Laserfiche WebLink
Geotechnical Engineering Evaluation NGA File No. 1014317 <br /> Zerzura Townhome Development November 9,2017 <br /> Everett,Washington Page 8 <br /> Lateral loads may be resisted by friction on the base of the footing and passive resistance against the <br /> subsurface portions of the foundation. A coefficient of friction of 0.35 may be used to calculate the base <br /> friction and should be applied to the vertical dead load only. Passive resistance may be calculated as a <br /> triangular equivalent fluid pressure distribution. An equivalent fluid density of 200 pounds per cubic foot <br /> (pcf) should be used for passive resistance design for a level ground surface adjacent to the footing. This <br /> level surface should extend a distance equal to at least three times the footing depth. These recommended <br /> values incorporate safety factors of 1.5 and 2.0 applied to the estimated ultimate values for frictional and <br /> passive resistance, respectively. To achieve this value of passive resistance, the foundations should be <br /> poured "neat" against the native medium dense soils or compacted fill should be used as backfill against <br /> the front of the footing. We recommend that the upper one foot of soil be neglected when calculating the <br /> passive resistance. <br /> Retaining Walls <br /> The lateral pressure acting on subsurface retaining walls is dependent on the nature and density of the soil <br /> behind the wall,the amount of lateral wall movement which can occur as backfill is placed,wall drainage <br /> conditions, and the inclination of the backfill. For walls that are free to yield at the top at least one <br /> thousandth of the height of the wall (active condition), soil pressures will be less than if movement is <br /> limited by such factors as wall stiffness or bracing (at-rest condition). We recommend that walls <br /> supporting horizontal backfill and not subjected to hydrostatic forces, be designed using a triangular earth <br /> pressure distribution equivalent to that exerted by a fluid with a density of 40 pcf for yielding (active <br /> condition)walls,and 60 pcf for non-yielding(at-rest condition)walls. <br /> These recommended lateral earth pressures are for a drained granular backfill and are based on the <br /> assumption of a horizontal ground surface behind the wall for a distance of at least the subsurface height <br /> of the wall, and do not account for surcharge loads. Additional lateral earth pressures should be <br /> considered for surcharge loads acting adjacent to subsurface walls and within a distance equal to the <br /> subsurface height of the wall. This would include the effects of surcharges such as traffic loads,floor slab <br /> loads, slopes, or other surface loads. We could consult with the structural engineer regarding additional <br /> loads on retaining walls during final design, if needed. <br /> The lateral pressures on walls may be resisted by friction between the foundation and subgrade soil, and <br /> by passive resistance acting on the below-grade portion of the foundation. Recommendations for <br /> frictional and passive resistance to lateral loads are presented in the Foundations subsection of this <br /> report. <br /> NELSON GEOTECHNICAL ASSOCIATES,INC. <br />