AND JUNCTION BOXES:INCLUDE PLASTER RINGS,COVERS.AND KO SEALS AS REQUIRED. REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS.THE CONTRACTOR IL+ Telephone:626.799.9898
<br /> 2.04 WIRE AND CABLE:UNLESS OTHERWISE NOTED,WIRE AND CABLE SHALL BE SOFT DRAWN,ANNEALED COPPER.WIRE SIZES NO.8 AND LARGER SHALL BE RESPONSIBLE AT HIS OWN EXPENSE FOR ANY CHANGE RESULTING Farsbtde:626.3728288
<br /> AND CONDUCTORS SERVING MOTORS AND SUBJECT TO VIBRATIONS SHALL BE STRANDED CABLE INSULATION TO BE THWNTTHHN,JACKETED FROM HIS PROPOSED SUBSTITIONS WHICH AFFECT OTHER PARTS OF HIS if)
<br /> 90C INSULATED WIRE.PROVIDE WIRE COLOR IDENTIFICATION:NEUTRAL WIRE-WHITE,LIVE WIRE- BLACK,RED,BLUE ON 120/208 VOLT OWN WORK OR SUBSTITUTIONS WHICH AFFECT OTHER PARTS OF HIS OWN
<br /> SYSTEM;NEUTRAL WIRE-GREY,UVE WIRE-BROWN,ORANGE YELLOW ON 277/480 VOLT SYSTEM:GROUND- GREEN. WORK OR THE WORK OF OTHER CONTRACTORS.
<br /> 2.05 ADDED PANELS TO BE PANELBOARDS-LOAD CENTERS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY APPROVED.
<br /> 2.06 SERVICE ENTRANCE AND DISTRIBUTION GEAR BY G.E.,SQUARE"D.,CUTLER HAMMER/SIEMENS ONLY.INTERIOR PANELBOARDS SHALL BE 5. THE ELECTRICAL DRAWINGS,CONDUIT RUNS,WIRING AND ELECTRICAL NI ideas,designs,arrangement and plans indurated or
<br /> RECESSED WITH FLANGED/REMOVABLE SCREW-ON COVER.SURFACE MOUNTED PANELBOARDS OR HINGED/FLUSH COVERS NOT ALLOWED. INFORMATION ARE DIAGRAMMATIC ONLY.DO NOT SCALE THE ELECTRICAL represented by EA410wing are the property el Panda
<br /> 2.07 SWITCHBOARDS:COPPER BUSSING WITH FULL CAPACITY NEUTRAL ALUMINUM ALLOWED WHEN APPROVED BY ARCHITECT. DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. Express Inc.and were aeakd Er use on Ibis speak project
<br /> 2.11 120/208 VOLT AND ]/480 VOLT WITH THERMALAND OARDS:3 PHASE,4 IMRE,COPPER
<br /> BUS,COMPOSED
<br /> OF AN ASSEMBLY OF OROFF POLICE MOLDED CASE 6. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT MC CABLE SHALL NOT BE USED, PREWIRED MC CABLE WHIPS FROM None of these ideas,designs,arrangements or plan may be
<br /> CIRCUIT BREAKERS
<br /> 2.13 SAFETY SWITCHES:FUSED,HEAVY DUTY,HORSEPOWER RATED. LOCATIONS OF ALL LIGHTING FIXTURES.CEILING MOUNTED OUTLETS AND LIGHTING FIXTURES ARE ACCEPTABLE WHEN SUPPLIED WITH THE or, o the
<br /> 1lanyperel Panda or corporation
<br /> without the written Remission al Panda Express Inc
<br /> 2.14 STARTERS.CONTACTORSS,PUSHBUTTON L,HAND-OFF-ONSWITC PROVIDE S SHOWN AND ASICES,REQUIRED BY RELAFURNIS COMPLETE S.THERMALOVHPILOTSGHTS, EQUIPMENT. FIXTURE AND NO LONGER THAN 72". _
<br /> AUXILIARY CONTACTS,PUSH BUTTONS,HAND-OFF-ON SWITCHES,CONTROL DEVICES,AND OVERLOAD RELAYS.THERMAL OVERLOADS TORE
<br /> SIZED PER MANUFACTURERS RECOMMENDATIONS.AMBIENT COMPENSATE ALL HEATERS EXPOSED TO HIGH TEMPERATURE OR INSTALLATION 7. ALL DEVICE MOUNTING HEIGHTS AND EXACT LOCATIONS SHALL BE
<br /> OUTSIDE. COORDINATED WITH ARCHITECTURAL DRAWINGS AND ELEVATIONS PRIOR TO
<br /> 2.16 NAMEPLATES:PROVIDE BLACK LAMICOID NAMEPLATES WITH 3/16"HIGH WHITE ENGRAVED LETTERS ON PANELS,SWITCHBOARDS,MAINS AND ROUGH-IN. REVISIONS:
<br /> SUBMAINS,DISTRIBUTION EQUIPMENT,REMOTE SAFETY SWITCHES,CIRCUIT BREAKERS,TIME SWITCHES,CONTACTORS,AND STARTERS.
<br /> 2.17 WIRING ADEVICES
<br /> HUBBELL OR COMPARABLE LEVITONORBRYANT:WHITE AND GREY IN COLOR-AS NOTED ON DRAWINGS.15 MAP DEVICES ALLOWED 8 CEILIT ING SYSTEM.FIXTURES CONTRACTOR'SALL BE THE TO LOCATEDINDAMPOR LOCATIONS
<br /> WETSHALLBE ELECTRICIAN TO PROVIDE STAINLESS STEEL COVER PLATES FOR
<br /> ONLY WHEN SPECIFICALLY DENOTED ON ELECTRICAL CONSTRUCTION DRAWINGS. LISTED AND LABELED FOR USE IN SUCH LOCATIONS. ALL LOW VOLTAGE JUNCTION BOXES.
<br /> LIM
<br /> B. TOGGLE SWITCHES:SINGLE POLE-HUBBELL 1221-20A,120/277V,THREE WAY-HUBBELL 1223-20A,120/277V,FOUR WAY-HUBBELL
<br /> 1224-20A,120/277V. 9. ALL RECESSED LIGHTING FIXTURES,PANELBOARDS,SWITCHES,ETC.,
<br /> C. RECEPTACLES:DUPLEX GROUNDING TYPE,SPECIFICATION GRADE,125 VOLT,20 AMPERES,SINGLE PHASE,HUBBELL NO.5262 OR MOUNTED IN FIRE RATED STRUCTURES SHALL BE ENCLOSED WITH AN
<br /> COMPARABLE. APPROVED ENCLOSURE CARRYING THE SAME FIRE RATING AS THE �L /•.
<br /> D. GROUND FAULT INTERRUPTER TYPE RECEPTACLE:DUPLEX GROUNDING TYPE,SPECIFICATION GRADE,125 VOLT,20 AMPERES, STRUCTURE. NO UNDER SLAB ELECTRICAL WORK ALLOWED UNLESS OTHERWISE
<br /> SINGLE PHASE,5 mA GROUND TRIP,FEED THROUGH CONSTRUCTION. I V R ELECTRICAL �7
<br /> 2.18 DEVICE PLATES:LEXAN(STA-KLEEN),SMOOTH FINISH IN STAINLESS STEEL AND WHITE-AS NOTED ON PLANS.MULTI-GANG OUTLET PLATES 10. PORTIONS OF THE CEILING SYSTEMS MAY BE INACCESSIBLE,THEREFORE, NOTED ON PLAN.
<br /> SHALL BE USED FOR MULTI-GANG BOXES. THE CONTRACTOR SHALL STRATEGICALLY LOCATE ACCESS BOXES,ETC.,
<br /> 2.19 NOT USED. WHICH SHALL BE READILY ACCESSIBLE.ALL LIGHTING FIXTURE WIRING,
<br /> 2.20 LIGHTING FIXTURES BALLASTS,J-BOXES,ETC.SHALL BE ACCESSIBLE FROM FIXTURE OPENING.
<br /> A. PROVIDE FIXTURES PER SCHEDULE WITH ALL PARTS INCLUDING PLASTER FRAMES FOR RECESSED FIXTURES AND FITTINGS . ISSUE DATE:
<br /> NECESSARY TO COMPLETELY AND PROPERLY INSTALL FIXTURES. 11. ALL WIRING AND ELECTRICAL EQUIPMENT INSTALLED FOR MECHANICAL AND
<br /> B. LAMPS:INCANDESCENT LAMPS BY G.E.,SYLVANIA,OR WESTINGHOUSE,130 VOLT,EXTENDED LIFE LAMPS.FLUORESCENT LAMPS BY PLUMBING EQUIPMENT SHALL BE IN ACCORDANCE WITH MECHANICAL AND
<br /> G.E.,SYLVANIA,PHILLIPS,OR WESTINGHOUSE.MINIMUM CRI OF 80.WATTAGE AND TYPES AS REQUIRED BY FIXTURE. PLUMBING SPECIFICATIONS AND ASSOCIATED DRAWINGS.CONTRACTOR ,
<br /> SHOULD OBTAIN THE REQUIRED MECHANICAL AND PLUMBING DRAWINGS AND
<br /> PART 3-EXECUTION PROVIDE ALL EQUIPMENT,RACEWAYS,WIRING,ETC.,AS INDICATED THEREON
<br /> AS PROVIDED UNDER THE ELECTRICAL WORK.
<br /> 3.01 GENERAL THE ENTIRE ELECTRICAL SYMBOLS LIST
<br /> A. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE MADE IN A NEAT,APPROVED,FINISHED,AND SAFE MANNER. 12 ALL FINAL CONNECTIONS TO OWNER FURNISHED EQUIPMENT SHALL BE MADE
<br /> LIM
<br /> B. INSPECT AND MAKE TIGHT ALL CONNECTIONS FOR ALL EQUIPMENT,INCLUDING FACTORY CONNECTIONS.TORQUE ALL BY THE CONTRACTOR,UNLESS OTHERWISE NOTED.VERIFY ELECTRICAL
<br /> CONNECTIONS PER MANUFACTURER'S RECOMMENDATIONS, CHARACTERISTICS AND U.L.USTING PRIOR TO CONNECTION.
<br /> C. LIGHTING FIXTURES INSTALLED AND USED FOR LIGHTING DURING CONSTRUCTION SHALL BE RELAMPED WITH NEW LAMPS JUST NOTE:ALL DIMENSIONS GIVEN ARE TO DEVICE CENTERLINES.CONTRACTOR TO COORDINATE ALL INSTALLATIONS.
<br /> PRIOR TO FINAL ACCEPTANCE OF THE PROJECT. 13. THE CONTRACTOR SHALL VERIFY THE LOAD INPUT VOLTAGE OF ALL
<br /> D. INSTALL SEISMIC RESTRAINT DEVICES FOR ALL CEILING MOUNTED EQUIPMENT,I.E.FLUORESCENT LAY-IN FIXTURES.PROVIDE GRID EQUIPMENT PRIOR TO INSTALLATION.ACCEPTING ANY EQUIPMENT POWER DISTRIBUTION RECEPTACLES&COMMUNICATIONS OUTLETS
<br /> CLIPS AND 912 SLACK WIRES FROM FIXTURE CORNERS TO STRUCTURE. RESULTING IN A LOAD INCREASE SHALL BE THE RESPONSIBILITY OF ® PANELBOARD
<br /> 3.02 RACEWAYS CONTRACTOR. m DUPLEX CONVENIENCE OUTLET,20A,125V,MTD @18"AF.F.U.N.O. DRAWN BY:
<br /> A. INSTALL COMPLETE RACEWAY SYSTEMS FOR ALL ELECTRICAL CONDUCTORS INCLUDING TELEPHONE,SIGNAL,CONTROL,AND S II SINGLE-POLE SWITCH,MANUAL MOTOR STARTER W SIMPLEX CONVENIENCE OUTLET,20A,125V,MTD @ 18'A.F.F.U.N.O.
<br /> OTHER SYSTEMS. 14. ELECTRICAL OUTLETS ON OPPOSITE SIDES OF FIRE RATED WALLS AND 0._, J-BOX(WITH FLEX CONNECTION TO EQUIPMENT.)
<br /> B. UNLESS OTHERWISE NOTED,INSTALL ALL RACEWAYS CONCEALED.WHERE IT IS NOT FEASIBLE TO CONCEAL RACEWAYS,INSTALL PARTITIONS MUST BE SEPARATED BY DISTANCE OF 24 IN.HORIZONTALLY,IN DUPLEX CONVENIENCE OUTLET MOUNTED 3"ABOVE COUNTERTOP
<br /> AS DIRECTED BY ARCHITECT. ACCORDANCE WITH I.B.C.SEC.711 3.2.OPENINGS IN FIRE RATED WALLS Ep DISCONNECT SWITCH,WITH RATING AS SHOWN ON PLANS BACKSPLASH OR APPROXIMATELY 44"A.F.F.
<br /> C. INSTALL EXPOSED RACEWAYS TO RUN PARALLEL OR AT RIGHT ANGLES TO STRUCTURAL BUILDING LINES WITH NEAT BENDS AND GREATER THAN 16 SQ.IN.MUST BE FIRE STOPPED. a COMBINATION DISCONNECT SWITCH/MOTOR STARTER FURNISHED BY J. GFCI DUPLEX CONVENIENCE OUTLET,20A,125V,5 mA TRIP,MTD@ 18" PANDA PROJECT IF: 1098
<br /> NEATLY OFFSET INTO TERMINATIONS. ELECTRICAL CONTRACTOR
<br /> D. IN EMPTY RACEWAY PROVIDE AND INSTALL A NO.14 NYLON DRAG LINE. 15. PROVIDE AN ADDITIONAL JUNCTION BOX(SIZE AS REQUIRED)WHERE THE A.F.F.U.N.O.
<br /> E. INSTALL RACEWAYS WITH APPROVED HEAVY DUTY SUPPORTS,STRAPS,HANGERS,CONNECTORS,AND COUPLINGS AS REQUIRED NUMBER OF CONDUCTORS EXCEEDS THE MAXIMUM ALLOWED FOR A GIVEN /LI'\ BRANCH CIRCUITRY CONCEALED IN WALL OR CEILING WITH ARCH PROJECT#:
<br /> TO MAINTAIN AN APPROVED INSTALLATION. JUNCTION POINT OR OUTLET. ADDITIONAL#12 INSULATED GND.U.N.O.HACHURES INDICATE NUMBER GFCI DUPLEX CONVENIENCE OUTLET MOUNTED 3"ABOVE
<br /> LL
<br /> F. DO NOT INSTALL CONDUIT RACEWAYS IN CONCRETE SLABS. OF CURRENT CARRYING CONDUCTORS.'X'INDICATES ADDITIONAL COUNTERTOP BACKSPLASH OR APPROXIMATELY 44'AF.F.
<br /> H. MINIMUM CONDUIT SIZE TO BE 3/4'U.N.O. 16. CONDUCTORS SHALL BE COPPER THHN/THWN 600 VOLT INSULATION UNLESS INSULATED,ISOLATED GROUND CONDUCTORS. V TELEPHONE OUTLET.PROVIDE FLUSH J-BOX @+18'AFF N.ND W/1'
<br /> 3.03 GALVANIZED RIGID CONDUIT(RC)ALL RACEWAYS SHALL BE GRC EXCEPT AS NOTED OR SHOWN.CONDUIT,ELBOWS,STANDARD COUPLINGS OTHERWISE NOTED.USE PROPER TEMPERATURE RATING OF CONDUCTORS BRANCH CIRCUITRY HOMERUN TO PANEL AS NOTED ON PLANS CONDUIT WI PULL WIRE TO MANAGER'S STATION.'2/SUBSCRIPT
<br /> SHALL BE HOT DIPPED GALVANIZED RIGID STEEL.IF PARTITIONS OR WALLS ARE SOLID CONCRETE OR ARE GROUTED SOLID WITH CONCRETE BASED ON THE AMBIENT AIR TEMPERATURE WHERE CONDUCTORS ARE INDICATES WALL PHONE AT 54•AFF. 2
<br /> OR MORTAR, RIGID STEEL CONDUIT SHALL BE USED, BEING USED.HIGHER AMPACITY CONDUCTOR AND LARGER RACEWAY SHALL ,--., INDICATES EXTERIOR UNDERGROUND WIRE RUNS.
<br /> 3.04 INTERMEDIATE METAL CONDUIT(IMC)IMC RACEWAY AND APPROVED FITTINGS WHERE PERMITTED BY APPUCABLE CODES AND REGULATIONS BE PROVIDED TO OFFSET THE AMPACITY CORRECTION FACTORS AS V DATA OUTLET.PROVIDE FLUSH J-BOX @+18"A.F.F.U.N.O WI 1. r GARY WANG
<br /> MAYBE USED IN UEU OF RIGID STEEL CONDUIT,WHERE INSTALLED ABOVE FINISH GRADE AND ABOVE CONCRETE SLABS ON GRADE. INDICATED IN NEC TABLE 310 AND ELSEWHERE IN CODE. - .LIGHTING&LIGHTING CONTROLS CONDUIT WITH PULL WIRE TO MANAGER'S STATION. Cam
<br /> 3.05 ELECTRIC METALLIC TUBING(E
<br /> MT)MT)EMT MAY BE USED WHERE CONCEALED IN AREAS ABOVE CEILINGS,FURRED SPACES,PARTTIDNS OR V COMBINATION TEL/DATA OUTLET.PROVIDE FLUSH J-BOX @+18'AFF 4. ^' G &ASSOCIATES.INC.
<br /> WALLS.ALSO MAY BE EXPOSED,WHEN NOT IN HAZARDOUS AREAS,AREAS SUBJECT TO PHYSICAL DAMAGE,OR WHEN DIRECTLY EXPOSED TO 17. ALL FLUORESCENT BALLASTS AND LAMPS SHALL BE CAUFORMA ENERGY LIGHTING FIXTURE SUBSCRIPT LETTER DENOTES FIXTURE TYPE AS U.N.O WI I"CONDUIT WITH PULL WIRE TO MANAGER'S STAIN.
<br /> RAIN OR WASH-DOWN. COMMISSION(CEC)CERTIFIED ENERGY SAVING TYPE DESCRIBED IN LIGHT FIXTURE SCHEDULE.
<br /> 17 3.06 FLEXIBLE METAL CONDUIT(FLEX)USE FLEXIBLE CONDUITS FOR CONNECTIONS TO MOTORS.WHERE SUBJECT TO MOVEMENT OR VIBRATION, 1 1000 Corporate Center Dr.,SUIN 550
<br /> T.V.SYSTEM DATA OUTLET.PROVIDE FLUSH J-BOX @+78'AF.F.U.N.O Monter Park,CA 01750
<br /> AND LIQUID TIGHT WHERE EXPOSED TO MOISTURE OR OIL 18. DO ALL DRILLING,CUTTING,CHANNEUNG AS REQUIRED FOR ELECTRICAL SINGLE-POLE SWITCH @ 44'AF.F.U.N.O.LOWER CASE LETTER °y
<br /> W/1' ADJACENTC WITH PULL WIRE, MANAGER'SARECEPTACLE
<br /> WHEN 1
<br /> 3.07 RIGID NONMETALLIC CONDUIT PVC SCHEDULE 40 MAY BE INSTALLED FOR DIRECT BURIAL RACEWAYS WHERE INSTALLED WITH MINIMUM WORK AND INDICATED OR HEREIN SPECIFIED.ALL HOLES,CURBS,ETC.,IN s ° DENOTES FIXTURE CONTROL 300V.20ATEL(BOB)289-b999 fA%:(626)768-7101
<br /> COVERAGE PER NEC TABLE 300-5. FLOORS,CEILINGS AND WALLS SHALL BE PATCHED,UNLESS INDICATED SHOWNFERTOR RECEPTACLE
<br /> OR MOUNTING MOUNT AT RECEPTACLE HEIGHT. Mtp;//www.ta,ywan9.00m
<br /> TWO-POLE SWITCH 44•A.F.F,U.N.O.LOWER CASE LETTER REFER RECEPTACLE FOR HEIGHT.
<br /> 3.08 OUTLET,PULL AND JUNCTION BOXES OTHERWISE.PALM ALL EXPOSED ELECTRICAL RACEWAYS,CABINETS, S 2 @
<br /> A. UNLESS OTHERWISE SHOWN OR AS DIRECTED PRIOR TO INSTALLATION,OUTLET BOXES SHALL GENERALLY BE PLACED AT THE ENCLOSURES AND FITTING TO MATCH IN COLOR TO ADJACENT SURFACES IN DENOTES FIXTURE CONTROL 300V.20A. ® SPECIAL PURPOSE RECEPTACLE MTD.@ 18'A.F.F.U.N.O.,AMPERAGE
<br /> FOLLOWING HEIGHTS,CENTER OF BOX TO FINISHED FLOOR LEVEL. FINISHED AREAS.(PROTECT UL LISTINGS LABELS FROM PAINT). S P SINGLE-POLE LIGHT SWITCH WITH PILOT LIGHT @ 44.A.F.F.U.N.O.300V. AND PHASE AS NOTED ON PLANS,NEMA CONFIGURATION AS REQ'D.
<br /> B. WALL SWITCHES:44".
<br /> C. CONVENIENCE RECEPTACLES:18'(OR 4'ABOVE COUNTERS)AND/OR AS NOTED.(SIMILAR TYPE OUTLETS SHALL BE MOUNTED AT 19. SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS,CEILINGS,FLOORS, ' 0 ISOLATED GROUND DUPLEX CONVENIENCE OUTLET(ORANGE),
<br /> SAME HEIGHT IN EACH AREA).GROUNDING PIN AT TOP. ETC.,TO MAINTAIN THE FIRE RATING.FURNISH AND INSTALL FIRE RATED SD OCCUPANCY SENSOR SWITCH WITH OFF CONTROL,AND ADJUSTABLE 20A.,125V.,MTD @ SIB'A.F.F.
<br /> 3.09 CONDUCTORS(COPPER ONLY) ENCLOSURE FOR ALL EQUIPMENT PENETRATING INTO FIRE RATED SETTINGS FOR TIME OFF DELAY,FOOTCANDLE LEVEL,AND MASKING.
<br /> A. USE SPECIFIED COLOR SCHEDULE FOR ALL WIRING.WHERE LARGE CONDUCTORS ARE NOT AVAILABLE IN COLORS.IDENTIFY WITH ENVELOPS,SPACES ETC. WATTSTOPPER OR EQUAL MOUNT AT 44"A.F.F.U.N.O.USE PW-100 FOR DOUBLE DUPLEX CONVENIENCE OUTLETS UNDER COMMON COVER
<br /> PERMANENT COLORED TAPE AT ALL TERMINATIONS,JUNCTION BOXES,ETC.COLOR CODING PER NEC. OFFICES/CONE/ETC.,WI-200 FOR CLASSROOMS/LARGE ROOMS/ETC.
<br /> B. MAKE TAPS.JOINTS,SPLICES.AND OTHER CONNECTIONS WITH FIXTURE CONNECTORS. 20.EMERGENCY LIGHTING SHALL BE PROVIDED PER U.B.C.AND SHALL BE 4* ISOLATED DOUBLE DUPLEX CONVENIENCE OUTLETS(ORANGE)
<br /> C. DO NOT INSTALL WIRING OR PULL WIRES,IN RACEWAYS UNTIL RACEWAY SYSTEM IS COMPLETE,CLEAN AND DRY AND FREE OF ALL DESIGNED TO PROVIDE MINIMUM REQUIRED FOOTCANDLES AND LUMENS. CEILING MOUNT DUAL TECHNOLOGY ULTRASONIC/P.I.R.MOTION 20A„72SV.
<br /> FOREIGN MATERIALS.LUBRICATE AS REQUIRED WITH SPECIFIED LUBRICANT. PROVIDE ADDITIONAL EMERGENCY ILLUMINATION AS REQUIRED BY A SENSOR TO CONTROL POWER TO ROOM SWITCHES-WATTSTOPPER
<br /> D. MINIMUM CONDUCTOR SIZE TO BE 812 CU.THWN. INSPECTION AUTHORITIES HAVING JURISDICTIONS. #DT-300(WITH POWER PACK)OR EQUAL En SPEAKER
<br /> 3.10 LIGHTING FIXTURES
<br /> A. LEAVE FIXTURES AND LAMPS CLEAN OF ALL DIRT,DUST,GREASE SPOTS AND DEBRIS AND ALL GLASS,PLASTIC AND OTHER 21. ALL ELECTRICAL EQUIPMENT SHALL BE BRACED OR ANCHORED TO RESIST A ABBREVIATIONS FIRE ALARM
<br /> COMPONENTS,UNSCRATCHED AND UNBROKEN. HORIZONTAL FORCE ACTING IN ANY DIRECTION USING THE FOLLOWING
<br /> B. FIT AND ADJUST ALL FIXTURES.WHERE STRUCTURAL CONDITIONS,PARTITIONS,FURNITURE,SHELVING.AND AIR CONDITIONING CRITERIA.[NON HEALTH CARE FACILITY INCLUDE OSHPD NOTES FOR HEALTH A AMPERES M.C.B. MAIN CIRCUIT BREAKER
<br /> DIFFUSERS INTERFERE WITH THE LIGHTING FIXTURES AT LOCATIONS SHOWN,NOTIFY ARCHITECT IN WRITING AND RELOCATE AT NO CARE FACILITY] AL ALUMINUM MLO. MAIN LUGS ONLY Q MANUAL PULL STATION WITH KEYED RESET.MOUNT UNIT AT 44'A.F.F.
<br /> ADDITIONAL COST AS DIRECTED. FIXED EQUIPMENT ON GRADE: 33%OF A.F.F. ABOVE FINISHED FLOOR MTD. MOUNTED ALIGN WITH LIGHT SWITCH IF APPLICABLE.
<br /> C. FIXTURES WITH FINISH TRIM OR LENS FRAMES SHALL BE GASKETED AND BAFFLED TO PREVENT LIGHT LEAKS.INSTALL SO THAT NO OPERATING WEIGHT A.F.G. ABOVE FINISHED GRADE P. POLE ,,��..,,
<br /> LIGHT LEAKS EXIST.D.FIXTURES MOUNTED DIRECTLY ON COMBUSTIBLE LOW-DENSITY CEIUNGS SHALL BE UL APPROVAL FIXED EQUIPMENT ON STRUCTURE: 50%OF C. CONDUIT SW. SWITCH LJ XENON STROBE UNIT MOUNTEDATO"R. OR 6"BELOW CEILING
<br /> FOR THIS CONDITION AND BE PLAINLY MARKED SO INDICATING. OPERATING WEIGHT CB CIRCUIT BREAKER T.M.B. TELEPHONE MOUNTING BOARD (WHICHEVER IS LOWER).MUSSTTMEET OR EXCEED A.D.A.REQUIREMENTS. PANDA EXPRESS
<br /> 3.11 GROUNDING EMERGENCY POWER AND COMMUNICATION&EQUIPMENT CU. COPPER TYP. TYPICAL /±q
<br /> A. GROUNDING FOR DISTRIBUTION EQUIPMENT,EQUIPMENT AND MATERIALS WITH ELECTRICAL CONNECTIONS,ELECTRIC MOTOR ON GRADE: 50%OF DISC. DISCONNECT U.N.O. UNLESS NOTED OTHERWISE LJ COMBINATION XENON STROBE AND HORN/CHIME UNIT MOUNTED AT
<br /> FRAMES,ELECTRIC RACEWAY AND RELATED EQUIPMENT,SHALL BE EFFECTIVELY AND PERMANENTLY GROUNDED IN OPERATING WEIGHT F. FUSE V. VOLTS 80'A.F.F.OR 6"BELOW CEILING(WHICHEVER IS LOWER).UNIT MUST CHULA VISTA CROSSING
<br /> ACCORDANCE WITH PERTINENT SECTIONS OF ARTICLE 250 OF NEC.RESISTANCE TO GROUND SHALL NOT EXCEED 10 OHMS. EMERGENCY POWER AND COMMUNICATION ON GFI GROUND FAULT W. WIRE MEET OR EXCEED A.D.A.REQUIREMENTS. 1820 MAIN CT
<br /> B. ALL RACEWAYS SHALL HAVE AN APPROVED SIZED,INSULATED.STRANDED COPPER GROUNDING TYPE CONDUCTOR. STRUCTURE: 75%OF
<br /> CURRENT INTERRUPTER W.P. WEATHERPROOF
<br /> GND. GROUND XFMR TRANSFORMER CHULA VISTA,CA 91911
<br /> C. WHERE RACEWAYS CONNECT TO A CONCENTRIC K.O.PROVIDE GROUNDING LOCKNUT OR BUSHING AND BOND WIRE EXTENDED AND OPERATING WEIGHT H.P. HORSE POWER 0 PHASE I FACP1 FIRE ALARM CONTROL PANEL MOUNT TOPOF UNIT AT 72'AF.F.
<br /> BONDED TO ENCLOSURE,SIZE AS PER NEC. k 1000
<br /> 3.12 DITCHING,EXCAVATION AND BACKFILLNG:PERFORM ALL DITCHING,EXCAVATION AND BACKFILLING REQUIRED FOR THE ELECTRICAL WORK. FOR FLEXIBLE MOUNTED EQUIPMENT USE 2X THE ABOVE VALUES. �FMPI FIRE ALARM ANNUNCIATION PANEL.MOUNT TOP OF UNIT AT 72'AF.E.
<br /> PROVIDE AND MAINTAIN ALL SHEATHING,BRACING AND PROPER GUARDS FOR PREVENTION OF ACCIDENTS. SIMULTANEOUS VERTICAL FORCE-USE 1/3 X HORIZONTAL FORCE [f PHOTO ELECTRIC TYPE SMOKE DETECTOR.
<br /> 3.13 UTILITY COMPANY SERVICE CONTRACTOR TO BE RESPONSIBLE FOR COORDINATING AND PROVIDING REQUIRED WORK FOR SUPPLYING
<br /> ELECTRICAL POWER AND COMMUNICATIONS UTILITIES TO THE PROJECT. CONDUIT,BUSDUCT,CABLE TRAY,WIREWAYS,ETC.,SHALL BE BRACED IN ‘. DUCT MOUNTED PHOTO ELECTRIC SMOKE DETECTOR.
<br /> 3.14 FINAL INSPECTION TESTS TEST SYSTEM FOR SHORTS AND GROUNDS.FAULTY WIRING SHALL BE REMOVED AND REPLACED.AFTER SYSTEM IS ACCORDANCE WITH"OUILDELINES',PUBLISHED BY SMACNA AND EPIC. 0 RATE OF RISE HEAT DETECTOR.
<br /> CONNECTED COMPLETE,TEST FOR INSULATION RESISTANCE RESISTANCE LOWER THAN OUTLINED IN THE NEC,MANUFACTURER'S DATA,ETC.,
<br /> SHALL BE REMOVED AND REPLACED.ANY DEVICE,APPARATUS OR FIXTURE UNDER THIS CONTRACT SHOWING SUBSTANDARD READINGS SHALL ' NOTICE ^ 000
<br /> BE REMOVED AND REPLACED AS DIRECTED BY THE ARCHITECT. THESE DRAWINGS ARE SUBJECT TO AN APPROVAL OF THE BUILDING LC_
<br /> 3.15 LABEL ALL RECEPTACLES WITH 3/16'HIGH BLACK LETTERING ON CLEAR TAPE.IF THE RECEPTACLE IS BLACK OR BROWN,PROVIDE WHITE DEPARTMENT,FIRE MARSHAL,UTILITY COMPANY AND OTHER AGENCIES
<br /> LETTERING ON CLEAR TAPE LABEL TO BE NEATLY CENTERED IN THE TOP SPACE OF THE COVERPLATE,AND INDICATE THE SERVING PANEL AUTHORITY HAVING JURISDICTION(AHJ).BY THE ACT OF SUBMITTING A
<br /> AND CIRCUIT ORIGIN. BID PROPOSAL FOR WORK,THE CONTRACTOR HAS REVIEWED THE PLANS
<br /> THOROUGHLY AND ACCEPT FULL RESPONSIBILITY OF PLAN CORRECTIONS
<br /> AND ASSOCIATED CONSTRUCTION COSTS REQUIRED
<br /> ELECTRICAL SYMBOLS
<br /> ELECTRICAL SPECIFICATIONS 3 GENERAL NOTES 2 ELECTRICAL SYMBOLS 1 SPECIFICATIONS,NOTES