Laserfiche WebLink
37. Sheet A0.6 with the revision of the construction type to VA doors #29, <br /> #33, #34 &#35 changed to 20 min rating of frames and doors. <br /> 2. Emergency egress lighting should be provided: <br /> a. Within the garage (Section 1008.3.1). Sheets A3.1 and A3.1LS added <br /> emergency lighting to the parking garage. <br /> b. Within the electrical room (Section 108.3.3). Sheet A3.1 added emergency <br /> lighting. <br /> c. At the exterior landings at the exterior exit doorways (Section 1008.3.2, Item 5). <br /> Sheets A3.1 and A3.1LS added exterior emergency lights, these will be <br /> on inverters. <br /> 3. The stairs and landings within the Type I portion of the building should be of <br /> noncombustible construction. Section 1011.7 Construction type has been revised <br /> to 4 story VA <br /> Energy <br /> 1. The minimum sone rating of 1.0 should be shown for the whole house fans. IMC Section <br /> 403.8.6.5 Sheet A0.2 under heat source added Whole house fans min. sone <br /> rating of 1.0 per IMC Section 403.8.6.5 <br /> 2. The requirements of WSEC C402.5.1.2 for testing of the air barrier should be shown on <br /> the plans. Sheet A0.1 added: Testing of the air barrier per WSEC C4O2.5.1.2 <br /> STRUCTURAL <br /> 1. Under separate letter to be forwarded upon completion. <br /> Sincerely, <br /> t‘a____ <br /> Charles E. Morgan <br />