Laserfiche WebLink
e ' s <br /> � e � <br /> � � � � <br /> (F-9 CONTINUED) <br /> Noted on submission 002 received OS/29/02 that fi�e alarm plans will be submitted <br /> separately. Please note that a review of sheet E2.0 indicated that fire alazm strobe <br /> devices would be r.;quired in Staff Lounge 133A and Behavioral Health 135A and <br /> I36A. <br /> 9.1 � Not Approved 12/10/02 -Based on plans received 11/27/02. Provide alarm strobes in <br /> Behavioral Health 135A and 136A. Section 1106.15.2, Unifortn Building Code, <br /> Washington State Amendments <br /> Approved 06/OT/03—Strobes have been provWed. <br /> 9.2 � Revised construction drawings received 11/27/02 show a Patient Toilet 125A which <br /> the alarm drawings do not show. Please reconcile this on the alazm drawings. lt <br /> appears that a str:+be device is installed in this area,please verify. Sxtion l 106.15.2, <br /> ti��iform Building Code,Washington State Amendments <br /> Approved 06/01/03—Drawings have been revis�d to ahow�paHmt tofkG <br /> A 10 � Provide revised drawings revising Naliway l 12A to a deadend of twenty feet or less. <br /> WAC 246-320-525(2), and Section 1004.2.6, Uniform Building Code <br /> 10.1 Not Approved 06/1 I/02 - Provide revised mechanical and electrical drawings <br /> coordinated with Sheet A-3.1 (rcv). WAC 246-320-505(2)(b) <br /> Approved 11J09/02-Mechanical and electrical drawinga revbed to match. <br /> A 1 I � Provide revised drawings with proper dimensions to show that Ezams 113A, 118A, <br /> and 119A have at least 80 square feet of floor area. WAC 246-320-815(5)(d)(i) <br /> 11.1 Not Approved 06/11/02 - Provide revised drawings. Upon scaling the cabinetry in <br /> Exatn Room 119A it appears that this room would contain less than eighty square feet <br /> of floor area. <br /> Approved 1?J09/02- Revised Sheets A3.1 (rev) and A6.2 show Exam Room 119A <br /> with a floor area of at least eighty square[ee� <br /> A 12 0 Provide revised drawings showing how patient privacy will be provided at Exams <br /> 118A, 119A, 128A, and Treatment 132A. WAC 246-320-245(2)(a)(i) <br /> Approved 06/11/02-Revised Sheet A•3.1 shows door swing changed at Rooms <br /> 11S and 119,and cubicle curtains added at Rooms 128 and 132 to provide <br /> patient privacy. <br /> G <br /> Pagc 5 of 5 Plan Review Comrt�ents for Projecl N W48 <br /> Review Kcy: A=Architat F=Firc&Life Sahty S=Seniterian M=Mxhaniul/qectricd C=Conference Nae <br />